MENU > Settings > Refill water
Change duration
12311
Circuit
Setting range
Factory setting
1
OFF / 1 . . . 60 days
7 days
The number of days between refill water pump change-over.
OFF:
The automatic refill water pump change-over is disabled.
1 - 60:
The automatic refill water pump change-over is enabled.
X
= Time
# 1 # = Change duration
The "Change duration" has no influence when only one refill water
pump is selected in "No. of pumps" (ID no. 11326).
MENU > Settings > Refill water
Pressure des.
11321
Circuit
Setting range
Factory setting
1
0.2 . . . 25.0 bar
3.0 bar
Setting of desired pressure at S10 in order to ON / OFF control the refill
pump(s) P3 / P4.
See also 'Pressure diff.'
0.2 - 25.0:
Set the desired pressure at S10.
The parameter "Pressure des." is also used in application A333.2 /
A333.3 for setting desired pressure for speed controlled refill pump(s)
P3 / P4.
104 | © Danfoss | 2017.09
VI.GU.T2.02
Operating Guide ECL Comfort 310, application A333