High voltage connections
The high voltage connections have a common ground connector.
U
HV
≥ U
LV
The voltage on the LV side (U
LV
) of the device cannot be higher than the HV side voltage
(U
HV
). If a higher voltage is applied to the LV side, current will immediately flow through the
diodes of device and the HV side voltage will increase to the same level as the LV side voltage.
Make sure the power cables exit straight from the terminals and do not rub against the sharp
cable through-holes or other sharp edges which could wear out the cable insulation over
time.
Do not place any excess weight on the connection box lid(s).
•
The electric device must be installed and connected according to the instructions.
•
Make sure that all the connected applications are connected to the electric device according to the
product specific operating voltage.
•
The electric device is delivered with the power terminal cover mounted. To access the power
connections, remove the mechanical safety feature and the connection box lid.
DC connection specifications (+MC, +AFE, +UG options)
DC-connection
DC link voltage range
0-1200 V
DC
DC link nominal voltage
1050 V
DC
AC connection specifications (+MC, +AFE, +UG -options)
AC connection
AC output voltage
0-700 V
EFF
(U
DC
= xxx V
DC
)
Output frequency
400 Hz
Switching frequency
4 kHz
Maximum power
250 kVA
AC connection specifications by product type (+MC, +AFE, +UG -options)
AC connection
Option
+MC95, +AFE95,
+UG95
+MC130, +AFE130,
+UG130
+MC175, +AFE175,
+UG175
+MC210, +AFE210,
+UG210
Nominal current 95 A
RMS
130 A
RMS
175 A
RMS
210 A
RMS
Nominal power 100 kVA
150 kVA
200 kVA
250 kVA
User Guide
EC-C1700B-420
Installation
54 |
©
Danfoss | June 2023