4. If you install the unit on a building frame, please install a waterproof plate (field supply) (within 150mm of the underside of the unit)
in order to avoid the drain water dripping. (See figure)
5. In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is not affected by the snow (If necessary construct a lateral canopy)
Example of solutions in snowy areas
1
2
1. Construct a large canopy.
2. Construct a pedestal. Install the unit high enough off the ground to prevent it being buried under snow.
1
2
3
4
If you install the unit on a frame, please install a waterproof plate within 150 mm of the underside of the unit
in order to prevent the invasion of water from the lower direction.
1. Snow-proof hood
2. Frame
3. Estimated snow fall
4. Ground
Heavy snow fall area (Natural drainage)
▪
When using the application in the heating mode, ice may accumulate. During defrosting, the condensed water must be drained off
safely. Follow the instructions below, to make the heat pump work satisfactory. Make space more than 80mm between the bottom
of the outdoor unit and the ground for installation.
80 mm
▪
If the product is installed in a region of heavy snow, allow enough separation distance between the product and the ground.
▪
When installing the product, make sure that the rack is not placed under the drain hole.
▪
Ensure that the drained water runs off correctly and safely.
Installation Guide
DHP-iQ
VIJSS102
Danfoss Heating Solutions
26