Danfoss AK-CC 550 Скачать руководство пользователя страница 7

AK-CC 550 

Manual  RS8EN502  ©  Danfoss  02-2010 

7

Coordinated defrost

There are two ways in which coordinated defrost can be arranged. 

Either with wire connections between the controllers or via data 

communication

Wire connections
The digital input DI2 is connected between the current controllers.
When one controller starts a defrost all the other controllers will 
follow suit and likewise start a defrost. After the defrost the indi

-

vidual controllers will move into waiting position. When all are in 
waiting position there will be a change-over to refrigeration.

Coordination via data communication
Here the system unit handles the coordination.

The controllers are gathered in defrosting groups and the system 
unit ensures that defrosting is started in the group according to a 

weekly schedule.
When a controller has completed defrosting, it sends a message 
to the system unit and then goes into a waiting position. When 
every controller in the group is in a waiting position, refrigeration 
is again permitted in all the individual controllers.

System manager

Defrost on demand

1 Based on refrigeration time

When the aggregate refrigeration time has passed a fixed time, 

a defrost will be started.

2 Adaptive defrosting based on monitoring of evaporator per

-

formance 
This function is based on a registration of the air flow through 

the evaporator. By using the AKV valve as mass flowmeter for the 

refrigerant flow it is possible to compare the energy input on the 
refrigerant side with the energy output on the air side. Via this 

comparison the air flow through the evaporator can be deter

-

mined and hence also the amount of ice/frost build-up on the 
evaporator surface. If the ice/frost build-up reduces the capac

-

ity of the evaporator the function will carry out an additional 

defrost.

Enter in the weekly defrost schedule the number of defrosts 
corresponding to the basic load. If the load of the evaporator is 

increased beyond this, defrost on demand will add the required 
additional defrosts.
The function requires the following connections:

- Expansion valve type AKV
- Temperature signal from both S3 and S4
- Temperature signal from the condensing pressure Pc which is to 

be distributed via the network from the system manager.

NOTE. The S3 and S4 sensors must be placed in the air flow/chan

-

nel immediately before/after the evaporator. 

Min. time between defrosts
There is a 2 hours minimum time between defrosts.

This avoids that planned defrosts in accordance with the weekly 

schedule are carried out immediately after a defrost on demand 
has been carried out. The time applies from when a defrost on 
demand has been completed to when a planned defrost is again 
permitted. The defrost on demand will not start defrosting with a 

shorter interval than the 2 hours either.

Reset

If the adaptive defrost function registers problems with the 

defrost, it will show an error message and the function will no 

longer carry out extra defrosts. In this event a manual reset of the 
function via d22 should be carried out.
When the reset function is activated it will start a defrost so that 
the subsequent tuning will take place on an evaporator with no 
ice/frost build-up.

Note

The function "Adaptive defrost” should only be activated when the 
evaporator runs under normal operational conditions.

Melting function

This function will stop the air flow in the evaporator from being re

-

duced by frost created by uninterrupted operation for a long time.

The function is activated if the thermostat temperature has 

remained in the range between -5°C and +10°C for a longer 

period than the set melting interval. The refrigeration will then be 

stopped during the set melting period. The frost will be melted 

so that the air flow and hence the evaporator’s capacity will be 
greatly improved.

Real-time clock

The controller has a built-in real-time clock which can be used to 
start defrosts. This clock has a power reserve of four hours. 
If the controller is equipped with data communication, the clock 

will automatically be updated from the system unit. 

Max. 10

Содержание AK-CC 550

Страница 1: ...Controller for appliance control AK CC 550 Manual...

Страница 2: ...rosting sensor In addition to the outlet to the electronic injection valve of the type AKV the controller has 5 relay outputs which are defined by the use selected the individual usage options are des...

Страница 3: ...s use is for refrigeration appliances with one valve two evapo rators and two refrigeration sections Here the temperature and alarm monitoring are always controlled using the S4 sensor The S3 sensor i...

Страница 4: ...rol The temperature in the appliance is registered by one or two temperature sensors which are located in the air flow before the evaporator S3 or after the evaporator S4 respectively A setting for th...

Страница 5: ...be used and which can register and monitor the temperature in the warmest part of the appliance There are separate alarm limits and time delays for the product sensor Appliance cleaning This function...

Страница 6: ...a heating element in the drip tray for hot gas defrosting When defrosting is commenced the heating element is activated The heating element remains activated until a set time after defrosting has ende...

Страница 7: ...eased beyond this defrost on demand will add the required additional defrosts The function requires the following connections Expansion valve type AKV Temperature signal from both S3 and S4 Temperatur...

Страница 8: ...have top priority during normal regulation But if one of the override functions is activated the Min On time will be disregarded Railheat It is possible to pulse control the power to the rail heat in...

Страница 9: ...day night function the light is controlled via the data communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay...

Страница 10: ...ion Door contact The door contact function can via the digital inputs be defined for two different applications Alarm monitoring The controller monitors the door contact and delivers an alarm message...

Страница 11: ...connected to the built in MODBUS the display can advantageously be changed to one of the same type but with Index A version with screw terminals If connection of two displays is required one must be c...

Страница 12: ...a product sensor but in application 9 and 10 it has a different use DI1 DI2 and DI3 are contact functions that can be used for one of the fol lowing functions door function alarm function defrost star...

Страница 13: ...n the light is switched off the night blinds are down In addition a digital input provides the option of forced opening of the blinds so that the appliance can be filled with products Application 8 He...

Страница 14: ...icating application 1 If you employ another use signs are provided so that you can mount the relevant one It is only the lower sign that needs to be mounted The number is indicated on the left hand si...

Страница 15: ...f signal from S3 Compensation possibility due to long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started stopped or a manual override of the outputs...

Страница 16: ...A12 Pulldown del Upper alarm limit Here you set when the alarm for high temperature is to start The limit value is set in C absolute value The limit value will be raised during night operation The val...

Страница 17: ...temperature sensor Defrost method Here you set whether defrost is to be accomplished with electricity gas or none During defrost the defrost relay will be cut in d01 Def method 0 non 1 El 2 Gas Defro...

Страница 18: ...unT Delay on stop of heating in the drip tray The time applies from the time the defrost stops by time or temperature to the time the heating element in the drip tray needs to be disconnected d20 Drip...

Страница 19: ...R 2 Temperature sensor S1 Pt1000 Ohm at 0 C n57 Pe S1 select Fan Fan control Fan stop temperature The function stops the fans in an error situation so that they will not provide power to the appliance...

Страница 20: ...ress The address is set between 0 and 240 depending on the system unit and the selected data communication If the system unit is gateway type AKA 245 the version must be 6 20 or higher o03 The address...

Страница 21: ...two minutes before the light is switched off 4 As 2 but if there are any 15 minute network errors the light will switch on and the night blind will open o38 Light config Activation of light relay The...

Страница 22: ...m This function is discussed earlier in the manual o86 DewP Min lim Dew point value where the rail heat is maximum This function is discussed earlier in the manual o87 DewP Max lim Lowest permitted ra...

Страница 23: ...or cooling u58 Comp1 LLSV Status on relay for fan u59 Fan relay Status on relay for defrost u60 Def relay Status on relay for railheat u61 Railh relay Status on relay for alarm u62 Alarm relay Status...

Страница 24: ...es S3 3 The evaporator drips off and waits for the time to run out S4 4 Refrigeration stopped by main switch Either with r12 or a DI input S10 10 Refrigeration stopped by thermostat S11 11 Defrost seq...

Страница 25: ...ure alarm High S6 1 A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case...

Страница 26: ...e button until the temperature value is shown 2 Push the upper or the lower button and select the new value 3 Push the middle button again to conclude the setting Reading the temperature at defrost se...

Страница 27: ...Alarm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 12h 8h 8h 6h Defrost sens...

Страница 28: ...ost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 1 1 1 1 1 1 1 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 1 1 1 1 1 1 1 1 1 50 C 50 C 30 High alarm limi...

Страница 29: ...1 1 1 1 1 50 C 50 C 50 Pulse operation on fans 0 No pulse operation 1 At thermostat cuts out only 2 Only at thermostat cut outs during night operation F05 1 1 1 1 1 1 1 1 1 1 0 2 0 Period time for fa...

Страница 30: ...ings o67 1 1 1 1 1 1 1 1 1 1 0 Off 1 On 0 Off Input signal on DI3 Function high voltage input 0 not used 1 status on DI2 2 door function with alarm when open 3 door alarm when open 4 defrost start pul...

Страница 31: ...cooling u58 1 1 1 1 Status on relay for fan u59 1 1 1 1 1 1 1 1 1 1 Status on relay for defrost u60 1 1 1 1 1 1 1 1 1 Status on relay for railheat u61 1 1 1 1 1 1 1 Status on relay for alarm u62 1 1 1...

Страница 32: ...s which EKA Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data com...

Страница 33: ...e hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail heat...

Страница 34: ...30 V a c Electrical con nection cable Max 1 5 mm2 multi core cable Solid state output DO1 for AKV coil Max 240 V a c Min 28 V a c Max 0 5 A Leak 1 mA Max 1 pcs AKV Relays CE 250 V a c DO3 DO4 4 3 A DO...

Страница 35: ...th plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw terminals 084B8562 EKA 164A Extern...

Страница 36: ...rves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specific...

Отзывы: