Defrost

Defrost control

The controller contains a timer function that is zeroset after each defrost start.

The timer function will start a defrost if/when the interval time is passed.

The timer function starts when voltage is connected to the controller, but it is displaced the first 

time by the setting in d05.

If there is power failure the timer value will be saved and continue from here when the power 

returns.

This timer function can be used as a simple way of starting defrosts, but it will always act as 

safety defrost if one of the subsequent defrost starts is not received.

The controller also contains a real-time clock. By means of settings of this clock and times for the 

required defrost times, defrost can be started at fixed times of the day. If there is a risk of power 

failure for periods longer than four hours, a battery module should be mounted in the controller. 

(only possible in EKC 202)

Defrost start can also be accomplished via data communication, via contact signals or manual 

start-up.
All starting methods will function in the controller. The different functions have to be set, so that 

defrosts do not ”come tumbling” one after the other.

Defrost can be accomplished with electricity, hot gas or brine.

The actual defrost will be stopped based on time or temperature with a signal from a tempera

-

ture sensor.

Defrost method

Here you set whether defrost is to be accomplished with electricity or "non". 

During defrost the defrost relay will be cut in.

When gas defrosting the compressor relay will be cut in during defrost.

d01

Def. method

Defrost stop temperature

The defrost is stopped at a given temperature which is measured with a sensor (the sensor is 

defined in d10).

The temperature value is set.

d02

Def. Stop Temp

Interval between defrost starts

The function is zeroset and will start the timer function at each defrost start. When the time has 

expired the function will start a defrost.

The function is used as a simple defrost start, or it may be used as a safeguard if the normal 

signal fails to appear.

If master/slave defrost without clock function or without data communication is used, the inter

-

val time will be used as max. time between defrosts.

If a defrost start via data communication does not take place, the interval time will be used as 

max. time between defrosts.

When there is defrost with clock function or data communication, the interval time must be set 

for a somewhat longer period of time than the planned one, as the interval time will otherwise 

start a defrost which a little later will be followed by the planned one.

In connection with power failure the interval time will be maintained, and when the power 

returns the interval time will continue from the maintained value.

The interval time is not active when set to 0.

d03

Def Interval

(0=off)

Max. defrost duration

This setting is a safety time so that the defrost will be stopped if there has not already been a 

stop based on temperature or via coordinated defrost.

(The setting will be the defrost time if d10 is selected to be 0)

d04

Max Def. time

Time staggering for defrost cut ins during start-up

The function is only relevant if you have several refrigeration appliances or groups where you 

want the defrost to be staggered in relation to one another. The function is furthermore only 

relevant if you have chosen defrost with interval start (d03).

The function delays the interval time d03 by the set number of minutes, but it only does it once, 

and this at the very first defrost taking place when voltage is connected to the controller.

The function will be active after each and every power failure.

d05

Time Stagg.

Drip-off time

Here you set the time that is to elapse from a defrost and until the compressor is to start again. 

(The time when water drips off the evaporator).

d06

DripOff time

Delay of fan start after defrost

Here you set the time that is to elapse from compressor start after a defrost and until the fan 

may start again. (The time when water is “tied” to the evaporator).

d07

FanStartDel

Fan start temperature

The fan may also be started a little earlier than mentioned under “Delay of fan start after defrost”, 

if the defrost sensor S5 registers another allowable value than the one set here.

d08

FanStartTemp

Fan cut in during defrost

Here you can set whether fan is to operate during defrost.

0: Stopped (Runs during pump down)

1: Running (stopped during  "fan delay")

2: Running during pump down and defrost. After that stopped

d09

FanDuringDef

Defrost sensor

 

Here you define the defrost sensor.

0: None, defrost is based on time

1: S5

2: Sair

d10

DefStopSens.

Содержание EKC 202B

Страница 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Страница 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Страница 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Страница 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Страница 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Страница 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Страница 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Страница 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Страница 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Страница 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Страница 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Страница 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Страница 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Страница 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Страница 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Страница 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Страница 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Страница 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Страница 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Страница 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Отзывы: