manualshive.com logo in svg
background image

Preliminary Considerations
Before energizing the control system, 
review your application carefully. What would happen if your
system overshoots – will damage result?

In an application where the load moves freely and cannot impact against anything or be crushed by the
actuator, overshoot can be tolerated during the adjustment of the loop.

However, in a clamping application, for example, overshoot could damage the actuator or the load being
clamped.
Stop and ask yourself – "Will my adjustments cause damage if not done properly?" If so, you may have
to modify the equipment for safety reasons so that it can tolerate over-positioning, overspeed, or higher-
than-planned forces during adjustments.
Caution: 

A bad setting of the PID parameters may cause the drive to oscillate.

An oscilloscope and a means of generating a square wave (signal generator or system controller) is
required in order to tune a closed loop controller. To adjust the controller parameters, the command
signal into the amplifier should continuously switch between 10-30% and 70-80%. Each signal level
should have a dwell time of several seconds (Figure 2).

Before installing the card, the potentiometers P, I, and D should be at the fully counter clockwise position
and the switches on the card should be set based on the application described in the "Application Notes"
section.

Finally, install the card and connect the command and feedback signals based on the appropriate option
described in the "Control Input Option" section.
Caution: 

If the feedback signal is not of the proper polarity, your load will promptly "run away" when the

command signal is applied. This is because the feedback is being added to, not subtracted from, the command
signal at the summing junction, producing a constantly increasing error signal.

Tuning Procedure

1. Connect a monitoring device, such as an oscilloscope or an XY recorder to the COMMAND INPUT, and

the FEEDBACK signals (see "Control Input Options").
Caution: 

Care should be taken when taking measurements using TP2. If this test point should become

grounded, the feedback command will change in turn causing unintended operation.

Do not attempt to visually "eyeball" the results of the adjustment. Visual observation of the actuator is
not accurate enough. If you do not know how to operate the monitoring device, seek the assistance
of someone who DOES know how to use it.

2. Energize the system and be sure the servo valve has been mechanically nulled.
3. Apply the step input repeatedly, and slowly increase the Proportional Gain of the amplifier a little at a

time while observing the system response (via the feedback signal).

A position control system, for example, will respond as shown in Figure 3.

As Proportional Gain is increased, the step input will give increasingly faster response. Eventually the
gain will reach a value where the input step will cause the actuator to just barely reach the desired
position.

Continue increasing the Proportional Gain until the system achieves the position that the step input
should produce, as shown in Figure 4.

4. When the Proportional Gain is set high enough so that the step input causes the desired position to

be achieved, measure the response time using the time base of monitoring instrument.

5. Now, continue to raise the Proportional Gain until a moderate overshoot occurs, as shown in Figure 5.
6. Begin increasing the DERIVATIVE Gain now, a little at a time, while observing the response carefully.

The overshoot should begin to reduce as Derivative Gain is increased.

Continue increasing the Derivative Gain, and applying the step input, until the overshoot is
eliminated (Figure 6).

Installation Guide

Servo Amplifier

PID Set-Up Procedure

 

14 | 

©

 Danfoss | August 2023

BC459665217198en-000101

Содержание EEA-PAM-591-A-10

Страница 1: ...Installation Guide Servo Amplifier EEA PAM 591 A 10 www danfoss com ...

Страница 2: ...Revision history Table of revisions Date Changed Rev August 2023 First edition 0101 Installation Guide Servo Amplifier 2 Danfoss August 2023 BC459665217198en 000101 ...

Страница 3: ...mplifier Discussed Operating Data Amplifier Settings Amplifier Set up Application Notes Control Input Options PID Set Up Procedure Accessory Products Installation Guide Servo Amplifier Contents Danfoss August 2023 BC459665217198en 000101 3 ...

Страница 4: ...and front panel adjustments by referring to the Amplifier Settings section 3 Set up the amplifier card current limits and null adjustments by referring to the Amplifier Set Up section 4 Decide on your application needs position control velocity control force control etc and the characteristic of your command feedback input signals voltage or current Then set the switches on the amplifier card inst...

Страница 5: ... 2 and S2 3 are used to activate the Integral Gain stage and switches S2 4 S2 5 and S2 6 are used to activate the Derivative Gain stage see switch descriptions for details The Proportional Gain can be used to influence system stiffness and possibly accuracy This stiffness is typically described as system response The Derivative Gain provides a means for system damping This damping is effective in ...

Страница 6: ...ct the amplitude of this signal while potentiometer P12 will adjust the frequency factory set at 200 hz The amplifier is factory set for 200 ma output however if desired the maximum output capability can be reduced via on board jumper JP1 The amplifier provides three jumper positions labeled A B and C When jumper JP1 is in the C position the amplifier can output 200 ma 100 ma when in the B positio...

Страница 7: ...rt circuit protected 1 mv ma short circuit protected Edge connector monitor points P I D output monitor Pre amp output monitor At pin B18 10 v at 5 ma At pin Z26 6 v at 2 ma Input bias 0 to 10 vdc Output bias 0 to 12 of full scale output Current limiters 0 to full scale output current Dither Amplitude Frequency 0 to 20 of full scale output current 50 to 400 hz Proportional Gain 1 v v to 20 v v Int...

Страница 8: ...olt Switch S2 3 should never be closed at the same time as this switch S2 3 I Gain Enable Used to control the Integral Gain stage input Set closed the integrator is disabled Set open in conjunction with S2 1 or S2 2 closed the integrator is enabled Switch S2 1 and switch S2 2 should never be closed at the same time as this switch Note If the Integral Gain is not used close S2 3 and ground the inte...

Страница 9: ... range See switch description for range settings Too much Integral Gain may cause oscillations Factory set fully CCW D Gain Affects the amount of Derivative Gain that is applied to the control signal Providing D Gain stage is enabled see switch descriptions Ajusted fully CCW the Derivative Gain is 05 volt sec volt in the low range and 3 volt sec volt in the high range Adjusted fully CW the Derivat...

Страница 10: ...djust output bias for 0 000v 1mv 1 ma output current Adjusting Current Limiters The purpose for setting the current limiters is to establish a relationship between maximum control signal amplitude and maximum valve current This procedure will utilize the input bias as on board command source to set the current limits 1 While monitoring front panel test point TP1 adjust input bias for 10v To utiliz...

Страница 11: ...sition control utilizing full P I D Typical velocity or pressure control Typical force control utilizing P and D Installation Guide Servo Amplifier Application Notes Danfoss August 2023 BC459665217198en 000101 11 ...

Страница 12: ... ratio Switch S1 2 can be set to either A or B Refer to switch description Option 2 In this configuration command and feedback signals are voltages of the same polarity For this configuration the ratio pot should be adjusted fully CCW When using this configuration care must be taken that switches S1 1 and S1 2 are not set to the same position In this example the command is not inverted so switch S...

Страница 13: ...ent loop signal must be calibrated If the 4 20 ma signal is to be summed with a single ended control signal Ex 0 to 10v apply 4 ma s and adjust the input bias so test point TP1 reads 0 00v If the signal is to be summed with a double ended control signal Ex 10v apply 12 ma s and adjust the input bias for 0 00v at test point TP1 Installation Guide Servo Amplifier Control Input Options Danfoss August...

Страница 14: ...ing error signal Tuning Procedure 1 Connect a monitoring device such as an oscilloscope or an XY recorder to the COMMAND INPUT and the FEEDBACK signals see Control Input Options Caution Care should be taken when taking measurements using TP2 If this test point should become grounded the feedback command will change in turn causing unintended operation Do not attempt to visually eyeball the results...

Страница 15: ...he Integral Gain to eliminate any steady state error Remember that you want the Integral Gain to be disabled RESET during the dynamic part of the motion cycle If Integral Gain is improperly timed the overshoots will return This is usually caused by the interaction between the Derivative and Integral terms as they fight each other for control If Integral Gain is set too high you may even lose contr...

Страница 16: ...ching desired command level Figure 5 Moderate overshoot Figure 6 Eliminated overshoot by adding Derivative Gain Installation Guide Servo Amplifier PID Set Up Procedure 16 Danfoss August 2023 BC459665217198en 000101 ...

Страница 17: ...Figure 7 Better response using additional P and D Gain Installation Guide Servo Amplifier PID Set Up Procedure Danfoss August 2023 BC459665217198en 000101 17 ...

Страница 18: ... of 3U height Connector DIN 41612 F48 female Connections Screw terminals Dimensions 5 1 in x 5 7 in x 2 2 in Assembly order number 732683 Female edge connector for 19 rack Style Adaptable into rack housing Connector DIN 41612 F48 female Connections Solder terminals Dimensions 3 74 in x 1 15 in x 69 in Assembly order number 508178 Command and ramp generator EEA DSG 453 A 10 Supply voltage 24 vdc 4 ...

Страница 19: ...anfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading Shanghai Co Ltd Building 22 No 1000 Jin Hai Rd Jin Qiao Pudong New District Shanghai China 201206 Phone 86 21 2080 6201 Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its produ...

Отзывы: