SW = 1.2x
Parameter
Wiring diagram
Min.
value
Max.
value
Factory
setting
Actual
setting
Function
Code
1 & 3
2
Normal operation
Temperature (setpoint)
- - -
1
1
-50 °C
50 °C
2
Thermostat
Differential
r01
1
1
0.1 K
20 K
2
Max. limitation of setpoint setting
r02
1
1
-49 °C
50 °C
50
Min. limitation of setpoint setting
r03
1
1
-50 °C
49 °C
-50
Adjustment of temperature indication
r04
1
1
-10
10
0
Temperature unit (°C/°F)
r05
1
1
0/°C
1/F
0/°C
Correction of the signal from S4
r09
1
1
-10 K
10 K
0
Correction of the signal from S3
r10
1
1
-10 K
10 K
0
Manual service, stop regulation, start regulation (-1, 0, 1)
r12
1
1
-1
1
0
Displacement of reference during night operation
r13
1
1
-50 K
50 K
0
Define thermostat function
1=ON/OFF
2=Modulating
r14
1
2
—
—
—
Definition and weighting, if applicable, of thermostat sensors - S4%
(100%=S4, 0%=S3)
r15
1
1
0 %
100 %
100
Time between melt periods
r16
1
1
0 hrs
10 hrs
1
Duration of melt periods
r17
1
1
0 min.
30 min.
5
Temperature setting for thermostat band 2
. As differential use r01
r21
1
1
-50 °C
50 °C
2
Correction of the signal from
S6
r59
1
1
-10 K
10 K
0
Definition and weighting, if applicable, of thermostat sensors
when night
cover is on. (100%=S4, 0%=S3)
r61
1
1
0 %
100 %
100
S4 min. limit. Frost protection. Cooling is stopped.
r98
1
1
-50 °C
20 °C
-50 °C
Alarms
Delay for temperature alarm
A03
1
1
0 min.
240 min.
30
Delay for door alarm
A04
1
1
0 min.
240 min.
60
Delay for temperature alarm after defrost
A12
1
1
0 min.
240 min.
90
High alarm limit for thermostat 1
A13
1
1
-50 °C
50 °C
8
Low alarm limit for thermostat 1
A14
1
1
-50 °C
50 °C
-30
High alarm limit for thermostat 2
A20
1
1
-50 °C
50 °C
8
Low alarm limit for thermostat 2
A21
1
1
-50 °C
50 °C
-30
High alarm limit for sensor S6 at thermostat 1
A22
1
1
-50 °C
50 °C
8
Low alarm limit for sensor S6 at thermostat 1
A23
1
1
-50 °C
50 °C
-30
High alarm limit for sensor S6 at thermostat 2
A24
1
1
-50 °C
50 °C
8
Low alarm limit for sensor S6 at thermostat 2
A25
1
1
-50 °C
50 °C
-30
S6 alarm time delay
With setting = 240 the S6 alarm will be omitted
A26
1
1
0 min.
240 min.
240
Alarm time delay or signal on the DI1 input
A27
1
1
0 min.
240 min.
30
Alarm time delay or signal on the DI2 input
A28
1
1
0 min.
240 min.
30
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36
1
1
0 %
100 %
100
Delay for S6 (product sensor alarm) after defrost
A52
1
1
0 min.
240 min.
90
Alarm limit for max. S7 brine temperature
A76
1
1
-50 °C
50 °C
8°C
Differential for S7 brine alarm
A77
1
1
0.1 K
10 K
3.0 K
Compressor
Min. ON-time
c01
1
1
0 min.
30 min.
0
Min. OFF-time
c02
1
1
0 min.
30 min.
0
Time delay for cutin of comp.2
c05
1
0 sec
999 sec
5
Min. speed for compressor
c46
1
25 Hz
70 Hz
30
Start speed for compressor. Must be set higher than Min. speed
c47
1
30 Hz
70 Hz
50
Max. speed for compressor
c48
1
50 Hz
100 Hz
100
Kp factor for compressor PI control
c82
1
3
30
20
Tn for compressor PI control
c83
1
30 sec
360 sec
60
Menu survey
User Guide | Controller for SemiPlugin appliance, AK-CC 460
22 | BC230086440483en-000201