1.0 Intended application (Hardware / Software)

The following important points define the intended application scope for a Com-Trol (local bus) retro-fit installation.  Please 

read these fundamental requirements before continuing. 

•  One Com-Trol 4K/4K2e should be replaced with one Danfoss AK-SC255 unit

•  The Danfoss AK-SC255 RS-485 (Modbus) port is used for communication to the Com-Trol I/O boards (figure 1).  

Host 

      communication to other AK -SC255 and/or AK-SC255 Loggers must be done via the Ethernet port

.

•  Only one local bus loop can be connected to the AK-SC255 (figure 1) - No star wiring configurations allowed

•  Valid local bus termination and wiring rules must be applied and maintained (see figure 3 below)

•  Existing system capacity for number of Com-Trol I/O boards (defined by Com-Trol documentation) must be maintained

•  AK-SC255 software version R2.151 and above must be used in order to provide Com-Trol support

•  The AK-SC255 being used in the application must have a valid Com-Trol license installed.   If a license is required contact

      Danfoss Customer service on 410-931-8714 with the AK-SC255 MAC address

Power Connection

(100 - 240 V a.c.)

LonWorks© Port(s)

RS485 Modbus - Used for COM-Trol local bus

Alarm Relay

External Modem  

Port

Ethernet

Fuse (1 Amp) 30 V d.c. 

Direct 

Connect

Port

Door latch

CPU Card

Battery

Battery Jumper 

circuit

Address 

Switch

Figure 2- AK-SC255 Internal port and connection layout

Figure 3- Com-Trol recommended wiring standard  

(extract from Com-Trol MCS-4xxx and 4K2e Install manual (F-27262-4)

Содержание AK-SC255

Страница 1: ...DANFOSS NORTH AMERICA Recommended Installation guide AK SC255 Com Trol local bus support V1 0 MAKING MODERN LIVING POSSIBLE...

Страница 2: ...Table of contents Page 3 Introduction and document scope Page 4 1 0 Intended application Hardware Software Page 5 2 0 Programming AK SC255 Database Page 6 3 0 Appendix...

Страница 3: ...the Danfoss AK SC255 has been suitably installed it will provide many years of trouble free efficient operation in parallel with the existing Com Trol local bus I O boards This installation guide does...

Страница 4: ...be applied and maintained see figure 3 below Existing system capacity for number of Com Trol I O boards defined by Com Trol documentation must be maintained AK SC255 software version R2 151 and above...

Страница 5: ...same version for the database pro gramming that will be installed in the physical AK SC255 unit 3a Start configuration of the AK SC255 database by setting the Legacy I O type to COMTL found in the St...

Страница 6: ...optimum Ethernet switch location and Cat5 cable length Danfoss highly recommends that all power communications grounding connections and termination resistors pertaining to the Com Trol I O boards are...

Страница 7: ...ible errors in catalogs brochures or other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that alterations can...

Отзывы: