Akva Lux II TDP-F

Electronic programmable room thermostat 

The Akva Lux II TDP-F types 004U8264 and 004U8044 are equipped 

with a zone valve, and thereby prepared for fitting of a thermal 

actuator TWA-A, which enables connection to an 

electronic pro-

grammable room thermostat

The thermal actuator is switched on by an external contact from 

the room thermostat, and starts to open or close the valve. The ac-

tuating movement is achieved by means of an electrically heated 

expansion element. When the heating current is switched off, the 

actuator shuts or opens the valve.

The actuator is equipped with a visual position indicator to show 

the open or closed position of the valve.

If the substation is connected to a room thermostat the tempera-

ture is controlled by the room thermostat and radiator thermostats. 

Please note that the room thermostat keeps the temperature at a 

constant level in the whole apartment according to the set room 

parameters.

Consult additional maintenance instructions for room thermostat 

for further information. It is recommended to avoid fully opened 

thermostats on some radiators and fully shut-off on others. Higher 

temperature at the top and lower temperature at the bottom part 

of radiators means that the system operation is correct. To keep cor-

rect temperature and friendly microclimate for human beings in the 

apartment, it is recommended to ensure regular airing in rooms.

11.0  Flow regulator

A flow regulator is a control device, which, irrespectively of mains pres-

sure, maintains the designated flow rate. This means that the flow reg-

ulator automatically equalizes all changes in pressure within a large 

pressure range (normally 1 to 10 bar), and thereby ensures a constant.

flow regardless of water supply pressure.

Even at low pressures the required flow is obtained. At high pres-

sures no unnecesssary water is wasted; in fact much water and en-

ergy can be saved by using flow regulators.

DKCD

VI.31.J4.00  02-2002

INSTRUCTIONS

FTC

013R9319

013R9319

Blandekreds på gulvvarmeanlæg.

Floor-heating system.
Fussboden-Mischkreis.
Système de chauffage au sol.
Menginjectie-systeem in vloerverwarming
Blandningskrets i golvvärmeanläggning.
Lattialämmitysjärjestelmä.

Ogrzewanie podłogowe.

Blandekreds på radiator- eller gulvvarmekreds med

veksler.
Heat exchanger in radiator heating or floor heating
system.
Wärmetauscher-Regelung für Heizkörper- und
Fussbodenheizung.
Echangeur thermique dans un système de chauffage
par radiateur ou au sol.
Warmtewisselaar in radiator- of vloerverwarming-
systeem.

Blandningskrets i radiator- eller golvvärmekrets med
värmeväxlare.
Lämmönvaihdin radiaattori- tai

lattialämmitysjärjestelmässä.

Wymiennik ciepła w instalacji z grzejnikami lub

podłogowej.

 Montage af fjernføler

 Mounting of remote sensor
 Montage von Fernfühler
 Montage du capteur à distance
 Montage van afstandsvoeler
 Montering av lös givare
 Anturin asennus

 Mocowanie zdalnego czujnika

 Anlæg

 Systems
 Anlagen

 Système
 Installatie
 Anläggning

 Järjestelmät

 

Zastosowanie

 Montage af termostatisk element

 Mounting of thermostatic head
 Montage von Thermostatkopf
 Montage de la tête thermostatique
 Montage van regelelement
 Montering av regulatordel
 Termostaatin asennus

 

Mocowanie głowicy termostatycznej

1)

2)

3)

Thermal actuator TWA-A

Please note

: Before mounting of 

the electronic room thermostat, an 

thermal actuator TWA-A for ON/OFF 

controls of the heating system must 

be mounted on the zone valve.

Содержание Akva Lux II TDP-F

Страница 1: ...Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Lux II TDP F Instructions for installation and use...

Страница 2: ...9 7 0 Installation instructions Getting started 10 8 0 Installation instructions general 11 9 0 Installation instructions recirculation connection 14 9 1 Installation instructions recirculation conne...

Страница 3: ...7 Air vent 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 38 PTC2 P controller 40 Thermostat for bypass circulation 52 Zone valve 60 Fitting piece for DCW meter Please note that the b...

Страница 4: ...4 Differential pressure controller 5 Dirt strainer 6 Non return valve 17 Air vent 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 38 PTC2 P controller 40 Thermostat for bypass circula...

Страница 5: ...ial pressure controller 5 Dirt strainer 5A Dirt strainer with plug 6 Non return valve 17 Air vent 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 30 Return temperature limiter 38 PTC2...

Страница 6: ...kva Lux II TDP F with bypass thermostat mounted before heat meter Type 004U8044 Akva Lux II TDP F with bypass thermostat mounted after heat meter Connections 1 Domestic cold water DCW 2 Domestic hot w...

Страница 7: ...deally in con nection with readings of the district heating meter Pay special attention to any leaks and an excessively high return tem peratureinthedistrictheatingcircuit poorcoolingofthedistrictheat...

Страница 8: ...hermostat Thermostat Fig 2 that keeps the branch pipe warm in the summer or regulates the circulation temperature if domestic hot water recir culation has been established in the hot water system The...

Страница 9: ...s far as possible do not lift the substation by the pipes Lifting by the pipes may cause leaks REMEMBER to retighten Disposal Dispose of the packaging in accordance with the local regulations for disp...

Страница 10: ...sub station on a solid wall using two sturdy bolts screws expan sion bolts or similar 3 Mount ball valves not part of the delivery on the substation and make sure that they are closed when connnecting...

Страница 11: ...Please note that the connections features EPDM rubber gaskets Therefore it is important that you DO NOT OVERTIGHTEN the union nuts Over tightening may result in leaks Leaks caused by over tightening o...

Страница 12: ...ball valves on the domestic cold water and the do mestic hot water supply Loosen the union nuts at both ends of the fitting piece and remove it Fit the cold water meter remember to insert gaskets Afte...

Страница 13: ...room thermostat keeps the temperature at a constant level in the whole apartment according to the set room parameters Consult additional maintenance instructions for room thermostat for further infor...

Страница 14: ...ation the substation must be connected to the recirculation system The circulation set for recirculation connection is not standard equipment The set must be purchased as extra equipment We recommend...

Страница 15: ...controller Fig 4 Loosen union nuts and remove the existing capillary tube between the bypass thermostat and the T piece as shown in fig 4 Fig 5 Plug the hole with ball C and union nut D Fig 6 Fit new...

Страница 16: ...hten the union nut again Fig 12 Please note that the arrow on the back of the housing indicates the dirction of flow Please note the position of the arrow as shown in the photo to your right Fig 13 Fi...

Страница 17: ...nipple A in the DHW controller pack Fig 3 Fit pipe bushing B in the DHW controller Fig 4 Remove the existing capillary tube and union nut from bypass thermostat and angle piece do not re use Fig 5 Plu...

Страница 18: ...fasten by means of two screws I Fig 9 Mount non return valve J and hexagon nipple K in the pump as shown in the photo to your right Fig 10 Loosen union nut Fig 11 Turn pump motor head by 180 degrees T...

Страница 19: ...structions 1 Start by shutting off all connections to the substation 2 First follow the instructions for Fig 1 2 and 3 on page 16 3 Then demount 3 4 plug in T piece pos A as illustrated in fig 1 4 Rem...

Страница 20: ...non return valve to the recir culation pipe with flow direction towards the substation A safety valve must be mounted in the DCW inlet For recirculation connection please refer to installation instru...

Страница 21: ...Allen key Fig 2 Mount hexagon nipple A in the DHW controller pack and mount hexagon nipple C and union nut D in hexagon nipple A for fitting of recirculation pipe Fig 3 Fit pipe bushing B in the DHW...

Страница 22: ...mount hexagon nipple C and union nut D in hexagon nipple A for fitting of recirculation pipe Fig 3 Fit pipe bushing B in the DHW controller Fig 4 Remove the existing capillary tube and union nut from...

Страница 23: ...ust be mounted before the heat meter Please follow the below instructions 1 Start by shutting off all connections to the substation 2 First follow the instructions for Fig 1 2 and 3 on page 21 3 Then...

Страница 24: ...insulation Fig 1 Remove the nipples plugs from the domestic hot water controller use a 6 mm Allen key Fig 2 Mount hexagon nipple A in the DHW controller pack Fig 3 Mount circulation pipe C incl hexag...

Страница 25: ...before the substation is prepared for recirculation i e the by pass thermostat must be mounted before the heat meter Please follow the below instructions 1 Start by shutting off all connections to the...

Страница 26: ...ng controllerPM2 P Fig 1b RegulationofthehotwatertemperaturePTC2 P SettheDHWtemperaturebymovingtheadjusterlevertowards hotter or colder Startbyturningtheleverclockwise untilitstops untilyou cannot tur...

Страница 27: ...a differential pressure controller type TD200 is mount ed in Akva Lux II TDP F types 004U8089 and 004U8044 This type of differential pressure controller is preset from factory and should not be adjust...

Страница 28: ...eflowreg ulator automatically equalizes all changes in pressure within a large pressurerange normally1to10bar andtherebyensuresaconstant flow regardless of water supply pressure Even at low pressures...

Страница 29: ...Max 4 5Watt For more information about the pump please refer to enclosed instal lation and maintenance instructions WILO STAR Z NOVA Installation and operating instructions D Einbau und Betriebsanlei...

Страница 30: ...isusedonthesecondaryside Ifitbecomes necessarytocleantheexchangerwithacid thiscanbedoneasshown on the drawing to the right Brazed plate heat exchangers can withstand rinsing with a dilute acid sulutio...

Страница 31: ...e a year Check all connections for leaks If you identify a leak replace the gaskets and retighten the pipe connec tions Check that the safety valve on the cold water supply is functioning correctly Ch...

Страница 32: ...Clean dirt strainer Poor cooling Too small heating surface too small radiator in relation to the total heating requirement of the building Poor utilization of existing heating surface Increase total h...

Страница 33: ...tion pump out of operation not part of the dly Check whether the pump is running whether the pump is receiving power control that there is no air in the pump housing see pump manual No domestic hot wa...

Страница 34: ...used in accordance with our instructions EU Directives EMC Directive 2004 108 EEC EN 61000 6 1 2007 Electromagnetic compatibility Generic standard Immunity for residential commercial and light indust...

Страница 35: ...comply with all technical regulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in...

Страница 36: ...Produced by Danfoss Redan A S 09 2012 VI HE A1 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Отзывы: