Installation and User Guide
DEVIreg™ Hotwater
FEC | Produced by Danfoss ©
13
Alarm delay:
Settable with
to select and
to confirm .
Temperature alarm delay
Settable between 10-240s
Defaults to 10s
Sensor weighting:
Settable with
to select and
to confirm .
Weighting the impact of the 2 sensors on the heater regulation .
0% means that the regulation is made on basis of sensor A only 100% meaning sensor B only,
thus 50% is the mean between sensor A and B .
Settable between 0-100%
Defaults to 50%
Disinfection temp:
Settable with
to select and
to confirm .
Settable between 55-80 .0°C
Defaults to 55°C
Pipe material:
Settable with
to select and
to confirm .
This parameter will have impact on the maximum settable temperatures .
Can be set to metal or plastic .
Has no default value as this must be set in setup wizard
Disinfection alarm temperature:
Settable
with
to select and to confirm .
This parameter will have impact on the alarm temperature for disinfection temperatures .
Defaults to 65°C