AKD 2800
Programming
Torque [%]
denotes the motor
’
s present load in
relation to the motor
’
s rated torque.
Power [kW]
gives the present power that the
motor is absorbing in kW.
Power [HP]
gives the present power that the
motor is absorbing in HP.
Motor voltage[V]
gives the voltage supplied to the motor.
DC link voltage [V]
gives the intermediate circuit
voltage of the frequency converter.
Thermal load motor [%]
gives the calculated/estimated
load on the motor. 100 % is the cut-out limit.
Thermal load [%]
gives the calculated/estimated
thermal load on the frequency converter. 100
% is the cut-out limit.
Running hours [Hours]
gives the number of hours that
the motor has tun since the last reset in parameter
619
Reset of running hours counter
.
Digital input [Binary code]
gives the signal status
from the 5 digital inputs (18, 19, 27, 29 and 33).
Terminal 18 corresponds to the bit on the extreme
left. ‘0
’
= no signal, ‘1
’
= signal connected.
Analog input 53 [V]
gives the voltage value of terminal 53.
Analog input 60 [mA]
gives the present value
of terminal 60.
Pulse reference [Hz]
gives the reference in Hz
connected to terminal 33.
External reference [%]
gives the sum of
external references as a percentage (sum of
analogue/pulse/serial communication) in the
range from Minimum reference, Ref
MIN
to
Maximum reference, Ref
MAX
.
Status word [Hex]
gives one or several status
conditions in a Hex code. See
Serial communication
in the
Design Guide
for further information.
Heatsink temp.[°C]
gives the present heatsink
temperature of the frequency converter. The
cut-out limit is 90-100°C, while cutting back
in occurs at 70 ± 5°C.
Alarm word [Hex]
gives one or several alarms
in hex code. See
Serial communication
in the
Design Guide
for further information.
Control word [Hex]
gives the control word for the
frequency converter. See
Serial communication
in
the
Design Guide
for further information.
Warning word [Hex]
gives one or several warnings
in hex code. See
Serial communication
in the
Design Guide
for further information.
Extended status word [Hex]
gives one or several status
modes in Hex code. See
Serial communication
in
the
Design Guide
for further information.
Communication option card warning [Hex]
gives a
warning word if there is a fault in the communication
bus. Only active if communication options are installed.
If there are no communication options 0
Hex is displayed.
Pulse count
gives the number of pulses that
the unit has registered.
010 Small display line 1.1
(DISPLAY LINE 1.1)
Value:
See par. 009
Large display readout
✭
Reference [%] [1]
Function:
In this parameter, the first of three data values
can be selected that is to be displayed in the LCP
control unit display, line 1, position 1. This is a useful
function, e.g. when setting the PID regulator, as
it gives a view of process reactions to reference
changes. The display readout is activated by
pushing the [DISPLAY STATUS] key.
Description of choice:
See parameter 009
Large display readout
.
011 Small display readout 1.2
(DISPLAY LINE 1.2)
Value:
See parameter 009
Large display readout
✭
Motor current [A][6]
Function:
See the functional description given under parameter
010
Small display readout
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.H2.02 -
15