D
US
© Danfoss | Climate Solutions | 2023.09
AQ450437934291en-US0301 | 9
Compressor operation is possible within the operating limits.
These can be found in Bock compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
- Permissible ambient temperature -4°F ... 140°F (-20°C ...+60°C).
- Max. permissible discharge end temperature 320°F (160°C).
- Min. discharge end temperature
≥
122°F (50°C).
- Min. oil temperature
≥
86°F (30°C).
- Max. permissible switching frequency 12x/h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
Avoid continuous operation in limit range.
3.3 Limits of application
3
|
Areas of application
Max. permissible operating pressure (LP/HP)
1)
: 100/150 bar (1450/2176 psig)
1)
LP = Low pressure
HP = High pressure