5
|
Electrical connection
Relay position INT69 G
B2 12 14 11
5.7 Function test of the trigger unit INT69 G
Before commissioning, after troubleshooting or making changes to the control power circuit, check
the functionality of the trigger unit. Perform this check using a continuity tester or gauge.
Gauge state
Relay position
1.
Deactivated state
11-12
2.
INT69 G switch-on
11-14
3.
Remove PTC connector
11-12
4.
Insert PTC connector
11-12
5.
Reset after mains on
11-14
5.6 External connection INT69 G
BT1
Cold conductor (PTC
sensor) motor winding