13
4.9.18 - BRODCAST menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
ccnbroad
0/1/2
2
-
Activates the broadcast
0 = deactivated, 1= broadast during holidays at the network, 2 =
broadcast during holidays, machine only
oatbusnm
0 to 239
0
-
Broadcast of the outside temperature
Bus number of the machine with the outside temperature
oatlocad
0 to 239
0
-
Element number of the machine with the outside temperature
dayl_sel
Disable/Enable
Disable
-
Activation summer time, winter time
Summer time
startmon
1 to 12
3
-
Month
startdow
1 to 7
7
-
Day of the week (1 = Monday)
startwom
1 to 5
5
-
Week of the month
Winter time
stopmon
1 to 12
10
-
Month
stoptdow
1 to 7
7
-
Day of the week (1 = Monday)
stopwom
1 to 5
5
-
Week of the month
4.9.19 - GENCONF menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
lead_cir
0/1/2
0
-
Circuit loading sequence
0 = auto, 1 = A first, 2 = B first
seq_typ
No/Yes
No
-
Loading sequence by circuit
ramp_sel
No/Yes
No
-
Ramp loading sequence
off_on_d
1 to 15
1
min
Start-up delay
nh_limit
0 to 100
100
%
Capacity limitation in night mode
nh_start
00:00 to 24:00
00:00
-
Night mode start hour
nh_end
00:00 to 24:00
00:00
-
Night mode stop hour
bas_menu
0 to 3
0
-
Basic menu configuration
0 = total access
1 = access to the alarm menu by password
2 = access to the setpoint menu by password
3 = combination of 1 and 2
synoptic
No/Yes
No
-
Synoptic diagram displayed
4.9.20 - PUMPCONF menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
clpmpseq
No/Yes
No
-
Evaporator pump selection
clpmpper
No/Yes
No
-
Evaporator pump seizure protection
clpmpsby
No/Yes
No
-
Pump shutdown when the unit is in standby
clpmploc
No/Yes
Yes
-
Flow rate verification when the pump has shut down
cdpmpseq
No/Yes
No
-
Condenser pump selection
cdpmpper
No/Yes
No
-
Condenser pump seizure protection
cdpmpsby
No/Yes
No
-
Pump shutdown when the unit is in standby
cdpmploc
No/Yes
Yes
-
Flow rate verification when the pump has shut down
ol_pump
No/Yes
No
Open-loop pump control selection
4.9.21 - HCCONFIG menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
auto_sel
No/Yes
No
-
Automatic changeover selection
cr_sel
0 to 2
0
-
Cooling reset selection
hr_sel
0 to 2
0
-
Heating reset selection
1 = outside temp., 0 = none, 2 = delta T
heat_th
-20 to 0
-15
°C
Outside temperature threshold cooling mode
boil_sel
No/Yes
No
-
Boiler control selection
boil_th
-15 to 15
-10
°C
Outside temperature threshold for the boiler
ehs_sel
0 to 4
0
-
Selection, number of electric heater stages
ehs_th
-5 to 21.2
5
°C
Outside temperature threshold for electric heater stages
both_sel
No/Yes
No
-
Heating or cooling command selection for HSM
ehs_back
No/Yes
No
-
1 backup electric heater stage
ehs_pull
0 to 60
0
minutes
Delay before start-up of the first electric heater stage
ehs_defr
No/Yes
No
-
Quick electric heat stages for defrost
4.9.22 - HDC_CONF menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
adpmpper
Yes/No
Yes
-
Additional pump anti-stick function
summ_oat
15.0 to 30.0
20.0
°C
Outside air temperature threshold for the mode
Summer
summ_on
0 to 12
5
hours
Time before changeover to summer mode
summ_off
0 to 12
5
hours
Time before changeover to winter moder
shc_min
0 to 720
30
minutes
Minimum duration in heating mode
shc_max
-1 to 720 *
180
minutes
Maximum duration in heating mode
dhw_min
0 to 720
30
minutes
Minimum duration in DHW mode
dhw_max
-1 to 720 *
180
minutes
Maximum duration in DHW mode
* -1 means that the maximum value is ignored