Manual  RS8DZ702  ©  Danfoss  03-2012                                                                               EKC 202 / 302 

Fault message

Alarms

In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you 

push the top button in this situation you can see the alarm report in the display. If there are 

further push again to see them.

There are two kinds of error reports - it can either be an alarm occurring during the daily opera

-

tion, or there may be a defect in the installation.

A-alarms will not become visible until the set time delay has expired. 

E-alarms, on the other hand, will become visible the moment the error occurs.

(An A alarm will not be visible as long as there is an active E alarm).

Here are the messages that may appear:

1 = alarm

A1: High temperature alarm

High t. alarm

A2: Low temperature alarm

Low t. alarm

A4: Door alarm

Door Alarm

A5: Information. Parameter o16  is expired

Max Hold Time

A15: Alarm. Signal from DI input 

DI1 alarm

A45: Standby position (stopped refrigeration via r12 or DI input)

Standby mode

A59: Case cleaning. Signal from DI input

Case cleaning

A61: Condenser alarm

Cond. alarm

E1: Faults in the controller

EKC error

E6: Fault in real-time clock. Check the battery / reset the clock.

-

E27: Sensor error on S5

S5 error

E29: Sensor error on Sair

Sair error

When copying settings to or from a copying key with functions o65 or o66, the following infor

-

mation may appear:

0: Copying concluded and OK

4: Copying key not correctly mounted

5: Copying was not correct. Repeat copying

6: Copying to EKC incorrect. Repeat copying

7: Copying to copying key incorrect. Repeat copying

8: Copying not possible. Order number or SW version do not match

9: Communication error and timeout

10: Copying still going on

(The information can be found in o65 or o66 a couple of seconds after copying has been 

started).

Alarm destinations

The importance of the individual alarms 

can be defined with a setting (0, 1, 2 or 3)

Warning ! Direct start of compressors *

To prevent compressor breakdown parameter c01 and c02 should be set according to suppliers requirements or in general :

Hermetic Compressors c02 min. 5 minutes

Semihermetic Compressors c02 min. 8 minutes and c01 min. 2 to 5 minutes ( Motor from 5 to 15 KW )

* ) Direct activating of solenoid valves does not require settings different from factory (0)   

Содержание EKC 202B

Страница 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Страница 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Страница 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Страница 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Страница 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Страница 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Страница 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Страница 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Страница 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Страница 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Страница 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Страница 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Страница 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Страница 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Страница 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Страница 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Страница 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Страница 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Страница 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Страница 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Отзывы: