PID Closed Loop menu for VTZ Compressor Drive

Parameter Nº

Par. Description

Default

For PID, change to

Comment

01-00

Configuration Mode

Speed Open 

Loop

Process

Allows the drive to receive a feedback from the refri-

geration system, typically pressure or temperature. 

In the following it is assumed pressure feedback is 

used.Hence, the input frequency to the compressor 

can be adjusted according to de cooling demand.

03-01

Reference / Feedback Unit

rpm

Bar or psi

The feedback (suction pressure) can be displayed on 

the LCP in its appropriate unit.

03-02

Min. Reference

2100 rpm

-1 [Bar] (-100 if SLC is used)

Sets the minimum range for the pressure transmitter

03-03

Max. Reference

5400 rpm

12 [Bar] (100 if SLC is used)

Sets the maximum range for the pressure transmit-

ter

03-10

Preset reference

0

Not necessary to change

Value will be added to the speed reference or to the 

set point for the PID control (closed loop)

03-13

Reference site

linked to Hand 

(local) / Auto 

(remote)

Select Local or Remote

From where the operator will control the Frequency 

Converter. To use a local reference adjusted locally 

on the Drive select «local». To apply an external refe-

rence select «Remote». To use SLC it is always nee-

ded to push «Auto On»

03-15

Reference resource 1

Input 53

Leave as Input 53 or set to 

«No function»

If PID set point is modified via external reference: 

Leave as Input 53. If set point is fixed and set locally 

in Drive: Set to «No function»

06-10

Terminal 53 Low Voltage

0

No change

Minimum value in Volts for the reference signal. Only 

relevant if external reference is used (input 53 selec-

ted in 3-15)

06-11

Terminal 53 High Voltage

10

No change

Maximum value in Volts for the reference signal. 

Only relevant if external reference is used (input 53 

selected in 3-15)

06-14

Terminal 53 Low Reference / 

Feedb. value

2100

E.g. 1 [Bar]

Only relevant if external reference is used (input 53 

selected in 3-15)

06-15

Terminal 53 High ref / Feed. value 5400

E.g. 5 [Bar]

Only relevant if external reference is used (input 53 

selected in 3-15

06-20

Terminal 54 Low Voltage

1V

Minimum value in V for the 

pressure transmitter’s range

Depends on output from the feedback device. Nor-

mally no changes are needed

06-21

Terminal 54 High Voltage

5V

Maximum value in V for the 

pressure transmitter’s range

Depends on output from the feedback device. Nor-

mally no changes are needed

06-22

Terminal 54 Low Current (only 

visible if switch set to I)

4

Minimum value in mA for 

the pressure transmitter’s 

range

Depends on output from the feedback device. Nor-

mally no changes are needed

06-23

Terminal 54 High Current (only 

visible if switch set to I)

20

Maximum value in mA for 

the pressure transmitter’s 

range

Depends on output from the feedback device. Nor-

mally no changes are needed

06-24

Terminal 54 Low ref / Feedb. value -1

Value according to transmit-

ter

Min value for range in Bar of pressure transmitter

06-25

Terminal 54 High ref / Feedb. 

value

9

Value according to transmit-

ter

Min value for range in Bar of pressure transmitter

07-20

Process CL Feedback Input 

resource

Analog Input 54 If input 54 is used for trans-

mitter no change is needed

Selects which input signal is used for PID-Closed 

loop control

07-33

Process PID Gain

2

According to system

Proportional gain of PID. Default values suitable for 

most systems for suction pressure control

07-34

Process PID Integration time (ms)

9000 ms

According to system

Integral time of PID in ms. Default valus suitable for 

most systems for suction pressure control

SLC

Pres  Anti-short cycling 

function

Optional 

feature

Only active if 13-00 set to On

13-00

Smart Logic Controller On/Off

Off

Set  only to On if pressostat fu anti short 

cycling are to be active

13-12.0

Comparator 0 (=cut-in pressure 

value)

3 Bar

Set desired start pressure

Pressostat function

13-12.1

Comparator 1 (=cut-out pressure 

value)

1 Bar

Set desired stop pressure

Pressostat function

13-20.0

Timer 0 (Start-to-Start timer)

5 min

Set desired time from start 

to start

Anti-short cycling function, 5 min = 12 starts per 

hour allowed

13-20.1

Timer 1 (Minimum Run-time)

0 min

Set desired minimum run-

ning time

Compressor will run for 1 min. before stopping

* SLC: Smart Logic Controller

Instructions

AN000086420674en-000201 | 23

© Danfoss | DCS (CC) | 2019.04

Содержание Compressor Drive CD302

Страница 1: ...t has been disconnected from mains Also make sure that other voltage inputs have been disconnected such as load sharing linkage of DC intermediate circuit Using CD 302 Com pressor Drives wait at least...

Страница 2: ...and switch S202 Voltage mode Switch S201 switch S202 OFF U Voltage level 10 to 10 V scaleable Input resistance Ri approx 10 k Max voltage 20 V Current mode Switch S201 switch S202 ON I Current level...

Страница 3: ...C dera ting of the frequency converter will become rele vant The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account Mechanical dimensions...

Страница 4: ...rth connection terminal 99 on decoupling plate with screws from the accessory bag Insert terminals 96 U 97 V 98 W and motor compressor cable to terminals labelled MOTOR Fasten screened cable to decoup...

Страница 5: ...ent anti overload and lock rotor motor compressor protection see description in the application manual The frequency converter is protected against short circuits on compressor terminals U V W If a ma...

Страница 6: ...mounted to the terminal To remove the cable from the terminal 1 Insert a screw driver in the square hole 2 Pull out the cable Basic Wiring Example 1 Mount terminals from the accessory bag to the fron...

Страница 7: ...0BA025 17 91 L1 92 L2 93 L3 PE 88 89 50 10V OUT 53 A IN 54 A IN 55 COM A IN 0 4 20 mA 12 24V OUT 13 24V OUT 37 D IN 18 D IN 20 COM D IN 10Vdc 15mA 130 200mA U 96 V 97 W 98 PE 99 COM A OUT 39 A OUT 42...

Страница 8: ...interrupt device If the interrupt device and the frequency converter are placed in the same installation panel you can use a regular cable instead of a protected one Electrical Installation EMC prote...

Страница 9: ...filled See the para graph EMC test results Safety earth connection The frequency converter has a high leakage cur rent and must be earthed appropriately for safety reasons acording to EN 50178 The ear...

Страница 10: ...4 20 mA 0 4 20 mA COM 68 69 4 5 0 10 V or 4 20 mA Open Loop input 0 10V between 53 55 to external Frequency converter CD302 Compressor Drive TM RS 485 Analog output Analog input 6 Incorporate securit...

Страница 11: ...if the motor compressor remains in the coasted state 4 Then send Reset signal via Bus Digital I O or Reset key The test step is passed if the motor compressor gets operational again 5 The commissioni...

Страница 12: ...iping oil return Reset start Power output from CD302 drive Yes No Check Alarm 14 15 30 31 32 38 Earth Fault Output side Short circuit Output side Motor phase missing Internal fault Check motor cable C...

Страница 13: ...pass Or recycled Missing CD 302 back side Metal sheet Turn off power Reset Start 24V supply to terminal 37 direct wire external controls inserted Check Alarm continue Speed limit low Automatic restart...

Страница 14: ...I No need to change any other parameter this is factory setting Quick setup The following lines describe the basic procedure to run the CD302 1 Connect the power supply to the terminals L1 L2 and L3...

Страница 15: ...the keys to move the cursor OK is used for choosing a parameter marked by the cursor and for enabling the change of a para meter Local Control Keys for local control are found at the bottom of the con...

Страница 16: ...Change from Open Loop factory set to Pro cess Loop Select Quick Menu Select Q3 PID Closed Loop Par 1 00 change to 3 Process Par 3 01 change to 71 bar Par 3 02 enter pressure sensor low range value fac...

Страница 17: ...rameter will be ignored 0 61 Access to Main Menu w o Password Option Full access 0 Read only 1 No access 2 Function Select Full access 0 to disable the password defi ned in par 0 60 Main Menu Password...

Страница 18: ...Minimum Reference unit matches the choice of configuration in par 1 00 Confi guration Mode for Speed closed loop 1 the unit selected in par 3 01 Reference Feedback Unit 3 03 Maximum Reference Enter th...

Страница 19: ...y two phases it can be da maged by overheating Retaining the On setting is therefore strongly recommended This parameter cannot be adjusted while the motor is running Parameters Digital In Out Paramet...

Страница 20: ...eded by the integrator to reach the same gain as the proportional gain 7 35 Process PID Differentiation Time Range 0 00 10 00 s 0 00s Function Enter the PID differentiation time The differen tiator do...

Страница 21: ...54 Cut in pressure is set at 3 000 bar in parameter 13 12 0 Comparator value Cut out pressure is set 1 000 bar in parameter 13 12 1 Comparator value Anti short cycle by adjusting minimum dura tion bet...

Страница 22: ...trolled by a switch connected to terminal 18 05 12 Terminal 27 Coast inverse Stop function coast inverse linked to safety line of the system HP LP switches 06 10 Terminal 53 Low Voltage 0 Minimum valu...

Страница 23: ...rminal 54 Low Voltage 1V Minimum value in V for the pressure transmitter s range Depends on output from the feedback device Nor mally no changes are needed 06 21 Terminal 54 High Voltage 5V Maximum va...

Страница 24: ...ref Feedb value 6 25 r w 12 Param Designation Param number Customer access Common parameters for all compressors Speed PID Feedback Source 7 00 Read Motor Feedb P1 02 PID Gain 7 02 Read 0 005 PID Inte...

Страница 25: ...90 RPM 90 RPM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 540...

Страница 26: ...PM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 Ramp down time running sec 3 42 r w 0 3 0 3...

Страница 27: ...RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 5400 5400 5100 Ramp...

Страница 28: ...the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specification...

Отзывы: