Data sheet
Actuators for modulating control AME 110 NL, AME 120 NL
Technical data
Type
AME 110 NL
AME 120 NL
Power supply
V
24 AC; +20 to −15% *
Power consumption
running
VA
2
standby
W
0,5
Frequency
Hz
50/60
Control input Y
V
0-10 (2-10) Ri = 110 kΩ
mA
0-20 (4-20) Ri = 500 Ω
Closing force
N
130
Stroke
mm
5
Speed
s/mm
24
12
Relative humidity
max. 80 %
Max. medium temperature
°C
120
Ambient temperature
0 … 55
Storage and transport temperature
–40 … 70
Protection class
III safety extra-low voltage
Grade of enclosure
IP 42
Weight
kg
0,3
- marking in accordance with
standards
Low Voltage Directive 2006/95/EC: EN 60730-1, EN 60730-2-14
EMC Directive 2004/108/EEC: EN 61000-6-2, EN 61000-6-3
* 24V AC; +10% to −15% if produced before w18y2013
Installation
Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring, which requires no tools for
mounting. The ring should be tightened by hand.
Electrical
Important:
It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Auto sleep mode
1. If actuator AME 110 NL is charged by 24 V
supply voltage and if it is not installed on
AB-QM valve, it will stop in lower position and
switch off all LED indicators after 5 minutes
2.
It is mandatory to drive the spindle of the
actuator to upper position before it will be
installed on AB-QM valve (please refer to
manual override drawings)!
3. Auto sleep mode switches back to learning
mode by pressing RESET button or by cycling
power supply
Each actuator is supplied with the connecting
cable for the controller.