6
2. Connect terminals 14 and 16 to an
ohmmeter
.
3. Turn screw
until the cam
switches
the end switch
and the ohmmeter
shows 0 Ω.
The end switches are adjusted.
Dismounting of Valve and
Actuator
11
DANGER!
Danger of injury by steam or hot water!
Valve without actuator is open
, sealing
is in the actuator.
It is absolutely necessary to depressurize
system prior to dismounting.
Carry out dismounting in reverse order as
mounting.
Installation Guide
AMV 410, AMV 413
DEN-SMT/SI
VI.AA.U4.7S