Installation and User Guide  

DEVIreg™ Hotwater

FEC | Produced by Danfoss ©

4

Introduction

DEVIreg™ Hotwater

 is a 4 channel electronic programmable controller . 3 additional chan-

cels are not used in this constellation . The device is DIN-rail mountable and is used for 
control of Devi Hotwatt cables . Every channel (4) can be individually set up, this will allow 
for 4 different temperatures and disinfection schedules .

Universal analog channels’ inputs can be selected via software between 7 types of temperature 
sensors including NTC 15 kOhm at 25 °C . The controller has a  LCD display, Modbus RS-485 
serial interface and 110/230 V AC power supply . Voltage to sensors is SELV .

DEVIreg™ Hotwater

 has 8 control relays – 2 sets of max . 10 A and 6 sets of max . 6 A; For this 

specific application 2, 10A and 2, 6A relays are used . Relay control functions can be set to 
Hot-water maintenance and legionella control of a hot-water system by use of applicable 
heating cables . Additionally, relay contacts are not connected to a voltage source inside the 
controller, and can be used for control systems with any voltage up to 250 V AC .

Hardware of 

DEVIreg™ Hotwater

 is based on the Danfoss controller type MCX08M2, 

art . no . 080G0307, but is customized with special software .

The product complies with the EN/IEC Standard “Automatic electrical controls for house-
hold and similar use”:

• 

EN/IEC 60730-1 (general)

• 

EN/IEC 60730-2-9 (thermostat)

More information on this product can also be found at: 

devi.com

Connection scheme DEVIreg™ Hotwater

S

 - temperature Sensor;

H

 - Heating element .

CO

M

CO

M

DI 1-4

DI 1

C 1

NO 1

DI 2

C 2

NO 2

DI 3

NC 3

C 3

NO 3

DI 4

NC 4

C 4

NO 4

DI 5

C 5

NO 5

DI 6

C 6

NO 6

DI 7

NC 7

C 7

NO 7

AI 1

CO

M

AI 2

CO

M

AI 3-4

AI 3

AI 4

CO

M

AI 5-8

AI 5

AI 6

AI 7

AI 8

Power

110/230 V AC

RS485

NC 8

DI 8

C 8

NO 8

CO

M

DI 5-8

D -

D +

GND

RS485

(Modbus)

for H2

for H3

for H1

H1

H2

H3

H4

for H4

S - 

temperature Sensor;

Содержание DEVI DEVIreg Hotwater

Страница 1: ...Intelligent solutions with lasting effect Visit devi com DEVIreg Hotwater Installation and User Guide DEVIreg Hotwater DIN rail programmable controller for hotwater maintenance EN...

Страница 2: ......

Страница 3: ...view 7 Setup wizard 8 First start up 9 Sub menu Alarm 10 Sub menu Service 10 Function Setup Wizard 11 Sub menu H1 H4 12 Sub menu Disinfection schedule 14 Alarms view 15 Main menu 15 4 2 Language setti...

Страница 4: ...e set to Hot water maintenance and legionella control of a hot water system by use of applicable heating cables Additionally relay contacts are not connected to a voltage source inside the controller...

Страница 5: ...ipped with transient protection 3 Mounting Instructions Please observe the following placement guidelines Install the thermostat in an electric cabinet with DIN rail attachment or a separate DIN attac...

Страница 6: ...ne next setting parameter Left Right Shows additional information Escape Escape return to previous level of menu show Alarm screen Enter Confirm select go to the Main menu Display The DEVIreg Hotwater...

Страница 7: ...ed from the respective heaters sub screen This view provides the user with an overview of all systems however with limited information Heater sub screen view These screens give to user quick and more...

Страница 8: ...run the wizard to do this press Press once more to proceed into the setup The device will ask for the amount heaters use to select and to accept The device will now ask for the details of each heater...

Страница 9: ...The final step in the wizard is the RTC Real Time Clock press Navigate with or select with Manipulate with accept with or return with Once time and date are set confirm with First start up Ensure eve...

Страница 10: ...date and timestamp This is navigated like Alarm view Clear log history clears the log history perma nently by pressing Sub menu Service The structure in this Sub menu is navigated like the main menu...

Страница 11: ...nd select with Configuration Contains buzzer activation time delay for alarm activation and alarm state when device is OFF Serial settings Contains Modbus CAN serial address Modbus serial baudrate and...

Страница 12: ...t value as this must be set in setup wizard Please refer to the sensors maximum and minimum temperatures to ensure safe operation of the system Setpoint Settable with to select and to confirm Settable...

Страница 13: ...sensor B only thus 50 is the mean between sensor A and B Settable between 0 100 Defaults to 50 Disinfection temp Settable with to select and to confirm Settable between 55 80 0 C Defaults to 55 C Pip...

Страница 14: ...ill be triggered due to too low temperature setpoint not reached Defaults to 120 minutes Sub menu Disinfection schedule The structure in this Sub menu is navigated like the main menu H1 H4 Schedule Pr...

Страница 15: ...1 0h 18minutes 72 0h 14 minutes 73 0h 12 minutes 74 0h 10 minutes 75 0h 10 minutes Alarms view By pressing button from Main Screen screen s with Alarm appears If more than 1 Alarm is happened use navi...

Страница 16: ...rmation for example Alarms NB Battery back up time is min 48 hours 4 4 BMS Building Management System settings DEVIreg Hotwater controller has Modbus RS 485 opto insulated serial interface Modbus RS 4...

Страница 17: ...1 NO 1 DI 2 C 2 NO 2 DI 3 NC 3 C 3 NO 3 DI 4 NC 4 C 4 NO 4 DI 5 C 5 NO 5 DI 6 C 6 NO 6 DI 7 NC 7 C 7 NO 7 AI 1 COM AI 2 COM AI 3 4 AI 3 AI 4 COM AI 5 8 AI 5 AI 6 AI 7 AI 8 Power 110 230 V AC RS485 NC...

Страница 18: ...16k 16 7 kOhm 100 C PT1000 1000 Ohm 0 C Digital inputs DI1 DI8 voltage free contacts on off inputs Connection specification Grouped screws plug in connectors Cable specification for connectors termina...

Страница 19: ...Installation and User Guide DEVIreg Hotwater FEC Produced by Danfoss 19 6 2 Dimensions 110 140 60 63...

Страница 20: ...Installation and User Guide DEVIreg Hotwater FEC Produced by Danfoss 20 7 Disposal Instruction...

Страница 21: ...rovides general indications for the setup of RS 485 networks A3 Modbus parameters and variables Modbus parameters and variables for DEVIreg Hotwater controller LABEL DESCRIPTION MIN MAX VALUE TYPE UNI...

Страница 22: ...0 10 s RW 3033 H05 Sensor weighting 0 100 sensor A 0 100 50 RW 3034 H06 Disinfection temp 55 S1 55 C RW 3035 H07 Pipe material 0 1 0 Metal Enum 6 RW 3036 H08 Disinfection alarm temp H06 90 0 65 0 C RW...

Страница 23: ...0 100 0 0 0 C Read 8104 V12 H1 pullDown 0 1 0 NO Enum 2 Read 8105 V13 H1 manualDis 0 1 0 RW 9901 V14 H2 manualDis 0 1 0 RW 9902 V15 H3 manualDis 0 1 0 RW 9903 V16 H4 manualDis 0 1 0 RW 9904 V16 H1 sen...

Страница 24: ...ullDown 0 1 0 NO Enum 2 Read 8145 V51 H1 Duty 0 100 0 Read 8146 V52 H2 Duty 0 100 0 Read 8147 V53 H3 Duty 0 100 0 Read 8148 V54 H4 Duty 0 100 0 Read 8149 V56 H1 counter 0 2147483647 0 Read 8150 V57 H2...

Страница 25: ...1 MANUAL INACTIVE Read 1902 13 A15 Heater3 high disinfection 0 1 MANUAL INACTIVE Read 1902 14 A16 Heater4 high disinfection 0 1 MANUAL INACTIVE Read 1902 15 I OCONFIGURATION AI ANALOG INPUTS 1 Sensor...

Страница 26: ...hout undue delay and proof of purchase is provided Please note that the WARRANTY CERTIFICATE must be filled in stamped and signed by the authorized installer performing the installation Installation d...

Страница 27: ...Installation and User Guide DEVIreg Hotwater FEC Produced by Danfoss 27...

Страница 28: ...08097137 AN377831097153en 010102 Produced by Danfoss 11 2021 Installation and User Guide DEVIreg Hotwater Danfoss A S Nordborgvej 81 6430 Nordborg Syddanmark Denmark...

Отзывы: