Actuator for two point control AMI 140

Data sheet

DH-SMT/SI

VD.KH.B1.02  

©  Danfoss 03/2008

2

Installation

Mechanical

The actuator should be mounted with the valve 

stem in either horizontal position or pointing 

upwards.

The actuator is fixed to the valve body by means 

of a mounting ring which requires no tools for 

mounting. The ring should be tightened by hand.

Electrical

Important: It is strongly recommended that the 

mechanical installation is completed before the 

electrical installation.

Each actuator is supplied with the connecting 

cable for the controller.

Wiring

AMI 140 - 230V

AMI 140 - 24V

Commissioning

The factory setting of the spindle is the fully 

stem up position because of easier mechanical 

connection of the actuator on the valve.

Disposal

The actuator must be dismantled and the 

elements sorted into various material groups 

before disposal.

BLACK

RED

GRAY

Top view

Jumper setting
sw=OFF actuator retracted 
sw=ON  actuator extracted

sw=OFF actuator extracted (pushed)
sw=ON  actuator retracted (pulled) 
default setting for use with ABQM valve

BLUE

BLACK

BROWN

Top view

Jumper setting
sw=OFF actuator retracted 
sw=ON  actuator extracted

sw=OFF actuator extracted (pushed)
sw=ON  actuator retracted (pulled) 
default setting for use with ABQM valve

Common

Black

Bed

Gray

Common

Blue

Black

Brown