AK-PC 783
Capacity
controller RS8GN202 © Danfoss 11-2013
39
Determine the connection points
All connections must be programmed with module and point, so
in principle it does not matter where the connections are made, as
long as it takes place on a correct type of input or output.
• The controller is the first module, the next one is 2, etc.
• A point is the two or three terminals belonging to an input or
output (e.g. two terminals for a sensor and three terminals for a
relay).
The preparation of the connection diagram and the subsequent
programming (configuration) should take place at the present
time. It is most easily accomplished by filling in the connection
survey for the relevant modules.
Principle:
Name
On module
On Point
Function
fx Compressor 1
x
x
Close
fx Compressor 2
x
x
Close
fx Alarm relay
x
x
NC
fx Main switch
x
x
Close
fx P0
x
x
AKS 32R 1-6 bar
The connection survey from the controller and any extension
modules are uploaded from the paragraph "Module survey. E.g.
controller module:
Module Point
10
Mind the numbering.
The right-hand part of the
controller module may look like
a separate module. But it
isn’t.
- Columns 1, 2, 3 and 5 are used for the programming.
- Columns 2 and 4 are used for the connection diagram.
Signal
Module
Point
Terminal
Signal type /
Active at
Discharge temperature - Sd - MT
1
1
(AI 1)
1 - 2
Pt 1000
Suction gas temperature- Ss - MT
2
(AI 2)
3 - 4
Pt 1000
Outdoor temperature - Sc3
3
(AI 3)
5 - 6
Pt 1000
Discharge temperature - Sd - LT
4
(AI 4)
7 - 8
Pt 1000
Suction gas temperature- Ss - MT
5
(AI 5)
9 - 10
Pt 1000
Suction pressure - P0-MT
6
(AI 6)
11 - 12
AKS 32R-12
Condensing pressure - Pc-MT
7
(AI 7)
13 - 14
AKS 32R-34
Level switch, oil, comp.1 LT
8
(AI 8)
19 - 20
Closed
Level switch, oil, comp.2 LT
9
(AI 9)
21 - 22
Closed
10
(AI 10)
23 - 24
11
(AI 11)
25 - 26
Solenoid valve, oil , comp. 1 LT
12
(DO 1)
31 - 32
ON
Solenoid valve, oil , comp. 2 LT
13
(DO 2)
33 - 34
ON
14
(DO 3)
35 - 36
15
(DO 4)
37 - 38
Solenoid valve, oil, Separator
16
(DO 5)
39 - 40 - 41
ON
Solenoid valve, oil, ccascade
17
(DO6)
42 - 43 - 44
ON
EC-motor on/off signal
18
(DO7)
45 - 46 - 47
ON
19
(DO8)
48 - 49 - 50
24
-
25
-
Example continued
Note
The safety relays should not be fitted onto a module
with override changeovers, as they can be put out of
operation by an incorrect setting.
Continued next page
Signal
Module
Point
Terminal
Signal type /
Active at
Compressor 1 MT
2
1
(DO 1)
25 - 26 - 27
ON
Compressor 2 MT
2
(DO 2)
28 - 29 - 30
ON
Compressor 3 MT
3
(DO 3)
31 - 32 - 33
ON
Compressor 4 MT
4
(DO 4)
34 - 35 - 36
ON
Compressor 1 LT
5
(DO 5)
37 - 38 - 39
ON
Compressor 2 LT
6
(DO6)
40 - 41 - 42
ON
7
(DO7)
43 - 44 - 45
8
(DO8)
46 - 47 - 48
Signal
Module
Point/Step
Terminal
Signal type
Level switch, oil, receiver High
3
1
(AI 1)
1 - 2
Closed
Level switch, oil, receiver Low
2
(AI 2)
3 - 4
Closed
Level switch, oil, Separator, High
3
(AI 3)
5 - 6
Closed
4
(AI 4)
7 - 8
5
(AI 5)
9 - 10
Pulse reset of stopped compressor
6
(AI 6)
11 - 12
Pulse
Suctioon pressure - P0-LT
7
(AI 7)
13 - 14
AKS 2050-59
Condenser pressure - Pc-LT
8
(AI 8)
15 - 16
AKS 2050-59
Stepper signal til ETS valve
1
(AO 1)
25 - 26 - 27 - 28
ETS
2
(AO 2)
29 - 30 - 31 - 32
3
(AO 3)
33 - 34 - 35 - 36
4
(AO 4)
37 - 38 - 39 - 40
Содержание ADAP-KOOL AK-PC 783
Страница 31: ...AK PC 783 Capacity controller RS8GN202 Danfoss 11 2013 31...
Страница 41: ...AK PC 783 Capacity controller RS8GN202 Danfoss 11 2013 41 Example continued...
Страница 44: ...44 Capacity controller RS8GN202 Danfoss 11 2013 AK PC 783...
Страница 125: ...AK PC 783 Capacity controller RS8GN202 Danfoss 11 2013 125...