6
DKRCI.PI.SC0.D2.02 / 520H5637
© Danfoss A/S (AC-SMC/MWA), 01-2012
• Connect the device to the power supply
(see the section "Electrical installation/
connection".
• Press 3 times.
• Press
• Press or to select either SINGLE
or COAXIAL. Press to confirm.
• Press to change the PROBE LENGTH.
Press to change the position of the
cursor.
Press to decrease the value or to
increase the value.
Press to confirm.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
• Press to change of SCALE 4 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press to change of SCALE 20 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete
8-second timeout
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
• Press to confirm.
• Press or to select either
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
You have the possibility of checking
your settings by pressing twice.
Press to return to
default screen.
Quick Setup (all values below are only examples)
Default screen
• Press
• Press
• Press
Enter password:
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
__________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.2.0
TESTS
AKS 4100
2.2.1
SET OUTPUT
AKS 4100
SET OUTPUT
3.5 mA
AKS 4100
SET OUTPUT
8 mA
AKS 4100
DISTANCE
5000 mm
• Press
• Press
• Press
• Press to decrease the value or to
increase the value.
Press to confirm.
• Press 4 times to return to default
screen.
Default screen appears:
Force mA completed and disabled
How to force mA output (all values below are only examples)
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
Note:
The signal converter can be programmed with or without mechanical process connector assembled.
AKS 4100
SINGLE CABLE 5000 mm
(0%) 4 mA
4877 mm
(100%) 20 mA
120 mm