background image

WARNING/ALARM 12, Torque limit:
The torque is higher than the value in par. 4-16 (in motor
operation) or the torque is higher than the value in par.
4-17 (in regenerative operation).

WARNING/ALARM 13, Over Current:
The inverter peak current limit (approx. 200% of the rated
current) is exceeded. The warning will last approx. 8-12
sec., then the frequency converter trips and issues an
alarm. Turn off the frequency converter and check if the
motor shaft can be turned and if the motor size matches
the frequency converter.

ALARM 14, Earth fault:
There is a discharge from the output phases to earth,
either in the cable between the frequency converter and
the motor or in the motor itself.
Turn off the frequency converter and remove the earth
fault.

ALARM 15, In-complete hardware:
A fitted option is not handled by the present control board
(hardware or software).

ALARM 16, Short-circuit:
There is short-circuiting in the motor or on the motor
terminals.
Turn off the frequency converter and remove the short-
circuit.

WARNING/ALARM 17, Control word timeout:
There is no communication to the frequency converter.
The warning will only be active when par. 8-04 is NOT set
to 

OFF

.

If par. 8-04 is set to 

Stop

 and 

Trip

, a warning appears and

the frequency converter ramps down until it trips, while
giving an alarm.
par. 8-03 Control word Timeout Time could possibly be
increased.

Alarm 18, Start Failed
The speed has not been able to exceed Max Start Speed
(par. 1-77) during the start within the allowed time (par.
1-79). This may be caused by a blocked rotor.

Warning/ Alarm 19, Discharge Temperature High
Warning:
The discharge temperature exceeds the level programmed
in par. 28-24. If so programmed in par. 28-25 the drive
lowers the speed of the compressor in an attempt to lower
the discharge temperature.

Alarm:
The discharge temperature exceeds the level programmed
in par. 28-26.

WARNING 25, Brake resistor short-circuited:
The brake resistor is monitored during operation. If it
short-circuits, the brake function is disconnected and the
warning appears. The frequency converter still works, but
without the brake function. Turn off the frequency
converter and replace the brake resistor (see par. 2-15
Brake Check.

ALARM/WARNING 26, Brake resistor power limit:
The power transmitted to the brake resistor is calculated as
a percentage, as a mean value over the last 120 s, on the
basis of the resistance value of the brake resistor (par.
2-11) and the intermediate circuit voltage. The warning is
active when the dissipated braking power is higher than
90%. If 

Trip

 [2] has been selected in par. 2-13, the

frequency converter cuts out and issues this alarm, when
the dissipated braking power is higher than 100%.

WARNING 27, Brake chopper fault:
The brake transistor is monitored during operation and if it
short-circuits, the brake function disconnects and the
warning comes up. The frequency converter is still able to
run, but since the brake transistor has short-circuited,
substantial power is transmitted to the brake resistor, even
if it is inactive. Turn off the frequency converter and
remove the brake resistor.

CAUTION

Warning: There is a risk of substantial power being
transmitted to the brake resistor if the brake transistor is
short-circuited.

ALARM/WARNING 28, Brake check failed:
Brake resistor fault: the brake resistor is not connected/
working.

ALARM 29, Frequency converter over temperature:
If the enclosure is IP 20 or IP 21/TYPE 1, the cut-out

temperature of the heat-sink is 95 

o

C +5 

o

C, dependent on

size of frequency converter. The temperature fault cannot
be reset, until the temperature of the heatsink is below 70

o

C +5 

o

C.

The fault could be:

-

Ambient temperature too high

-

Too long motor cable

ALARM 30, Motor phase U missing:
Motor phase U between the frequency converter and the
the motor is missing.
Turn off the frequency converter and check motor phase
U.

ALARM 31, Motor phase V missing:
Motor phase V between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase V.

ALARM 32, Motor phase W missing:
Motor phase W between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase
W.

ALARM 33, Inrush fault:
Too many power-ups have occurred within a short time
period. See the chapter 

Specifications

 for the allowed

number of powerups within one minute.

Troubleshooting

ADAP-KOOL

®

 Drive Operating Instructions

MG.11.L4.02 - ADAP-KOOL

®

 Drive

113

8

8

Содержание ADAP-KOOL AKD 102

Страница 1: ...5 Electrical Installation 25 5 1 How to Connect 25 5 1 2 Electrical Installation and Control Cables 26 5 1 5 Mains Wiring Overview 30 5 1 11 Motor Wiring Overview 36 5 1 19 How to Test Motor and Dire...

Страница 2: ...Loop 100 7 2 16 21 Ext Closed Loop 101 7 2 17 22 Application Functions 103 7 2 18 23 Time Based Funtions 105 7 2 19 25 Pack Controller 106 7 2 20 26 Analog I O Option MCB 109 107 7 2 21 28 Compressor...

Страница 3: ...o the customer The drive can be supplied in either of two protection classes IP21 IP20 up to 7 5kW or IP55 IP66 on request this insures that our customers benefit from having the most robust of design...

Страница 4: ...information contained in this manual even if advised of the possibility of such damages In particular Danfoss is not responsible for any costs including but not limited to those incurred as a result o...

Страница 5: ...LV Protective Extra Low Voltage Watt Power W Btu hr hp Pascal Pressure Pa N m2 psi psf ft of water IINV Rated Inverter Output Current RPM Revolutions Per Minute SR Size Related T Temperature C F t Tim...

Страница 6: ...ated PCB Mains option 21 X No Mains disconnect switch 1 With Mains disconnect switch IP55 only Adaptation 22 Reserved Adaptation 23 Reserved Software release 24 27 Actual software Software language 28...

Страница 7: ...out Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs 2 The STOP RESET key on the LCP of the frequency converter does not...

Страница 8: ...occur in the electronics of the frequency converter or if a temporary overload or a fault in the supply mains or the motor connection ceases WARNING Touching the electrical parts may be fatal even aft...

Страница 9: ...e loadsharing and relay Grid configuration IT TN grounded leg etc Safety of low voltage ports PELV conditions Consult the relevant clauses in these instructions and in the AKD102 Design Guide for info...

Страница 10: ...130BA491 Illustration 2 1 This certificate also covers AKD102 Safety ADAP KOOL Drive Operating Instructions 10 MG 11 L4 02 ADAP KOOL Drive 2 2...

Страница 11: ...0 V IT mains and delta earth grounded leg mains voltage may exceed 760 V between phase and earth 14 50 RFI Filter can be used to disconnect the internal RFI capacitors from the RFI filter to ground 2...

Страница 12: ...though the menu structure Quick Menu or Main Menu in the drive The Application guide covers all standard settings for Compressors Single fan and pump Condenser fans After completing setup choose to r...

Страница 13: ...ructure Quick Menu Main Menu etc in the drive The Application guide covers all standard settings for Compressors Single fan and pump Condenser fans Compressor pack setup As an example please see scree...

Страница 14: ...the drive and controls from the sensor signal External Open loop The AKD 102 takes its control signal from another controller such as a pack controller which gives the drive e g 0 10v 4 20 mA or ADAP...

Страница 15: ...t fixed or floating setpoint Set setpoint Set high low limit for setpoint Set cut out in value Choose pack control setup Set number of compressors in pack Application Guide ADAP KOOL Drive Operating I...

Страница 16: ...cancelled at any time by pressing Back The Application Guide can be re entered through the Quick Menu When re entering the Application Guide the user will be asked to keep previous changes to the fact...

Страница 17: ...is thus completed in 10 15 easy steps using just two buttons of the drives local control panel Illustration 3 1 Standard drawing of Compressor with internal control Single or multiple fans or pumps Th...

Страница 18: ...or pump multiple fans or pumps in parallel Compressor pack Illustration 3 4 P0 pressure transmitter 54 Illustration 3 5 How to connect the AKD102 and AKS33 for closed loop applications Application Gu...

Страница 19: ...7 45 380 480 V 1 1 4 0 5 5 7 5 1 1 7 5 11 18 5 11 18 5 22 30 22 37 37 55 45 55 75 90 75 90 Table 4 1 Unpacking table Please note that a selection of screwdrivers phillips or cross thread screwdriver a...

Страница 20: ...A4 A5 B1 B2 C1 C2 IP20 21 IP20 21 IP55 66 IP55 66 IP21 55 66 IP21 55 66 IP21 55 66 IP21 55 66 All measurements in mm A5 in IP55 66 only Mechanical Installation ADAP KOOL Drive Operating Instructions 2...

Страница 21: ...70 With one C option B 130 130 170 170 242 242 242 308 370 Back plate B 90 90 130 130 200 242 242 242 308 370 Distance between mount holes b 70 70 110 110 171 215 210 210 272 334 Depth mm Without opti...

Страница 22: ...Frame sizes B1 and B2 Frame sizes C1 and C2 1 2 only available in units with brake chopper For DC link connection Load sharing the connector 1 can be ordered separately An eight pole connector is inc...

Страница 23: ...w Air passage for different enclosures Enclosure A2 A3 A4 A5 B1 B2 C1 C2 a mm 100 100 100 100 200 200 200 225 b mm 100 100 100 100 200 200 200 225 1 Drill holes in accordance with the measurements giv...

Страница 24: ...mbient Temperature The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account 4 2 3 Field Mounting For field mounting the IP 21 IP 4X top TYPE...

Страница 25: ...orque Nm Enclo sure 200 240 V 380 480 V Line Motor DC connection Brake Earth Relay A2 1 1 3 0 1 1 4 0 1 8 1 8 1 8 1 8 3 0 6 A3 3 7 5 5 7 5 1 8 1 8 1 8 1 8 3 0 6 A4 1 1 2 2 1 4 4 1 8 1 8 1 8 1 8 3 0 6...

Страница 26: ...d Control Cables Illustration 5 1 Diagram showing all electrical terminals Terminal 37 present for units with Safe Stop Function only Electrical Installation ADAP KOOL Drive Operating Instructions 26...

Страница 27: ...put 6 50 Speed 0 HighLim 53 Terminal 53 Analog Input 3 15 6 1 20 0 Reference 54 Terminal 54 Analog Input 3 15 6 2 20 0 Feedback Table 5 2 Terminal connections Very long control cables and analog signa...

Страница 28: ...lied with Danfoss recommends using the fuses mentioned in table 4 2 which will ensure compliance with EN50178 In case of malfunction not following the recommendation may result in unnecessary damage t...

Страница 29: ...KTS R6 JKS 6 JJS 6 5017906 006 KLS R6 ATM R6 A6K 6R 1K5 2K2 KTS R10 JKS 10 JJS 10 5017906 010 KLS R10 ATM R10 A6K 10R 3K0 KTS R15 JKS 15 JJS 15 5017906 016 KLS R16 ATM R16 A6K 16R 4K0 KTS R20 JKS 20 J...

Страница 30: ...ARNING IT Mains Do not connect 400 V frequency converters with RFI filters to mains supplies with a voltage between phase and earth of more than 440 V For IT mains and delta earth grounded leg mains v...

Страница 31: ...rst mount the two screws on the mounting plate slide it into place and tighten fully Illustration 5 4 When mounting cables first mount and tighten earth cable Electrical Installation ADAP KOOL Drive O...

Страница 32: ...rately according to EN 50178 IEC 61800 5 1 Illustration 5 5 Then mount mains plug and tighten wires Illustration 5 6 Finally tighten support bracket on mains wires NOTE With single phase A3 use L1 and...

Страница 33: ...ut mains disconnect switch Note that a cable clamp is used Illustration 5 8 How to connect to mains and earthing with mains disconnect switch NOTE With single phase A5 use L1 and L2 terminals Electric...

Страница 34: ...B2 NOTE For correct cable dimensions please see the section General Specifications at the back of this manual 5 1 9 Mains connection for C1 and C2 Illustration 5 10 How to connect to mains and earthi...

Страница 35: ...spondingly Switching frequency When frequency converters are used together with sine wave filters to reduce the acoustic noise from a motor the switching frequency must be set according to the sine wa...

Страница 36: ...Wiring Overview Enclosure A2 IP 20 IP 21 A3 IP 20 IP 21 A4 IP 55 IP 66 A5 IP 55 IP 66 B1 IP 21 IP 55 IP 66 B2 IP 21 IP 55 IP 66 C1 IP 21 IP 55 66 C2 IP 21 IP 55 66 Motor size 200 240 V 1 1 3 0 kW 3 7...

Страница 37: ...st terminate the motor earth then place motor U V and W wires in plug and tighten Illustration 5 13 Mount cable clamp to ensure 360 degree connection between chassis and screen note the outer insulati...

Страница 38: ...of the motor cable is removed under the EMC clamp 5 1 14 Motor Connection for B1 and B2 Illustration 5 15 First terminate the motor earth then Place motor U V and W wires in terminal and tighten Plea...

Страница 39: ...cable is removed under the EMC clamp 5 1 16 Wiring Example and Testing The following section describes how to terminate control wires and how to access them For an explanation of the function programm...

Страница 40: ...Illustration 5 17 Access to control terminals for A2 A3 B3 B4 C3 and C4 enclosures Remove front cover to access control terminals When replacing the front cover please ensure proper fastening by apply...

Страница 41: ...one end in terminal 27 using a suitable terminal screwdriver Note For units with Safe Stop function the existing jumper between terminal 12 and 37 should not be removed for the unit to be able to run...

Страница 42: ...Step 7 To move the cursor use the left and right arrow buttons This enables changing the speed in larger increments Illustration 5 27 Step 8 Press the Off button to stop the motor again Illustration 5...

Страница 43: ...nnected This information is located on the motor name plate data Illustration 5 30 Motor name plate example Step 2 Enter motor name plate data in following parameter list To access list first press QU...

Страница 44: ...Log shows the last measuring sequence carried out by the AMA before the frequency converter entered alarm mode This number along with the description of the alarm will assist troubleshooting If conta...

Страница 45: ...display with Status lines 2 Menu keys and indicator lights LED s selecting mode changing parameters and switching between display functions 3 Navigation keys and indicator lights LEDs 4 Operation keys...

Страница 46: ...QUICK MENU Q3 Function Setups Q3 1 General Settings Q3 13 Display Settings Each value measurement readout parameter selected in par 0 20 to par 0 24 has its own scale and number of digits after a poss...

Страница 47: ...he Status key 5 line readouts 4 line readouts or Smart Logic Control Use Status for selecting the mode of display or for changing back to Display mode from either the Quick Menu mode the Main Menu mod...

Страница 48: ...formation is displayed about the condition of the frequency converter before it enters the alarm mode The Alarm log button on the LCP allows access to both Alarm log and Maintenance log Back reverts t...

Страница 49: ...top function is selected and the Off key is inactive the motor can only be stopped by disconnecting the mains supply Auto On enables the frequency converter to be controlled via the control terminals...

Страница 50: ...p Software The PC is connected via a standard host device USB cable or via the RS 485 interface as shown in the ADAP KOOL Drive AKD102 Design Guide chapter How to Install Installation of misc connecti...

Страница 51: ...Load Frequency Converter Settings 1 Connect a PC to the frequency converter via USB com port 2 Open MCT 10 Set up software 3 Choose Open stored files will be shown 4 Open the appropriate file 5 Choose...

Страница 52: ...motor before performing any of these operations Data storage in LCP 1 Go to 0 50 LCP Copy 2 Press the OK key 3 Select All to LCP 4 Press the OK key All parameter settings are now stored in the GLCP i...

Страница 53: ...l stay present with default factory setting Manual initialisation NOTE When carrying out manual initialisation serial communication RFI filter settings and fault log settings are reset Removes paramet...

Страница 54: ...g output representing motor current or kW to an analog input of a DDC controller and to configure the analog outputs to be controlled by the BMS via a high level interface HLI e g to control a chilled...

Страница 55: ...ctions which can be based on running or operating hour time intervals or on specific dates and times energy log especially useful in retrofit applications or where information of the actual historical...

Страница 56: ...2 Trip The frequency converter will now trip if a broken fan belt is detected Select My Personal Menu to display only the parameters which have been pre selected and programmed as personal parameters...

Страница 57: ...Operating Instructions Illustration 7 1 Quick Menu view The Quick Setup menu gives access to the 13 most important setup parameters of the drive After programming the drive will in most cases be read...

Страница 58: ...otor power factor parameter manually 3 Single fan pump AEO Auto Energy Optimization VT For optimum energy efficient speed control of centrifugal pumps and fans Provides a voltage which is optimized fo...

Страница 59: ...on 1 23 Motor Frequency Motor Frequency and 1 25 Motor Nominal Speed Motor Nominal Speed This parameter cannot be adjusted while the motor is running 4 12 Motor Speed Low Limit Hz Range Function Appl...

Страница 60: ...al 2 the frequency converter will start with this setting again following a power down 5 10 Terminal 18 Digital Input Option Function 0 No operation No reaction to signals transmitted to terminal 1 Re...

Страница 61: ...l 18 Digital Input Option Function 19 Freeze ref Freezes actual reference The frozen reference is now the point of enable condition for Speed up and Speed down to be used If Speed up down is used the...

Страница 62: ...up Terminal 29 and 33 only Input for increment counting in the SLC counter 65 Reset Counter B Input for reset of counter B 66 Sleep Mode Forces frequency converter into Sleep Mode see par 22 4 5 10 Te...

Страница 63: ...e of the settings in par 1 2 Motor Data is changed 1 30 Stator Resistance Rs to 1 39 Motor Poles the advanced motor parameters will return to default setting This parameter cannot be adjusted while th...

Страница 64: ...Illustration 7 3 Step 2 Press the Quick Menus button Quick Menus choices appear Illustration 7 4 Step 3 Use the up down navigation keys to scroll down to Function Setups Press OK Illustration 7 5 Ste...

Страница 65: ...4 Low Current only visible if switch set to I 6 23 Terminal 54 High Current only visible if switch set to I 6 24 Terminal 54 Low ref Feedb value 6 25 Terminal 54 High ref Feedb value 3 02 Min Referenc...

Страница 66: ...n a Hex code 1609 Custom Readout View the user defined readouts as defined in par 0 30 0 31 and 0 32 0 20 Display Line 1 1 Small Option Function 1610 Power kW Actual power consumed by the motor in kW...

Страница 67: ...30 8 mA Actual value at output X30 8 General Purpose I O Card Optional Use Par 6 60 to select the variable to be shown 0 20 Display Line 1 1 Small Option Function 1680 Fieldbus CTW 1 Control word CTW...

Страница 68: ...serial communication If to be displayed permanently select Display Text 1 in 0 20 Display Line 1 1 Small 0 21 Display Line 1 2 Small 0 22 Display Line 1 3 Small 0 23 Display Line 2 Large or 0 24 Disp...

Страница 69: ...ed Loop or via the Function Setups accessed by pressing the Quick Menus button This parameter can not be changed when motor is running NOTE When set for Closed Loop the commands Reversing and Start Re...

Страница 70: ...ected 0 None 1 Analog input 53 2 Analog input 54 3 Digital input 18 4 Digital input 19 5 Digital input 32 6 Digital input 33 NOTE This parameter cannot be adjusted while the motor is running NOTE Digi...

Страница 71: ...ge Range Function feedback value set in 6 15 Terminal 53 High Ref Feedb Value 6 14 Terminal 53 Low Ref Feedb Value Range Function 0 000 N A 999999 999 999999 999 N A Enter the analog input scaling val...

Страница 72: ...3 Ext Closed Loop 1 0 100 0 20 mA 114 Ext Closed Loop 2 0 100 0 20 mA 115 Ext Closed Loop 3 0 100 0 20 mA 130 Output freq 4 20mA 0 100 Hz 131 Reference 4 20mA Minimum Reference Maximum Reference 6 50...

Страница 73: ...6 51 Terminal 42 Output Min Scale to 50 Output signal 20 mA is needed at 100 75 of range set 6 52 Terminal 42 Output Max Scale to 75 EXAMPLE 3 Variable value REFERENCE range Min ref Max ref Range need...

Страница 74: ...k 1 Option Function 1 Square root Square root 1 is commonly used when a pressure sensor is used to provide flow feedback flow pressure 2 Pressure to temperature Pressure to temperature 2 is used in co...

Страница 75: ...ressure to temperature conversion to be accurate If the refrigerant used is not listed in choices 0 through 6 select User defined 7 Then use par 20 31 20 32 and 20 33 to provide A1 A2 and A3 for the e...

Страница 76: ...he Sleep Mode should be cancelled 22 43 Wake up Speed Hz Range Function 0 Hz par 4 12 par 4 14 Hz To be used if 0 02 Motor Speed Unit has been set for Hz parameter not visible if RPM selected Only to...

Страница 77: ...kept within a zone rather than at a constant level 25 20 25 20 Neutral Zone unit Range Function The NZ is programmed in the same unit as selected in par 20 12 Reference Feedback Unit It places a zone...

Страница 78: ...tion cards added to the unit enable additional parameters associated with the option device 7 1 5 Parameter Selection In the Main Menu mode the parameters are divided into groups Select a parameter gr...

Страница 79: ...ved and press OK Illustration 7 14 Display example 7 1 9 Changing of data value Step by Step Certain parameters can be changed step by step or infinitely variably This applies to 1 20 Motor Power kW 1...

Страница 80: ...Lists at the back of this manual 0 xx Operation Display 1 xx Load Motor 2 xx Brakes 3 xx Reference Ramps 4 xx Limits Warnings 5 xx Digital In Out 6 xx Analog In Out 8 xx Comm and Options 11 xx ADAP KO...

Страница 81: ...ups TRUE Uint16 0 23 Display Line 2 Large ExpressionLimit All set ups TRUE Uint16 0 24 Display Line 3 Large ExpressionLimit All set ups TRUE Uint16 0 25 My Personal Menu ExpressionLimit 1 set up TRUE...

Страница 82: ...71 Date Format null 1 set up TRUE Uint8 0 72 Time Format null 1 set up TRUE Uint8 0 74 DST Summertime 0 Off 1 set up TRUE Uint8 0 76 DST Summertime Start ExpressionLimit 1 set up TRUE 0 TimeOfDay 0 7...

Страница 83: ...Compensation 100 All set ups TRUE 0 Int16 1 61 High Speed Load Compensation 100 All set ups TRUE 0 Int16 1 62 Slip Compensation 0 All set ups TRUE 0 Int16 1 63 Slip Compensation Time Constant 0 10 s A...

Страница 84: ...In Speed Hz ExpressionLimit All set ups TRUE 1 Uint16 2 1 Brake Energy Funct 2 10 Brake Function 0 Off All set ups TRUE Uint8 2 11 Brake Resistor ohm ExpressionLimit All set ups TRUE 0 Uint16 2 12 Bra...

Страница 85: ...19 Jog Speed RPM ExpressionLimit All set ups TRUE 67 Uint16 3 4 Ramp 1 3 41 Ramp 1 Ramp Up Time ExpressionLimit All set ups TRUE 2 Uint32 3 42 Ramp 1 Ramp Down Time ExpressionLimit All set ups TRUE 2...

Страница 86: ...Uint32 4 51 Warning Current High ImaxVLT P1637 All set ups TRUE 2 Uint32 4 52 Warning Speed Low 0 RPM All set ups TRUE 67 Uint16 4 53 Warning Speed High outputSpeedHighLimit P413 All set ups TRUE 67 U...

Страница 87: ...utput 0 No operation All set ups TRUE Uint8 5 31 Terminal 29 Digital Output 0 No operation All set ups TRUE Uint8 5 32 Term X30 6 Digi Out MCB 101 0 No operation All set ups TRUE Uint8 5 33 Term X30 7...

Страница 88: ...operation All set ups TRUE Uint8 5 68 Pulse Output Max Freq X30 6 5000 Hz All set ups TRUE 0 Uint32 5 9 Bus Controlled 5 90 Digital Relay Bus Control 0 N A All set ups TRUE 0 Uint32 5 93 Pulse Out 27...

Страница 89: ...54 High Current 20 00 mA All set ups TRUE 5 Int16 6 24 Terminal 54 Low Ref Feedb Value 1 000 N A All set ups TRUE 3 Int32 6 25 Terminal 54 High Ref Feedb Value ExpressionLimit All set ups TRUE 3 Int32...

Страница 90: ...ntrol 0 00 All set ups TRUE 2 N2 6 54 Terminal 42 Output Timeout Preset 0 00 1 set up TRUE 2 Uint16 6 6 Analog Output X30 8 6 60 Terminal X30 8 Output 0 No operation All set ups TRUE Uint8 6 61 Termin...

Страница 91: ...action Command 0 Off All set ups FALSE Uint8 8 46 BTM Transaction Status 0 Off All set ups TRUE Uint8 8 47 BTM Timeout 60 s 1 set up FALSE 0 Uint16 8 5 Digital Bus 8 50 Coasting Select 3 Logic OR All...

Страница 92: ...Values 0 Off All set ups TRUE Uint8 11 9 AK LonWorks 11 90 AK Network Address 0 N A 1 set up TRUE 0 Uint16 11 91 AK Service Pin 0 Off 1 set up TRUE Uint8 11 98 Alarm Text 0 N A All set ups FALSE 0 Vi...

Страница 93: ...ps TRUE Uint8 13 12 Comparator Value ExpressionLimit 2 set ups TRUE 3 Int32 13 2 Timers 13 20 SL Controller Timer ExpressionLimit 1 set up TRUE 3 TimD 13 4 Logic Rules 13 40 Logic Rule Boolean 1 null...

Страница 94: ...ion Settings 0 No action All set ups TRUE Uint8 14 29 Service Code 0 N A All set ups TRUE 0 Int32 14 3 Current Limit Ctrl 14 30 Current Lim Ctrl Proportional Gain 100 All set ups FALSE 0 Uint16 14 31...

Страница 95: ...Time ExpressionLimit All set ups FALSE 0 TimeOfDay 15 3 Alarm Log 15 30 Alarm Log Error Code 0 N A All set ups FALSE 0 Uint8 15 31 Alarm Log Value 0 N A All set ups FALSE 0 Int16 15 32 Alarm Log Time...

Страница 96: ...15 72 Option in Slot B 0 N A All set ups FALSE 0 VisStr 30 15 73 Slot B Option SW Version 0 N A All set ups FALSE 0 VisStr 20 15 74 Option in Slot C0 0 N A All set ups FALSE 0 VisStr 30 15 75 Slot C0...

Страница 97: ...16 22 Torque 0 All set ups FALSE 0 Int16 16 3 Drive Status 16 30 DC Link Voltage 0 V All set ups FALSE 0 Uint16 16 32 Brake Energy s 0 000 kW All set ups FALSE 0 Uint32 16 33 Brake Energy 2 min 0 000...

Страница 98: ...r A 0 N A All set ups TRUE 0 Int32 16 73 Counter B 0 N A All set ups TRUE 0 Int32 16 75 Analog In X30 11 0 000 N A All set ups FALSE 3 Int32 16 76 Analog In X30 12 0 000 N A All set ups FALSE 3 Int32...

Страница 99: ...A All set ups FALSE 0 Uint8 18 11 Fire Mode Log Time 0 s All set ups FALSE 0 Uint32 18 12 Fire Mode Log Date and Time ExpressionLimit All set ups FALSE 0 TimeOfDay 18 3 Inputs Outputs 18 30 Analog In...

Страница 100: ...d Refrigerant A2 2250 00 N A All set ups TRUE 2 Int32 20 33 User Defined Refrigerant A3 250 000 N A All set ups TRUE 3 Uint32 20 4 Thermostat Pressostat 20 40 Thermostat Pressostat Function null All s...

Страница 101: ...rse Control 0 Normal All set ups TRUE Uint8 21 21 Ext 1 Proportional Gain 0 01 N A All set ups TRUE 2 Uint16 21 22 Ext 1 Integral Time 10000 00 s All set ups TRUE 2 Uint32 21 23 Ext 1 Differentation T...

Страница 102: ...nt 0 000 ExtPID3Unit All set ups TRUE 3 Int32 21 57 Ext 3 Reference Unit 0 000 ExtPID3Unit All set ups TRUE 3 Int32 21 58 Ext 3 Feedback Unit 0 000 ExtPID3Unit All set ups TRUE 3 Int32 21 59 Ext 3 Out...

Страница 103: ...s TRUE 67 Uint16 22 37 High Speed Hz ExpressionLimit All set ups TRUE 1 Uint16 22 38 High Speed Power kW ExpressionLimit All set ups TRUE 1 Uint32 22 39 High Speed Power HP ExpressionLimit All set ups...

Страница 104: ...6 22 84 Speed at No Flow Hz ExpressionLimit All set ups TRUE 1 Uint16 22 85 Speed at Design Point RPM ExpressionLimit All set ups TRUE 67 Uint16 22 86 Speed at Design Point Hz ExpressionLimit All set...

Страница 105: ...4 Hours 2 set ups TRUE Uint8 23 51 Period Start ExpressionLimit 2 set ups TRUE 0 TimeOfDay 23 53 Energy Log 0 N A All set ups TRUE 0 Uint32 23 54 Reset Energy Log 0 Do not reset All set ups TRUE Uint8...

Страница 106: ...isabled All set ups TRUE Uint8 25 34 Destage Function Time 15 s All set ups TRUE 0 Uint16 25 4 Staging Settings 25 40 Ramp Down Delay 10 0 s All set ups TRUE 1 Uint16 25 41 Ramp Up Delay 2 0 s All set...

Страница 107: ...s TRUE 2 Int16 26 31 Terminal X42 5 High Voltage 10 00 V All set ups TRUE 2 Int16 26 34 Term X42 5 Low Ref Feedb Value 0 000 N A All set ups TRUE 3 Int32 26 35 Term X42 5 High Ref Feedb Value 100 000...

Страница 108: ...tback 0 000 ReferenceFeedbackUnit All set ups TRUE 3 Int32 28 74 Night Speed Drop RPM ExpressionLimit All set ups TRUE 67 Uint16 28 75 Night Speed Drop Override 0 000 N A All set ups TRUE 3 Int32 28 7...

Страница 109: ...ssed to restart the motor If an alarm cannot be reset the reason may be that its cause has not been rectified or the alarm is trip locked see also table on following page Alarms that are trip locked o...

Страница 110: ...ard over temp X X X 30 Motor phase U missing X X X 4 58 31 Motor phase V missing X X X 4 58 32 Motor phase W missing X X X 4 58 33 Inrush fault X X 34 Fieldbus communication fault X X 36 Mains failure...

Страница 111: ...0 1024 DC under Volt DC under Volt Output Freq Low 11 00000800 2048 DC over Volt DC over Volt Brake Check OK 12 00001000 4096 Short Circuit DC Voltage Low Braking Max 13 00002000 8192 Inrush Fault DC...

Страница 112: ...205 410 Voltage warning high w o brake w brake 390 405 810 840 Overvoltage 410 855 The voltages stated are the intermediate circuit voltage of the frequency converter with a tolerance of 5 The corresp...

Страница 113: ...equency converter and replace the brake resistor see par 2 15 Brake Check ALARM WARNING 26 Brake resistor power limit The power transmitted to the brake resistor is calculated as a percentage as a mea...

Страница 114: ...o resume normal operation apply 24 V DC to the terminal programmed for external interlock and reset the frequency converter via serial communication digital I O or by pressing reset button on keypad W...

Страница 115: ...ALARM 251 New Type Code The frequency converter has got a new type code Troubleshooting ADAP KOOL Drive Operating Instructions MG 11 L4 02 ADAP KOOL Drive 115 8 8...

Страница 116: ...8 3 11 7 13 8 18 4 Continuous kVA 208 V AC kVA 2 38 2 70 3 82 4 50 6 00 Max cable size mains motor brake mm2 AWG 2 4 10 Max input current Continuous 3 x 200 240 V A 5 9 6 8 9 5 11 3 15 0 Intermittent...

Страница 117: ...11 1 16 6 21 4 26 9 31 7 41 4 51 5 61 2 Max cable size mains motor brake mm 2 AWG 2 10 7 35 2 50 1 0 B4 35 2 95 4 0 120 250 MCM With mains disconnect switch included 16 6 35 2 35 2 70 3 0 185 kcmil35...

Страница 118: ...kVA 400 V AC kVA 2 1 2 8 3 9 5 0 6 9 9 0 11 0 Continuous kVA 460 V AC kVA 2 4 2 7 3 8 5 0 6 5 8 8 11 6 Max cable size mains motor brake mm2 AWG 2 4 10 Max input current Continuous 3 x 380 440 V A 2 7...

Страница 119: ...480 V A 20 9 27 5 34 1 39 6 51 7 64 9 80 3 105 130 160 Max pre fuses 1 A 63 63 63 63 80 100 125 160 250 250 Environment Estimated power loss at rated max load W 4 278 392 465 525 698 739 843 1083 1384...

Страница 120: ...for 1 min Percentage relates to ADAP KOOL Drive s nominal torque Cable lengths and cross sections Max motor cable length screened armoured 150 m Max motor cable length unscreened unarmoured 300 m Max...

Страница 121: ...29 33 5 kHz open collector Min frequency at terminal 29 33 4 Hz Voltage level see section on Digital input Maximum voltage on input 28 V DC Input resistance Ri approx 4 k Pulse input accuracy 0 1 1 kH...

Страница 122: ...esistive load 2 3 400 V AC 2 A Max terminal load AC 15 1 on 4 5 NO Inductive load cos 0 4 240 V AC 0 2 A Max terminal load DC 1 1 on 4 5 NO Resistive load 80 V DC 2 A Max terminal load DC 13 1 on 4 5...

Страница 123: ...ance Scan interval 5 ms Control card USB serial communication USB standard 1 1 Full speed USB plug USB type B device plug WARNING Connection to PC is carried out via a standard host device USB cable T...

Страница 124: ...rn which can be set to 60 AVM or SFAVM in parameter 14 00 A enclosures 60 AVM Pulse Width Modulation Illustration 9 1 Derating of Iout for different TAMB MAX for enclosure A using 60 AVM SFAVM Stator...

Страница 125: ...e mode 110 over torque SFAVM Stator Frequency Asyncron Vector Modulation Illustration 9 8 Derating of Iout for different TAMB MAX for enclosure C using SFAVM in Normal torque mode 110 over torque 9 2...

Страница 126: ...of the speed and the power is proportional to the cube of the speed there is no need for additional cooling or de rating of the motor In the graphs shown below the typical VT curve is below the maximu...

Страница 127: ...speeds As a response to a critical level the frequency converter can adjust the switching frequency and or change the switching pattern in order to ensure the performance of the frequency converter T...

Страница 128: ...evision Rights 4 D DC Link 112 Default Settings 52 Derating For Ambient Temperature 124 For Low Air Pressure 125 For Running At Low Speed 126 For The Installation Of Long Motor Cables Or Cables With L...

Страница 129: ...ack Controller 25 00 77 Panel Through Mounting 24 Parameter Selection 78 Set Up 54 PC Software Tools 50 Protection And Features 123 Pulse Inputs 121 Width Modulation 124 Q Quick Menu 47 55 Menu Mode 4...

Страница 130: ...ng T C 5 U UL Fuses 200 240 V 29 USB Connection 41 V Variable Quadratic Torque Applications VT 126 Voltage Level 120 W Warning Against Unintended Start 8 Wiring Example And Testing 39 Zone unit 25 22...

Отзывы: