Data sheet 

Actuator for modulating control AME 55 QM

2 | © Danfoss | 2016.09

VD.CV.A2.02 

Installation

Mechanical

The actuator should be mounted with the valve 

stem in either horizontal position or pointing 

upwards. Use a 4 mm Allen key (not supplied) to 

fit the actuator to the valve body.

Allow for necessary clearance for maintenance 

purposes.

The valve has position indication rings 

which should be pushed together before 

commissioning; after stroking they indicate the 

ends of the stroke.

Electrical

Electrical connections can be accessed by 

removing the cover. Two M16 

×

 1.5 cable entries 

are provided. Both entries are provided with a 

rubber grommet for use with flexible cable. Note 

that in order to maintain the enclosure IP rating, 

appropriate cable glands must be used.

 

Wiring

Note:
If switch SW6 is set to ON than use this wiring.

Wiring for modulating control

Wiring for 3-point control

The actuator must be dismantled and the 

elements sorted into various material groups 

before disposal.

Disposal

24 Vac only.

Wiring length

Recommended

square of the wiring

0-50 m

0.75 mm

2

> 50 m

1.5 mm

2

Automatic self stroking feature

When power is first applied, the actuator will 

automatically adjust to the length of the valve 

stroke. Subsequently, the self stroking feature 

can be re-initialised by changing position of SW9.

Diagnostic LED

The red diagnostic LED is located on the pcb 

under the cover. It provides indication of three 

operational states: 

•  Actuator Healthy (Permanently ON), 

•  Self Stroking (Flashes once per second), 

•  Error (Flashes 3 times per second - seek 

technical assistance).