Danfoss AK-CC 550B Скачать руководство пользователя страница 20

20 

Manual RS8GL302 © Danfoss 2016-03 

AK-CC 

550B

Miscellaneous

Miscellaneous

Delay of output signal after start-up

After start-up or a power failure the controller’s functions can be delayed so that over-

loading of the electricity supply network is avoided. 

Here you can set the time delay.

o01

DelayOfOutp.

Digital input signal - DI1

The controller has a digital input 1 which can be used for one of the following func-

tions:

Off: The input is not used

1) Status display of a contact function

2) Door function. When the input is open it signals that the door is open. The refrig-

eration and the fans are stopped and light switched on. When the time setting in 

“A04” is passed, an alarm will be given and refrigeration will be resumed (o89).

3) Door alarm. When the input is open it signals that the door is open. When the time 

setting in “A04” is passed, there will be alarm.

4) Defrost. The function is started with a pulse signal. The controller will register when 

the DI input is activated. The controller will then start a defrost cycle.

5) Main switch. Regulation is carried out when the input is short-circuited, and regula-

tion is stopped when the input is put in pos. OFF.

6) Night operation. When the input is short-circuited, there will be regulation for 

night operation.

7) Thermostat band changeover. Switch to thermostat 2 (r21).

8) Separate alarm function. Alarm will be given when the input is short-circuited.

9) Separate alarm function. Alarm will be given when the input is opened.   (For 8 and 

9 the time delay is set in A27)

10) Case cleaning. The function is started with a pulse signal. See also description on 

page 5.

11) Forced refrigeration at hotgas defrost when the input is short-circuited.

12) Night cover

13,14) Not used

15) Appliance shutdown

o02

DI 1 Config.

Definition takes place with the nu-

merical value shown to the left.

(0 = off)

DI state

(Measurement)

The DI input’s present status is shown 

here. ON or OFF.

If the controller is built into a network with data communication, it must have an 

address, and the master gateway of the data communication must then know this 

address.

The address is set between 0 and 240, depending on the system unit and the selected 

data communication. If the system unit is gateway type AKA 245, the version must be 

6.20 or higher.

o03

The address is sent to the gateway when the menu is set in pos. ON

IMPORTANT: Before you set o04, you MUST set o61. Otherwise you will be transmit-

ting incorrect data.

(The function is not used when the data communication is MODBUS)

o04

Access code 1 (Access to all settings)

If the settings in the controller are to be protected with an access code you can set a 

numerical value between 0 and 100. If not, you can cancel the function with setting 0. 

(99 will always give you access).

o05

Acc. code

Sensor type for S3, S4, S5, S6

Normally a Pt 1000 sensor with great signal accuracy is used. But you can also use a 

sensor with another signal accuracy. That may either be a PTC 1000 sensor.

All the mounted sensors S3-S6 must be of the same type.

o06

SensorConfig

Pt = 0

PTC = 1

Max. standby time after coordinated defrost

When a controller has completed a defrost it will wait for a signal which tells that the 

refrigeration may be resumed. If this signal fails to appear for one reason or another, 

the controller will itself start the refrigeration when this standby time has elapsed.

o16

Max HoldTime

Select signal for the display S4%

Here you define the signal to be shown by the display.

S3, S4, or a combination of  the two.

With setting 0% only  S3 is used. With 100% only S4.

o17

Disp. S4%

Pe. Working range for pressure transmitter - min. value

o20

MinTransPres

Pe. Working range for pressure transmitter - max. value

o21

MaxTransPres

Refrigerant setting (only if "r12" = 0)

Before refrigeration is started, the refrigerant must be defined. You may choose be-

tween the following refrigerants

1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  6=R13.  7=R13b1.  8=R23.  9=R500.  

10=R503.  11=R114.  12=R142b. 13=Userdefined. 14=R32. 15=R227.  16=R401A.  

17=R507. 18=R402A.  19=R404A. 20=R407C.  21=R407A.  22=R407B.  23=R410A.  

24=R170.  25=R290.  26=R600.  27=R600a.  28=R744.  29=R1270. 30=R417A. 

31=R422A.  32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=R513A. 37=R407F.

Warning: Wrong selection of refrigerant may cause damage to the compressor.

Other refrigerants: Here Setting 13 is selected and then three factors -Ref.Fac a1, a2 

and a3 - via AKM must be set.

o30

Refrigerant

Содержание AK-CC 550B

Страница 1: ...Manual Controller for appliance control AK CC 550B User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...ing sensor In addition to the outlet to the electronic injection valve of the type AKV the controller has 5 relay outputs which are defined by the use selected the individual usage options are describ...

Страница 3: ...d applica tion Application 9 This use is for refrigeration appliances with one valve two evapo rators and two refrigeration sections each with its own tempera ture measurement There are shared alarm l...

Страница 4: ...the evaporator S4 respectively A setting for the thermostat alarm thermostat and display reading deter mines how much the two sensor values should influence each individual function e g 50 will produc...

Страница 5: ...nction is not available in application 9 Appliance cleaning This function makes it easy for the shop s staff to carry out a cleaning of the appliance according to a standard procedure Appliance cleani...

Страница 6: ...a heating element in the drip tray for hot gas defrosting When defrosting is commenced the heating element is activated The heating element remains activated until a set time after defrosting has ende...

Страница 7: ...rooms A value is calculated for the evaporator air flow The evaporator is monitored and the next scheduled defrost will be carried out as required If the function does not require a defrost at the ti...

Страница 8: ...always have top priority during normal regulation But if one of the override functions is activated the Min On time will be disregarded Railheat It is possible to pulse control the power to the rail h...

Страница 9: ...ight is controlled via the day night function the light is controlled via the data communication from a system unit Here there are two operational options if data communication should fail The light c...

Страница 10: ...in operation Door contact The door contact function can via the digital inputs be defined for two different applications Alarm monitoring The controller monitors the door contact and delivers an alar...

Страница 11: ...ndex A version with screw terminals The controllers address must be set higher than 0 in order for the display to be able to communicate with the controller If connection of two displays is required o...

Страница 12: ...is a product sensor but in application 9 it has a different use DI1 DI2 and DI3 are contact functions that can be used for one of the fol lowing functions door function alarm function defrost start e...

Страница 13: ...s of the light function when the light is switched on the night blinds are up and when the light is switched off the night blinds are down In addition a digital input provides the option of forced ope...

Страница 14: ...signs from the factory indicating application 1 If you employ another use signs are provided so that you can mount the relevant one The number is indicated on the left hand side of the signs Use the s...

Страница 15: ...alues in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the set ting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from S3 a...

Страница 16: ...active until the set time delay has been passed The time delay is set in minutes A03 Alarm delay Time delay for door alarm The time delay is set in minutes The function is defined in o02 o37 or in o8...

Страница 17: ...two compressors Settings indicate the time that has to elapse from the first relay cuts in and until the next relay has to cut in c05 Step delay The LED on the controller s front will show whether re...

Страница 18: ...rost Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again The time when water is tied to the evaporator d07 FanStartDel Fan start temperature...

Страница 19: ...e will be re start at 2 K below the setting The function is not active during a defrost or start up after a defrost With setting 50 C the function is interrupted F04 FanStopTemp Pulse operation of fan...

Страница 20: ...ss The address is set between 0 and 240 depending on the system unit and the selected data communication If the system unit is gateway type AKA 245 the version must be 6 20 or higher o03 The address i...

Страница 21: ...be a time delay of two minutes before the light is switched off 4 As 2 but if there are any 15 minute network errors the light will switch on and the night blind will open o38 Light config Activation...

Страница 22: ...rlier in the manual o87 DewP Max lim Lowest permitted rail heat effect Here the part of the effect to be achieved when the dew point value is minimum o88 Rail Min ON Start of refrigeration when door i...

Страница 23: ...t u63 Light relay Status on relay for valve in suction line u64 SuctionValve Status on relay for compressor 2 u67 Comp2 relay Temperature measured with S5B sensor u75 S5 temp B Temperature measured wi...

Страница 24: ...for the time to run out S4 4 Refrigeration stopped by main switch Either with r12 or a DI input S10 10 Refrigeration stopped by thermostat S11 11 Defrost sequence Defrost in progress S14 14 Defrost se...

Страница 25: ...A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case clean Case cleaning Signal from DI input A70 High temp S3B Hig...

Страница 26: ...scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower button and select the new value 3 Push the middle button again to co...

Страница 27: ...Min temp setting r03 0 C 4 C 30 C 0 C 2 C 24 C Sensor signal for thermostat S4 r15 100 0 Alarm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for...

Страница 28: ...0 Delay for door alarm A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 1 1 1 1 1 1...

Страница 29: ...Clock Setting of hours t07 1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0 Clock Setting of minute t08 1 1 1 1 1 1 1 1 1 1 0 min 59 min 0 Clock Setting of date t45 1 1 1 1 1 1 1 1 1 1 1 day 31 day 1 Clock Setting...

Страница 30: ...eration 7 thermostat band changeover activate r21 8 Not used 9 Not used 10 case cleaning pulse signal 11 forced cooling at hot gas defrost 12 night cover 13 Not used 14 Refrigeration stopped forced cl...

Страница 31: ...2 u67 1 Temperature measured with S5B sensor u75 1 Temperature measured with S3B sensor u76 1 1 Status on relay for hot gas drain valve u80 1 Status on relay for heating element in drip tray u81 1 Sta...

Страница 32: ...3B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data communication module is inserted in the controller The module can be a LON RS485 DANBUSS or a MODBUS T...

Страница 33: ...is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail heat Compressor 2 There is connection between...

Страница 34: ...e used Relays CE 250 V a c DO3 DO4 4 3 A DO2 DO5 DO6 4 3 A Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density IP 20 Mount...

Страница 35: ...L L Type Function Code no AK CC 550B Case controller with MODBUS data communication 084B8032 EKA 175 Data communication module LON RS 485 084B8579 EKA 178B Data communication module MODBUS 084B8571 EK...

Страница 36: ...erves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi...

Отзывы: