2
ED.95.R9.02
© Danfoss 03/2014
DEN-SMT/SI
T
max
≤150°C for AMV 25, 35
and VFS
Adapter for VFS
(Code No.065Z7548)
≈
5
o
≈
5
o
T
max
= 200°C for AMV 25, 35
and VFS
T
max
≤150°C for AMV 25, 35
and VRB, VRG, VF and VL
Data sheet
Actuators for three point control AMV 25, AMV 35
Installation
Mechanical
Use 4 mm Allan key (not part of actuator
delivery) to mount actuator on the valve.
Installation of the valve with the actuator is
allowed in horizontal position or upwards.
Installation downwards is not allowed.
The actuator must not be installed in an
explosive atmosphere, at ambient temperature
lower than 0 °C or at ambient temperature higher
than 55 °C. It must not be subject to steam jets,
water jets or dripping liquid as well.
Note:
the actuator may be rotated up to 360° with
respect to the valve stem by loosening the retaining
fixture. Once the actuator is placed, retighten the
fixture.
Electrical
Electrical connections can be accessed by
removing the actuator cover. Two cable gland
entries with thread (M20 x 1.5 and M16 x 1.5) are
prepared for cable glands.
Note:
Cable and cable gland used must not
compromise the actuator’s IP rating, and must
ensure the connectors are fully strain relieved.
Please observe local rules and regulations as well.
Disposal
The actuator must be dismantled and the
elements sorted into various material groups
before disposal.