Instructions  RI8AS767  ©  Danfoss  01/2005 

EKC 101

Controller application setting parameters 

        

Code No.: 084B7020, SW = 3.0x., 084B7021, SW = 3.0x

Quick Guide

Setting and read-off parameters

Parameter 

codes

Min. value

Max. value

Factory

setting 

3

)

Actual

setting

Temperatur controller, temperature

-60(0)°C

50(99)°C

0°C

Thermostat

Differential 

1

)

r1

1 K

20 K

2 K

Max. limitation of set temperature

r2

-59(1)°C

50(99)°C

50°C

Min. limitation of set temperature

r3

-60(0)°C

49(99)°C

-60°C

Adjustment of temperature indication

r4

-20 K

20 K

0.0 K

Temperature unit (°C/°F). 084B7021 only

r5

-

-

°C

Compressor

Min. ON-time

c1

0 min

15 min

0 min

Min. OFF-time

c2

0 min

15 min

0 min

Cut-in frequency on sensor fault 

2

)

c3

0 %

99 %

0 %

Defrost

Defrost stop temperature

d2

0°C

25°C/OFF

OFF

Interval between defrost starts

d3

OFF

48 hour

8 hour

Max. defrost duration

d4

0 min

99 min

45 min

Delay of display view after defrost stop

d5

0 min

15 min

0 min

Defrost after strart-up

084B7020

d6

ON

99 min

OFF

084B7021

ON

240 min

OFF

Miscellaneous

Delay of outputsignal after start-up

o1

0 min

15 min

0 min

Access code

o5

OFF

99

OFF

Used sensor type Pt/Ptc. 084B7021 only

o6

-

-

Ptc

Refrigeration or heat (rE=refrigeration, HE = heat)

o7

rE

HE

rE

Fault code display

Fault in controller

Er

Disconnected room sensor

Er

Short-circuited room sensor

Er

�����������������������������

�������

�������

��������������������������������������

����������

�����������

�����

�������

���������

����

��������

������

����������

����������

������

������

������������

��������������

���������

����������

��������

�������

���������

�������

���������

�����
�����

�����
�����

���

�����

������

������

������

���

�����

�����
�����

�����
�����

��������

������

��

�����
�����

�����
�����

����������

����������

�����������������

�����
�����

��������

�����������

�����

�����

���

������

������
������

�������

�����

����������

���������

������

����

��������

�������������

������������

��������

���������

���������

����������

���������

���������

�������

���������

���������

������

���������

�����

�������

������

���������
����������

�������

�����

������������

��������

��������

�������

���������

��������

���������

�����
�����

�����
�����

����

�����
�����

�����
�����

�����
�����

English

( )  Values stated in parenthesis, are only possible if the setting o7 = HE.

1

)  Refrigeration (o7 = rE):

 

The relay closes when the room temperature exceeds 

 

the setting value and differential.

 

Heat (o7 = HE):

 

The relay closes when the room temperature drops to the setting value less 
the differential

2

)  After start-up and throughout three days and nights this value is used by 

the controller. Afterwards the controller is capable by   itself to calculate the 
average value of previous cut-in times. 

3

)  The factory setting has been indicated for standard units 084B7020 and 

084B7021. See also page 1. If the code number is a different one, the factory 
setting will be changed as per agreement.

Содержание EKC 101

Страница 1: ...en Warensicherheitslogs berhitzungsregelung Ne jamais utiliser ce capteur pour le contr le de valeurs utilis es pour s curit aliments enregistrement une r gulation de surchau e El sensor no se debe ut...

Страница 2: ...r 2 s bet tigen Beide Tasten gleichzeitig bet tigen R gulateur lectronique EKC 101 pour montage sur tableau Montage Voir page 1 Connexion lectrique Voir page 1 ainsi que le diagramme lectrique sur l a...

Страница 3: ...lse af displayvisning efter afrimningsstop d5 0 min 15 min 0 min Afrimning efter opstart 084B7020 d6 ON 99 min OFF 084B7021 ON 240 min OFF Diverse Forsinkelse af udgangssignal ved opstart o1 0 min 15...

Страница 4: ...0 min 15 min 0 min Defrost after strart up 084B7020 d6 ON 99 min OFF 084B7021 ON 240 min OFF Miscellaneous Delay of outputsignal after start up o1 0 min 15 min 0 min Access code o5 OFF 99 OFF Used se...

Страница 5: ...in Wert Max Wert Werkseinstel lung3 Aktuelle Einstellung Temperaturregler Temperatur 60 0 C 50 99 C 0 C Thermostat Di erenz 1 r1 1 K 20 K 2 K Begrenzung des Einstelltemperatur Maximalwerts r2 59 1 C 5...

Страница 6: ...lage actuel R gulateur de temp 60 0 C 50 99 C 0 C Thermostat Di rentiel 1 r1 1 K 20 K 2 K Limite max de temp rature de r glage r2 59 1 C 50 99 C 50 C Limite min de temp rature de r glage r3 60 0 C 49...

Страница 7: ...ar la temp despues de terminar el deses carche d5 0 min 15 min 0 min Desescarche al arrancar 084B7020 d6 ON 99 min OFF 084B7021 ON 240 min OFF Otros Retardo de la se al de salida despu s de un arranqu...

Страница 8: ...99 min 45 min Ritardo visualizzazione display dopo ne sbrinamento d5 0 min 15 min 0 min Sbrinamento all avviamento 084B7020 d6 ON 99 min OFF 084B7021 ON 240 min OFF Varie Ritardo segnale di uscita al...

Отзывы: