5
VD.KH.C6.02
© Danfoss 01/2014
SMT/SI
⑤
①
②
③
④
Data sheet
Actuators for modulating control AME 110 NL, AME 120 NL
• Remove cover
①
• Press and hold the button
②
(on the
bottom side of the actuator) during manual
override
③
• Replace cover
④
• Install actuator on valve
⑤
Remark:
A ‘click’ sound after energising the actuator
indicates that the gear wheel has jumped into
normal position.
If manual override has been used, the Y
signal will not be correct until the actuator
has reached its end position. If this is not
acceptable, reset the actuator.
Manual override
(for service purposes only)
Caution:
Do not manually operate the
drive if power is connected!
Do not dismount the actuator
from the valve when it is in a
stem down position!
If dismounted in a stem down
position, there is a high risk
that the actuator gets stuck.
Dimensions
(mm)