41
VMBME102
14
Troubleshooting
⚠
NOTE! This troubleshooting section contains general heat pump information for the whole range and can therefore contain certain
points that do not apply to the installed heat pump.
14.1
Alarm list
Shown in display in the event of an alarm. To reset alarms 1-5. set the operating mode to OFF or cut the power supply.
Message
Meaning
HIGHPRESS ERROR
Tripped high pressure switch. Compressor stopped. No hot water production.
LOWPRESS ERROR
Tripped low pressure switch. Compressor stopped. No hot water production.
MOTOR P ERROR
Deployed motor protection (Over current relay compressor). Compressor stopped. No hot water production.
BRINE OUT
Brine supply does not exceed set temperature. Compressor stopped. No hot water production. Not normally
activated.
BRINEFLOW LOW
Flow sensor not active during last start. Compressor stopped. No hot water production.
ADD. HEAT
Overheating protection deployed. No auxiliary heating active.
SENSOR OUTDOOR
Fault in outside sensor. Zero degrees used for calculations.
SENSOR FRONT
Incorrect supply pipe sensor. Everything stops except circulation pump.
SENSOR RETURN
Return sensor fault. Return temperature = Supply pipe – 5 is used. Calculated supply temperature limited to
maximum 45°C.
SENSOR HOT WATER
Fault on sensor for start temperature. No hot water production.
SENSOR DEFROST
Defrost sensor fault. Heat and hot water production is controlled from the outdoor sensor’s value instead.
MS FAN
Deployed motor protection for outdoor unit fan. Compressor stopped. No hot water production.
SENSOR COOLING
Sensor fault. Cooling function stops.
14.2
Measurement points
Conversion table for sensors
NOTE! When reading the resistance of the sensors. the sensor leads must first be disconnected from the control equipment.
Outdoor sensor
Other sensors
°C
kohm
°C
kohm
-30
1884
0
66.3
-25
1443
5
52.4
-20
1115
10
41.8
-15
868
15
33.5
-10
681
20
27.1
-5
538
25
22.0
0
428
30
18.0
5
343
35
14.8
10
276
40
12.2
15
224
45
10.1
20
183
50
8.5
25
150
55
7.1
30
124
60
6.0
35
103
65
5.0
40
86
70
4.2
75
3.7
80
3.1
85
2.7
90
2.3
95
2.0
1. First measure the sensor including the cable.
2. Then measure the sensor only.
Содержание DHP-AL