3.0 Appendix

Site Survey considerations

Location of Com-Trol 4k2 or 4k2e - Note whether box mount or panel-mount.
Modem location (6k)
Danfoss Logger requirements?
Location of CWeb or 5K (if applicable)
Leak detector location and type
Note any HGM 300 units and number of zones
Document Com-Trol hardware copyright dates.  Dates prior to 1998 will cause compatibility issues (see figure 7)
Determine optimum Ethernet switch location and Cat5 cable length
Danfoss highly recommends that all power, communications, grounding connections and termination resistors 

pertaining to the Com-Trol I/O boards are reviewed before conversion to the Danfoss AK 255.
Note any global bus devices that exist and considerations for each (Energy meters, lighting panels, etc.)

 

Figure 7 - example of Com-Trol I/O board with copyright date of 1994 - this is 

not

 compliant or suitable for a Danfoss retro-fit 

operation.  Seek to have older boards (pre 1998) to be either replaced with Danfoss I/O or newer Com-Trol I/O 

NOTES








Содержание AK-SC255

Страница 1: ...DANFOSS NORTH AMERICA Recommended Installation guide AK SC255 Com Trol local bus support V1 0 MAKING MODERN LIVING POSSIBLE...

Страница 2: ...Table of contents Page 3 Introduction and document scope Page 4 1 0 Intended application Hardware Software Page 5 2 0 Programming AK SC255 Database Page 6 3 0 Appendix...

Страница 3: ...the Danfoss AK SC255 has been suitably installed it will provide many years of trouble free efficient operation in parallel with the existing Com Trol local bus I O boards This installation guide does...

Страница 4: ...be applied and maintained see figure 3 below Existing system capacity for number of Com Trol I O boards defined by Com Trol documentation must be maintained AK SC255 software version R2 151 and above...

Страница 5: ...same version for the database pro gramming that will be installed in the physical AK SC255 unit 3a Start configuration of the AK SC255 database by setting the Legacy I O type to COMTL found in the St...

Страница 6: ...optimum Ethernet switch location and Cat5 cable length Danfoss highly recommends that all power communications grounding connections and termination resistors pertaining to the Com Trol I O boards are...

Страница 7: ...ible errors in catalogs brochures or other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that alterations can...

Отзывы: