Danfoss AMV 25 Скачать руководство пользователя страница 3

3

ED.95.R9.02

   © Danfoss 03/2014

DEN-SMT/SI

230V

Data sheet 

Actuators for three point control AMV 25, AMV 35

Wiring

230 Vac version:

Do not touch anything on 

the PCB! Lethal voltage!

Terminals 1, 3:

Control voltage input from the controller.

Power supply 24 V~, 230 V~ (dependent on type)

Terminals 4, 5:

Output used for position indication or 

monitoring.

N

Neutral/Common (0 V)

Additional switches (2

×

)

Additional switches (2

×

) and potentiometer

Accessories

Commissioning

Complete the mechanical and electrical 

installation and perform the necessary checks 

and tests: 

-  Turn on the power.

-  Set the appropriate control signal and  

check that the valve stem direction is correct 

for the application.

The unit is now fully commissioned. 

Manual override

The manual override is achieved by turning the 

manual knob to the required position.

Observe the direction of rotation symbol. 

•   Disconnect control signals

•   Press rubber button

•   Adjust valve position using the control knob

•  Set valve to closed position

•   Restore control signals.