Setting of presettings (r89).
After setting 1-5,  
setting is returned to 0. 

Food type =

1

Vege-

tables

2

Milk

3

Meat/

fish

4

Frozen

food

5

Ice

cream

Temperature (r00)

8 °C

0 °C

-2 °C

-20 °C

-24 °C

Max. temp. setting (r02)

10 °C

4 °C

2 °C

-16 °C

-20 °C

Min. temp. setting (r03)

4 °C

-4 °C

-6 °C

-24 °C

-28 °C

Upper alarm limit (A13)

14 °C

8 °C

8 °C

-15 °C

-15 °C

Lower alarm limit (A14)

0 °C

-5 °C

-5 °C

-30 °C

-30 °C

Upper alarm limit for S6 (A22)

14 °C

8 °C

8 °C

-15 °C

-15 °C

Lower alarm limit for S6 (A23)

0 °C

-5 °C

-5 °C

-30 °C

-30 °C

Can only be set when r12=0.

Food type

Get a good start

With the following procedure you can start regulation very quickly:
1.  Open parameter r12 and stop the regulation (in a new and 

not previously set unit, r12 will already be set to 0 which 
means stopped regulation.)

2.  Select application based on the wiring diagrams on pages 2-4
3.  Open parameter o61 and set the application number
4.  For network. Set the address in o03
5.  Then select a set of presets from the "Food type" help table
6.  Open parameter r89 and set the number for the array of 

presettings. The few selected settings will now be transferred 
to the menu

7.  Set the desired cut-out temperature r00
8.  Select refrigerant via parameter o30
 

(only application 5-9)

9.  Set the pressure transmitter min. and max. range via 

parameter o20 and o21 (only application 5-9)

10.  Set the desired defrost method in d01
11.  Set the interval time between defrost starts in d03
12.  Set the desired defrost sensor in d10
13.  Set the maximum defrost time in d04
14.  Set the defrost stop temperature in d02
15.  Open parameter r12 and start the regulation
16.  Go through the parameter list and change the factory values 

where needed.

17.  Get the controller up and running on network:
 

• MODBUS: Activate scan function in system unit

 

• If another data communication card is used in the controller:

 

 

- Lon RS485: Activate the function o04

SET

Set

(PS)

<

cFg

SET

Þ

r12

Main switch

<

o61

Application

r--

M

enu g

roups 

See also the f

ollo

wing pages

.

o03

MODBUS address

A--

r89

Food type

c--

r00

Cut-out temperature

d--

o30

Refrigerant type

n--

o20

Min. transmitter range

F--

o21

Max. transmitter range

t--

d01

Defrost method

o--

d03

Defrost interval

p--

d10

Defrost sensor

q--

d04

Max. defrost time

u--

d02

Defrost stop temperature

<

<

(Return)

(Return)

Parameter grouping at display operation

SET button, 3 s: Configuration settings

PS: Password (if any)

Info button, 3 s: Information for service 
use

Output status

When you want info on a relay 
output, the dot will show whether 
the relay is activated (energized) 
for e.g.:  
do4 = not activated 
do.4 = activated

*)
The output's function. 
(Determined at configuration).
The DOs and AOs can also be forced 
controlled from this menu, when r12 Main 
switch has been set in position "service".
Forced control of a function can also be 
performed in codes q11 to q27.

**)
The input's function.
(Determined at configuration).

© Danfoss | DCS (vt) | 2019.10

AN300028324304en-000401 | 9

Содержание AK-CC55

Страница 1: ...084R8054 AN300028324304en 000401 Installation Guide AK CC55 Compact Danfoss DCS vt 2019 10 AN300028324304en 000401 1 Principle Dimensions Identification 084B4081...

Страница 2: ...3 8 9 7 10 11 12 Alarm 13 14 Fan 16 15 17 Defrost Danfoss 84B3257 10 Comp 1 40 41 42 43 44 S3 45 46 S4 47 48 S5 49 50 AI5 60 61 DI2 DI1 70 71 AO1 83 84 85 B A MODBUS 115 230V AC L N 1 2 3 8 9 7 10 11...

Страница 3: ...3 47 48 S4 49 50 AI5 60 61 DI2 S5 Pe 5V s 70 71 AO1 83 84 85 B A MODBUS 115 230V AC L N 1 2 3 8 9 7 10 11 12 Alarm 13 14 Fan 16 15 17 Defrost Danfoss 84B3262 10 AKV 6 40 41 42 43 44 S3 45 46 S4 47 48...

Страница 4: ...S3 47 48 S4 49 50 AI5 60 61 DI2 S5 Pe 5V s 70 71 AO1 83 84 85 B A MODBUS 115 230V AC L N 1 2 3 8 9 7 10 11 12 Railheat 13 14 Fan 16 15 17 Defrost Danfoss 84B3264 10 AKV 8 40 41 42 43 44 S2 45 46 S3 4...

Страница 5: ...AKV info Application 5 9 Relay info Application 1 4 230 V or 115 V AC coil AKS 32R info Application 5 9 The signal from one pressure transmitter can be received by up to 10 controllers There must not...

Страница 6: ...urement it will appear as AI5 DI1 Digital input signal The defined function is active when the input is short circuited or opened depending on the function defined in o02 DI2 Digital input signal The...

Страница 7: ...ectric noise Cables for sensors low voltage DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance between cables of at least 10 cm...

Страница 8: ...down arrow simultaneously UnL The configuration is unlocked The parameter has reached min or max limit PS A password is required for access to the menu Fan Appliance cleaning has been initiated The f...

Страница 9: ...Set the pressure transmitter min and max range via parameter o20 and o21 only application 5 9 10 Set the desired defrost method in d01 11 Set the interval time between defrost starts in d03 12 Set th...

Страница 10: ...riods 1 2 r16 1 1 1 1 1 1 1 1 1 0 hrs 10 hrs 1 Duration of melt periods 1 2 r17 1 1 1 1 1 1 1 1 1 0 min 30 min 5 Temperature setting for thermostat band 2 As differential use r01 0 2 r21 1 1 1 1 1 1 1...

Страница 11: ...ree at PWM 1 2 n64 1 1 1 1 n65 100 100 Min opening degree at PWM 1 2 n65 1 1 1 1 0 n64 0 Expert setting Wind up at PWM 1 2 n66 1 1 1 1 0 2 1 0 1 0 Expert setting Kp at PWM 1 2 n67 1 1 1 1 0 5 10 0 4 0...

Страница 12: ...507 18 R402A 19 R404A 20 R407C 21 R407A 22 R407B 23 R410A 24 R170 25 R290 26 R600 27 R600a 28 R744 29 R1270 30 R417A 31 R422A 32 R413A 33 R422D 34 R427A 35 R438A 36 R513A 37 R407F 38 R1234ze 39 R1234y...

Страница 13: ...t Rfg factor K1 1 3 P83 1 1 1 1 1 999 999 300 User defined refrigerant 3 digit Rfg factor K2 1 3 P84 1 1 1 1 1 999 999 300 User defined refrigerant 3 digit Rfg factor K3 1 3 P85 1 1 1 1 1 999 999 300...

Страница 14: ...or temperature To Calculated 0 0 u26 1 1 1 1 1 Status on DI2 input on 1 closed 0 0 u37 1 1 1 1 1 1 1 1 1 Readout display 1 value 0 0 u56 1 1 1 1 1 1 1 1 1 Readout of alarm air temp Section A 0 0 u57 1...

Страница 15: ...tion stopped refrigeration via r12 or DI input 8 A59 Case clean Appliance cleaning Signal from DI input 8 AA2 Refrig Leak A refrigerant leak detection signal is received 9 AA3 CO2 alarm A refrigerant...

Страница 16: ...pped due to open ON input or stopped regulation S16 16 Door is open DI input is open S17 17 Melt function in progress Refrigeration is interrupted S18 18 Modulating thermostat control S19 19 Emergency...

Отзывы: