58
VMBMA602
Sub menu SERVICE -> ADD. HEAT
Used to change the heat pump stage’s operating settings.
Menu selection
Meaning
Factory setting
INTEGRAL A2
Two conditions must be fulfilled in order to start the auxiliary heater: the inte-
gral’s value to start must be less than integral A1 + A2, and the supply tempera
-
ture must be 2° lower than the calculated temperature.
600 (interval: 50 / 990)
HYSTERESIS
If the difference between the actual supply temperature and the calculated sup-
ply temperature is too great either the integral value is set to start value A1 + A2
(the addition starts) or the value is set to 0 (stops the addition).
20°C (interval: 5°C / 30°C)
MAXSTEP
Maximum number of permitted steps for auxiliary heating.
0 = no auxiliary heating permitted (Means that only AUTO or can be selected
and that legionella operation is not possible.)
2 (at AIR 5)
(interval: , 1 / 3)
(interval at OUTSIDE AIR:
, 1 / 5)
MAX CURRENT
(Expansion card)
Refers to main fuse in the unit, in amperes.
20 (interval: 16 / 35)
Menu selection
Meaning
Factory setting
SHUNTTIME
Minimum time interval between signals to shunt motor to affect the supply tem-
perature, in seconds. Applies to all connected shunt groups (applies to system D
or VLD).
60S (interval: 10S / 99S)
HOT WATER STOP
Stop temperature for hot water during ADD. HEAT operation (applies to the VL
system). The value is read off by the hot water sensor.
60°C
(interval: 50°C / 65°C)
Sub menu SERVICE -> MANUAL TEST
Used to manually test and test operate the heat pump’s components or signal outputs.
Menu selection
Meaning
Factory setting
MANUAL TEST
Setting options for manual test.
0 = deactivate manual test
1 = activate manual test
2 = activate manual test with option of navigating from the SERVICE menu to
check that the temperatures rise.
-
HEATPUMP
0 = stop heat pump, does not stop started brine pump
1 = start heat pump, also starts brine pump.
NOTE! The heat pump cannot be started in the event of an active alarm.
-
BRINEPUMP
0 = stop brine pump
1 = start brine pump
-
CIRC: PUMP
0 = stop circulation pump
1 = start circulation pump
-
VXV HOT WATER
0 = heating mode for 3-way valve
1 = hot water mode for 3-way valve
-
SHUNT 1
- = closes shunt (applies to D-system)
0 = shunt unaffected
+ = opens shunt (applies to D-system)
-
ADD. HEAT 1
0 = stop auxiliary heat step 1
1 = start auxiliary heat step 1
-
ADD. HEAT 2
0 = stop auxiliary heat step 2
1 = start auxiliary heat step 2
-
ADD. HEAT 3 (
DHP-A, -AL
)
(Defrost card)
0 = stop auxiliary heat step 3
1 = start auxiliary heat step 3
-
SHUNT DEFR (
DHP-A, -AL
)
(Defrost card)
- = opens flow from the defrost tank
0 = shunt unaffected
+ = closes the flow from the defrost tank
-
FAN L
(Defrost card)
0 = stop fan
1 = start fan with low speed
-
FAN H
(Defrost card)
0 = stop fan
1 = start fan with high speed
-
ADD.HEAT EXT (
DHP-A,
-AL
)
(Defrost card)
0 = 0V on terminal block 283
1 = control voltage 230V on terminal block 283
-