Select signal for display view. S4% (100%=S4, 0%=S3)
o17
1
1
0 %
100 %
100
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door
alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night
operation 7=
Thermostat band changeover
(activate r21). 8=alarm function
when closed. 9=alarm function when open. 10=case cleaning (pulse signal).
12=night cover, 13=coordinated defrost). 15=application shutdown
o37
1
1
0
15
0
Configuration of light function
: 1=Light follows day /night operation,
2=Light control via data communication via ‘o39’, 3=Light control with
a DI-input, 4=As "2", but light switch on and night cover will open if the
network cut out for more than 15 minutes.
o38
1
1
1
4
1
Activation of light relay (only if o38=2)
On=light
o39
1
1
0/Off
1/On
0/Off
Rail heat On time during day operations
o41
1
1
0 %
100 %
100
Rail heat On time during night operations
o42
1
1
0 %
100 %
100
Rail heat period time (On time + Off time)
o43
1
1
6 min.
60 min.
10
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.
***
o46
1
1
0
2
0
Selection of Application mode. See overview on page 26.
1 = Two compressor sequential mode
2 = One compressor with variable speed control
3 = Two compressors cyclic mode
*
o61
1
1
1
3
1
Access code 2 (partial access)
***
o64
1
1
0
100
0
Replace the controllers factory settings with the present settings
o67
1
1
0/Off
1/On
0/Off
Rail heat control
0=not used, 1=pulse control with timer function (o41 and o42), 2=pulse
control with dew point function
o85
1
1
0
2
0
Dew point value where the rail heat is minimum
o86
1
1
-10 °C
50 °C
8
Dew point value where the rail heat is 100% on
o87
1
1
-9 °C
50 °C
17
Lowest permitted rail heat effect in %
o88
1
1
0 %
100 %
30
Time delay from "open door” refrigeration is started
o89
1
1
0 min.
240 min.
30
Definition of readings on lower button:
1=defrost stop temperature, 2=S6 temperature
o92
1
1
1
2
1
Display of temperature
1= u56 Air temperature
2= u36 product temperature
o97
1
1
1
2
1
Light and night blinds defined
0: Light is switch off and night blind is open when the main switch is off
1: Light and night blind is independent of main switch
o98
1
1
0
1
0
Configuration of alarm relay
The alarm relay will be activated upon an alarm signal from the following
groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input is activated for alarm
16 - Defrost alarms
32 - Miscellaneous
The groups that are to activate the alarm relay must be set by using a
numerical value which is the sum of the groups that must be activated.
(E.g. a value of 5 will activate all high temperature alarms and all sensor
errors).
0 = Cancel relay function
P41
1
1
0
63
47
Stop time for fans while the night blinds are rolling down
P65
1
1
0 min.
5 min.
0 min.
Continued
code
Wiring diagram
Min.
Max.
Fac.
Actual
User Guide | Controller for SemiPlugin appliance, AK-CC 460
24 | BC230086440483en-000201
© Danfoss | DCS (vt) | 2019.12