background image

 

Installation Guide 

DLX seriesL00410622-01 

 

47 

9. Technical Data 

 

Parameter 

DLX 2.0

DLX 2.9

DLX 3.8 

DLX 4.6 

 

AC 

|S| 

Rated apparent power 

2000 VA 

2900 VA 

3800 VA 

4600 VA 

Rated active power @ cosphi = 1 

2000 W 

2900 W 

3800 W 

4600 W 

Reactive power range 

0-1600 VAr 

0-2320 VAr 

0-3120 VAr 

0-3680 VAr 

 

Controlled power factor range 

0.8 over-excited, 0.8 under-excided 

V

ac,r

 

Rated output voltage 

230 V 

V

ac, min

; V

ac

max

 

AC voltage range (P-N. P-P) 

230 V±20%, single or split phase 

 

Nominal output current 

9.0 A 

13.0 A 

17.0 A 

20.0 A 

I

acmax

 

Max output current 

10.5 A 

15.2 A 

19.7 A 

23.0 A 

 

AC current distortion (THD %) 

2.59% 

3.36% 

Cosphi 

ac,r

 

Power Factor (cos φ) 

0.8 over-excited, 0.8 under-excided 

 

Night-time power loss 

< 1 W 

f

r

 

Mains frequency 

50 Hz 

f

min

, f

max 

 

Grid frequency range 

50 Hz ± 5 % 

 

DC 

 

Nominal DC power 

2100 W 

3000 W 

4000 W 

4800 W 

 

Max recommended PV power 

2625 W 

3750 W 

5000 W 

6000 W 

V

dc,r

 

Nominal voltage DC 

220 – 480 V 

220 - 480 V 

V

mppmin 

V

mppmax

 

MPP voltage-nominal power 

230 – 480 V 

250 - 480 V 

 MPP 

efficiency 

99.9% 

 

Max. DC voltage 

600 V 

 

Turn on voltage 

230 VDC 

 

Turn off voltage 

220 VDC 

 

Max current DC 

9.5 A 

13.5 A 

18.0 A 

21.0 A 

 

Max. short circuit current DC at STC 

9.5 A 

13.5 A 

18.0 A 

21.0 A 

 

Min. on grid power 

7 W 

 

Efficiency 

 

Maximum efficiency 

97.2 % 

97.2 % 

97.2 % 

97.3 % 

 

CEC efficiency 

96.8 % 

96.8 % 

97.0 % 

97.0 % 

 

EU efficiency 

96.3 % 

96.5 % 

96.7 % 

96.9 % 

 

Other 

 

Dimensions 

610 x 353 x 158 mm(169.5 mm with bracket) 

 Mounting 

recommendation 

Wall 

bracket 

 

Weight 

19 kg 

21 kg 

 Sealing 

grade 

IP65 

 

Acoustic noise level 

< 37dB (A) 

 

Operation temperature range 

-25 to +65 °C (Possible power derating above +45 °C) 

 

Storage temperature 

-30 °C to + 80 °C 

 

Relative humidity 

4 to 99% 

 

Number of PV string inputs 

 

Number of MPP trackers 

 

Protection against excessive PV power 

Yes 

 

Overvoltage category AC / DC 

Class B / Class B 

 

Reverse polarity protection 

Yes 

 Ground 

fault 

monitoring 

Yes 

 

Integral DC switch 

Yes 

 

PV grounding 

Field configurable for ungrounded, positive grounded or 

negative grounded 

 

Topology 

High frequency transformer, galvanic isolation 

 

Performance monitoring 

Graphical colour display with 6 touch sense buttons, 3x 
LEDs for visual status indication, Built-in Web Server 

 PV 

connection 

SunClix 

 

AC/grid connection 

Screw terminals 

 

Ethernet 

1 x RJ45 

 

RS-485 / CAN 

Screw terminals 

 

Functional safety 

 

 

Safety (protective class) 

Class I 

 

Islanding detection/ loss of mains 

Active Frequency Shift 

 

RCD type A recommendation 

Yes 

 

Indirect contact protection 

Yes, (Start class I, grounded) 

 

Voltage & frequency surveillance 

Included 

 

Insulation resistance surveillance 

Included 

 

DC content of AC current surveillance 

Included 

 

Содержание DLX 2.0

Страница 1: ...DLX Installation Guide DLX 2 0 DLX 2 9 DLX 3 8 DLX 4 6 MAKING MODERN LIVING POSSIBLE SOLAR INVERTERS...

Страница 2: ...er its products without notice This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed All...

Страница 3: ...Installation 13 2 5 Required Safety Equipment 23 2 6 Checks before Start Up 24 3 Start Up 25 3 1 Initial Start 25 3 2 Self Test for Italy 36 4 Connection between Inverter and PC 38 4 1 Without a Netwo...

Страница 4: ...o workers and or the general public if not avoided WARNING Situations where a potentially hazardous condition exists that could result in the death or serious injury of workers and or the general publ...

Страница 5: ...meets the EU safety health and environmental protection requirements S NO Serial Number for inverter identification 1 3 Unpacking and Inspection After unpacking the inverter safely check that all com...

Страница 6: ...f the foam packaging and take out the inverter mounting bracket Store all the original packaging for possible later reuse Figure 1 3 2 Handles After unpacking the inverter safely check that all compon...

Страница 7: ...ea 4 AC output 5 DC input 6 Network input DANGER Always disconnect the PV array cables from the inverter after turning the AC and DC OFF but before removing the covers as the PV array can supply up to...

Страница 8: ...ower supply can be used The inverter must be operated in its original and technically intact condition without any unauthorized modifications Always keep the values of operation within the limits give...

Страница 9: ...An overcurrent protection device is required on every current carrying conductor If a fuse blows or a circuit breaker trips the cause should always be determined before replacing or resetting them It...

Страница 10: ...tion of the LCD screen quality CAUTION Ensure a location where people cannot accidentally come in contact with the rear inverter surface due to temperatures up to 90 C 2 2 1 Wall Bracket Depending on...

Страница 11: ...xing clip Figure 2 2 3 Distances between fixing screws D1 232 5 mm D2 232 5 mm D3 75 mm D4 75 mm 2 2 2 Inverter Attach the inverter to the mounting bracket as follows Figure 2 2 4 Hooks on the back of...

Страница 12: ...e DC switch es are OFF and that the terminals are in a discharged state to prevent shock hazards DANGER Contact with energized ports may cause lethal injuries All installation of the inverter must be...

Страница 13: ...egulations applicable to the installation site may install the inverter This is to ensure a safe connection and avoid electrocution DANGER Never work with live wires All work on the inverter must be p...

Страница 14: ...lectrical malfunctions occur All metal parts of the DLX inverters are electrically bonded to ground through the terminal labeled GND in the AC terminal block CAUTION If the positive or negative PV con...

Страница 15: ...om the nameplate rating and at higher temperatures the PV voltage decreases from the nameplate rating NOTICE Ensure the DC switch in the Stringbox is in the OFF position when removing the lower cover...

Страница 16: ...al for the grounding strap P4 Ungrounded terminal DS DC Switch Negative Grounded PV String Figure 2 4 7 Negative grounded PV string The inverter is delivered from the factory in an ungrounded PV strin...

Страница 17: ...ll connections Ensure compliance with the relevant national electrical regulations Conductor insulation rating must be higher where the backs of the modules cannot receive cooling or where the ambient...

Страница 18: ...fore turning ON the DC switch es and the AC circuit breaker s 2 4 3 4 Jumper Position for the System Grounding Setup The jumper above the NEG terminal in the customer connection area monitors the arra...

Страница 19: ...electrocution The DLX series are single phase output inverters which are designed so that they can be connected to a three phase system When several inverters are connected together they must be dist...

Страница 20: ...with the relevant national electrical regulations The AC conductor resistance should be minimized Unscrew the cable gland locknut Guide the AC cable through the opening and connect the conductors to t...

Страница 21: ...ication with Danfoss compatible third party products or to Danfoss CLX products Figure 2 4 11 Connection without network 1 Follower inverter 2 Master inverter 3 CAN bus cable 4 Ethernet cable 5 RS 485...

Страница 22: ...3 if more cables 4 Guide the assembly into the cable gland 5 Connect the cables to the terminals in the connection area as follows Ethernet Plug the Ethernet cable directly into the RJ45 socket CAN Th...

Страница 23: ...ries The pins must be disconnected on the inverters between the first and last inverters in the linked series To disconnect the pins the jumper must be pulled up and placed only on one of the pins Be...

Страница 24: ...the DC polarity is correct AC side Verify that the AC conductors are correctly connected to the AC terminals Grounded conductors Check that the grounded conductors are properly sized and not fused or...

Страница 25: ...the configuration of all inverters in a plant via one inverter The Start Up can then be carried out on any inverter and if configured as the master inverter the configuration settings of time date lan...

Страница 26: ...power the display shows the Start Up screen 3 1 2 1 Function keys The function keys have the following uses Table 3 1 Function keys Symbol Function Symbol Function Up Scroll up increase value Right N...

Страница 27: ...rid No action NONE Yellow Inverter is OFF Power 7WDC No action 3 1 2 3 LCD Screen To navigate in the LCD screen the six function keys must be used By selecting one of the seven items in the Main Menu...

Страница 28: ...all up the list of languages Up or Down Navigate through the list to find the preferred language English German French Spanish Italian etc Enter Confirm Right Next Enter Confirm 3 Date DD MM YYYY Ente...

Страница 29: ...ta may be overwritten 5 Set Bus ID Enter Call up the digits Up Increase present digit Down Decrease present digit Enter Confirm Left Back Right Next Enter Confirm If RS485 communication is used set a...

Страница 30: ...own Select the grid configuration of the actual installation site TN TT IT Undefined Enter Confirm Left Back Right Next Enter Confirm 8 Feeding Phase Enter Call up the list of phases Up or Down Select...

Страница 31: ...lue shown in the installation menu is a suggestion and must be confirmed Please call up the digits and change value if required before pressing Enter Enter Call up the digits Up Increase present digit...

Страница 32: ...electing the grid code setting either Germany 126 VDE 0126 1 1 or Germany 4105 VDE AR N 4105 The following screen is displayed while the settings are updated Grid Code Selection NOTICE An installation...

Страница 33: ...ue to be set is 30 sec and the highest is 99 sec Setting the value to 0 disables the screen timeout and leaves the screen backlight ON at all times 13 Customer Name Enter Call up the keyboard The keyb...

Страница 34: ...the wanted letter number symbol is shown It is possible to navigate between the characters by using the Up arrow to set the marker into the text window then using Left and Right to navigate between t...

Страница 35: ...rried out on all the follower inverters Look at the displayed menu and the LEDs It is not carried out correctly if the installation menu is still displayed and or the green LED is not lit and the yell...

Страница 36: ...ation screen is still shown run through the installation process on the inverter 3 2 Self Test for Italy The Self Test function is only valid for installation in Italy It tests the inverters grid moni...

Страница 37: ...een After the test is finalized each test result must be confirmed by entering Next After entering Finish on the last result the screen displays the Inverter Commands menu The test results can be foun...

Страница 38: ...N bus cable 4 Ethernet cable 5 RS 485 cable 6 Computer 7 Data logger NOTICE With several inverters connected together via CAN bus the Ethernet cable must be attached to the master inverter only 4 1 1...

Страница 39: ...lorer 8 0 or later versions From the web page certain inverter settings can be changed after applying the correct user name and password Type the inverter s IP address in the computer s web browser De...

Страница 40: ...all these items are OK and there is still no power fed to the grid please contact the system installer 6 2 Table of Events The inverter automatically identifies operational issues and displays the me...

Страница 41: ...sistance is below permitted level The grounding setup is configured incorrect Check the jumper for the grounding setup Jumper Position for the System Grounding Setup If the jumper is correct positione...

Страница 42: ...jumper for the grounding setup is positioned incorrect Check the jumper position 2 4 3 4 Jumper Position for the System Grounding Setup Contact the system installer for DC fuse replacement Active pow...

Страница 43: ...er limit The inverter tries to restart when the frequency is within the permissible range Check that the country settings have been successfully set in Setup Grid Setup If the failure persists contact...

Страница 44: ...e trouble free for many years Performing regularly maintenance will ensure high efficiency and a longer service life for the inverters NOTICE Prior to service and maintenance work the inverter should...

Страница 45: ...thorized persons removing the inverter upper cover Unauthorized modifications made to the inverter Inverter is installed commissioned operated or maintained incorrectly Relevant safety regulations and...

Страница 46: ...46 Installation Guide DLX series L00410622 01...

Страница 47: ...Min on grid power 7 W Efficiency Maximum efficiency 97 2 97 2 97 2 97 3 CEC efficiency 96 8 96 8 97 0 97 0 EU efficiency 96 3 96 5 96 7 96 9 Other Dimensions 610 x 353 x 158 mm 169 5 mm with bracket M...

Страница 48: ...ible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterat...

Отзывы: