Danfoss AMV 25 Скачать руководство пользователя страница 2

2

ED.95.R9.02

   © Danfoss 03/2014

DEN-SMT/SI

T

max

≤150°C for  AMV 25, 35

and VFS

Adapter for VFS
(Code No.065Z7548)

5

o

5

o

T

max

 = 200°C  for  AMV 25, 35

and VFS

T

max

≤150°C for  AMV 25, 35

and VRB, VRG, VF and VL

Data sheet 

Actuators for three point control AMV 25, AMV 35

Installation

Mechanical

Use 4 mm  Allan key (not part of actuator 

delivery) to mount actuator on the valve. 

Installation of the valve with the actuator is 

allowed in horizontal position or upwards. 

Installation downwards is not allowed.

The actuator must not be installed in an 

explosive atmosphere, at ambient temperature 

lower than 0 °C or at ambient temperature higher 

than 55 °C. It must not be subject to steam jets, 

water jets or dripping liquid as well.

Note:

 the actuator may be rotated up to 360° with 

respect to the valve stem by loosening the retaining 

fixture. Once the actuator is placed, retighten the 

fixture.

Electrical

Electrical connections can be accessed by 

removing the actuator cover. Two cable gland 

entries with thread (M20 x 1.5 and M16 x 1.5) are 

prepared for cable glands. 

  

Note:

 Cable and cable gland used must not 

compromise the actuator’s IP rating, and must 

ensure the connectors are fully strain relieved.

Please observe local rules and regulations as well. 

Disposal

The actuator must be dismantled and the 

elements sorted into various material groups 

before disposal.