6.2 Relays for Pump and Boiler Control

Activate Relay mode on CF-MC Master Controller (fig. 20):

•   

Use the menu selection button   to select the Relay mode. Relay LED   flashes.

•  Activate Relay mode by pressing OK  . Relay LED   goes ON.

Select the Relay configuration (fig. 20/22):
•  Press the output selection button   and toggle between the possible Relay configurations   -  
 

the output LEDs will be ON – indicated below:
•  NO LEDs: The relays are not used.
•  1 LED: Pump control.
•  2 LEDs: Boiler control.
•  3 LEDs: Pump and boiler control.
•  4 LEDs: Pump control with 2 min. start/stop delay.
•  5 LEDs: Pump and boiler control, with  2 min. start/stop delay on pump (default).

•  Activate selected relay configuration by pressing OK  .

Note! 

If the pump relay is active, the CF-MC Master Controller will run a pump motion program every 3rd 

day and it will last for one minute.
More relay configurations can be made via the CF-RC Remote Controller (see separate instruction).

6.3 Input for Away Function and Heating and Cooling

Activate Input mode on CF-MC Master Controller (fig. 20):
•  Use the menu selection button   to select the Input mode. Input LED   flashes.
•  Activate Input mode by pressing OK  . Input LED   goes ON.

Select the Input configuration (fig. 20/21/22):
•  Press the output selection button   and toggle between the possible Input configurations          
 

- the output LEDs will be ON – indicated below:
•  1 LED: The input ports are not used.

•   

2 LEDs: The CF-MC Master Controller will switch to cooling mode when the input for heating/
cooling is activated (fig. 2 -  ).

•  3 LEDs: The CF-MC Master Controller will switch to a fixed set room temperature at 8 °C for  
 

all Room Thermostats when the input for away function is activated (fig. 2 -  ).

•  4 LEDs: The CF-MC Master Controller will switch to cooling mode when the input for           
 

heating/cooling is activated (fig. 2 -  ). In heating mode the CF-MC Master Controller will  

 

switch to a fixed set room temperature at 8 °C for all Room Thermostats when the input for  

 

away unction is activated (fig. 2 -  ) (default).

•   

Activate selected input configuration by pressing OK  .

6.4 Heating/Cooling

A 2-pipe system can be configured for automatic heating/cooling change-over.
•  A PT-1000 pipe sensor must be connected to the PT-1000 input (fig. 2 -  ).
•  Configuration is only possible via CF-RC Remote Controller (see separate instruction).

6.5 Relays on more (2 to 3) CF-MC Master Controllers

If more CF-MC Master Controllers are connected to CF-MC Master Controller 1 in one system, their 
relays for pump and boiler control should be configured separately!

Activate Relay mode on CF-MC Master Controller 2/3 (fig. 20):
•  Use the menu selection button   to select the Relay mode. Relay LED   flashes.
•  Activate Relay mode by pressing OK  . Relay LED   goes ON.

Select the Relay configuration (fig. 20/22):

•   

Press the output selection button   and toggle between the possible Relay configurations   - 
the output LEDs will be ON – indicated below:
Uses pump and boiler connected to CF-MC Master Controller 1:
•  NO LEDs: The relays are not used (default).
If local manifold and pump are separate:
•  1 LED: Pump control.

•   

4 LEDs: Pump control with 2 min. start/stop delay.

•  Activate selected relay configuration by pressing OK  .

6.6 Wireless relay

CF-WR Wireless Relay can be connected to the CF-MC Master Controller and configured by the CF-RC 
Remote Controller (see separate instruction).

GB

Содержание CF-MC

Страница 1: ...DANFOSS HEATING SOLUTIONS MAKING MODERN LIVING POSSIBLE Installation Guide CF MC Master Controller...

Страница 2: ...Installation Guide CF MC Master Controller 2 01 2016 VIUHK902 Danfoss Heating Solutions...

Страница 3: ...12 Transmission Test Link Test 6 4 13 Mounting of CF RS RP RD and RF Room Thermostats 7 5 Temperature Settings 7 5 1 CF RS Room Thermostat 7 5 2 CF RD and CF RF Room Thermostat with Digital Display 7...

Страница 4: ...External Antenna 3 Functional Overview fig 2 Menu selection button Menu LEDs Output and configuration selection button OK button Output LEDs Output cable fixing Relays for pump and boiler Input for he...

Страница 5: ...hanged with the CF RC Remote Controller If the system is configured for cooling a dew point sensor can be connected instead of an external switch 4 5 Input for Heating and Cooling Connect both wires f...

Страница 6: ...ller should be within a distance of 1 5 m Activate Install mode on CF MC Master Controller fig 20 Use the menu selection button to select the Install mode Install LED flashes Activate Install mode by...

Страница 7: ...e enclosed strips from batteries to activate A Room Thermostat can be assigned to several outputs if needed by repeating the installation process 5 Temperature Settings 5 1 CF RS and RP Room Thermosta...

Страница 8: ...sh button shortly SET MIN is also shown in the display Press the up down selector to set the minimum floor surface temperature limitation IMPORTANT Asheatemissionfromthefloormayvaryslightlydepending o...

Страница 9: ...3 LEDs The CF MC Master Controller will switch to a fixed set room temperature at 8 C for all Room Thermostats when the input for away function is activated fig 2 4 LEDs The CF MC Master Controller wi...

Страница 10: ...ED and all the output LEDs are ON The CF MC Master Controller is reset when all output LEDs goes OFF Resetting the CF RS RP RD and RF Room Thermostats fig 27 Remove the Room Thermostat from the back p...

Страница 11: ...put load total 35 VA Relays 230 V AC 8 2 A Ambient temperature 0 50 C IP class 30 8 2 CF RS RP RD and RF Room Thermostats Temperature setting range 5 35 C Transmission frequency 868 42 MHz Transmissio...

Страница 12: ...r 3 CF MC Master controller 1 Alarm and Install LED s flashes for approx 20 sec CF MC Master Controller 2 Alarm LED lights up for approx 1 sec CF MC Master Controller 2 has an older version of softwar...

Страница 13: ...Installation Guide CF MC Master Controller Danfoss Heating Solutions VIUHK902 01 2016 13 GB...

Страница 14: ...tallation Guide CF MC Master Controller 14 01 2016 VIUHK902 Danfoss Heating Solutions A1 Fig 1a CF MC Fig 1b CF RS CF RP CF RD CF RF Fig 1c CF RC Fig 1d CF RU Fig 1e CF DS Fig 1f CF WR Fig 1g CF EA Fi...

Страница 15: ...llation Guide CF MC Master Controller Danfoss Heating Solutions VIUHK902 01 2016 15 A2 Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 Fig 8 Fig 9 Fig 10 Fig 11 Click Click CF MC CF RS RP RD RF CF MC CF RS RP RD RF CF...

Страница 16: ...Installation Guide CF MC Master Controller 16 01 2016 VIUHK902 Danfoss Heating Solutions B1 Fig 12 Fig 13 Fig 14 Fig 15 Fig 16 Fig 17 Fig 18 Fig 19 Fig 20 Fig 21...

Страница 17: ...Installation Guide CF MC Master Controller Danfoss Heating Solutions VIUHK902 01 2016 17 1 5 m 0 5 m 0 25 m B2 Fig 22 Fig 23 Fig 24 Fig 25 Fig 26 Fig 27 Fig 28 Fig 29 Fig 20 CF RP CF RS GB...

Страница 18: ...VIUHK902 Danfoss A S Indoor Climate Solutions Ulvehavevej 61 7100 Vejle Denmark Phone 45 7488 8500 Fax 45 7488 8501 Email heating solutions danfoss com www heating danfoss com...

Отзывы: