MENU > Settings > Control parameters, circulation pump(s)
V out max. (A333.2 / A333.3)
12165
Circuit
Setting range
Factory setting
1
0 . . . 100 %
100 %
The output voltage for controlling the speed of the circulation pump can be
limited to a maximum value.
See also "V out min".
0 - 100:
The value in % expresses the maximum voltage
for controlling the analogue output for the speed
control of the circulation pump.
Example:
A setting of 60 % means that the output voltage will be 6 volt as a
maximum.
The setting of "V.out min" has priority over "V.out max".
MENU > Settings > Control parameters, circulation pump(s)
V out min. (A333.2 / A333.3)
12167
Circuit
Setting range
Factory setting
1
0 . . . 100 %
0 %
The output voltage for controlling the speed of the refill pump can be limited
to a minimum value.
See also "V out max"..
0 - 100:
The value in % expresses the minimum voltage
for controlling the analogue output for the speed
control of the circulation pump.
Example:
A setting of 15 % means that the output voltage will be 1.5 volt as a
minimum.
The setting of "V.out min" has priority over "V.out max".
VI.GU.T2.02
© Danfoss | 2017.09 | 99
Operating Guide ECL Comfort 310, application A333