8. Technical Specifications
8.1 CF-MC Master Controller
Transmission frequency
868.42 MHz
Transmission range in normal constructions (up to)
30 m
Transmission power
< 1 mW
Supply voltage
230 V AC
Actuator outputs
10 x 24 V DC
Max. continued output load (total)
35 VA
Relays
230 V AC/8 (2) A
Ambient temperature
0 - 50 °C
IP class
30
8.2 CF-RS, -RP, -RD and -RF Room Thermostats
Temperature setting range
5 - 35 °C
Transmission frequency
868.42 MHz
Transmission range in normal constructions
(up to)
30 m
Transmission power
< 1 mW
Battery
Alkaline 2 x AA, 1.5 V
Battery lifetime (up to)
1 to 3 years
Ambient temperature
0 - 50 °C
IP class
21
Floor sensor accuracy*
+/- 1 °C
Floor sensor emission coefficient*
0.9
* Only valid for CF-RF Room Thermostat