
126
Capacity
controller RS8GN202 © Danfoss 11-2013
AK-PC 783
Appendix B - Alarm texts
Settings
Priority
(factory)
English alarm texts
Description
Suction group
Low suction pressure P0
Low
Low pressure P0
Minimum safety limit for suction pressure P0 has been exceeded
High suction pressure P0
High
High pressure P0
High alarm limit for P0 has been exceeded
High/Low superheat Ss
Medium
High superheat suction _
Superheat in suction line too high
Low superheat section _
Superheat in suction line too low
Load shedding
Medium
Load Shed active
Load shedding has been activated
P0/S4 sensor error
High
P0_ sensor error
Pressure transmitter signal from P0 is defective
S4_ sensor error
Temperature signal from S4 media temp. sensor defective
Scasc_ sensor error
Temperature signal from cascade sensor is defective
Prec sensor error
Pressure transmitter signal from the receiver is defective
Misc. sensor error
Medium
Ss_ sensor error
Temperature signal from Ss suction gas temp. is defective
Sd_ sensor error
Temperature signal from Sd discharge gas temp. is defective
Sc3 sensor error
Temperature signal from Sc3 air on condenser defective
Heat recovery sensor error
Temperature signal from Shrec heat recovery thermostat defective
Stw sensor error
Temperature signal from hot water circuit is defective
Shr sensor error
Temperature signal from heat circuit is defective
Saux_ sensor error
Signal from extra Temp.sensor Saux_ is defective
Paux_ sensor error
Signal from extra pressure sensor Paux_ is defective
All compressors
Common safety
High
Common compr. Safety
cutout
All compressors have been cut out on common safety input
Comp. 1 safety
Comp. 2 safety
Comp. 3 safety
_________________
Comp. 12 safety
Medium
Comp. X oil pressure cut out
Compressor no. x has been cut out on oil pressure safety
Comp. x over current cut out
Compressor no. x has been cut out on over current safety
Comp. 1 motor prot. cut out
Compressor no. x has been cut out on motor protection safety
Comp. 1 disch. Temp cut out
Compressor no. x has been cut out on discharge temperature safety
Comp. 1 disch. Press. Cut out
Compressor no. x has been cut out on discharge pressure safety
Comp. 1 General safety cut
out
Compressor no. x has been cut out on general safety
VSD safety
Medium
Comp. 1 FCD safety error
Variable speed drive for comp. x has been cut out on safety
Comp. Low oil lvl
Medium
Low oil level comp. x
Oil level too low in compressor x
Comp. High oil lvl
Medium
High oil level in compressor x
Oil level too high in compressor x
Separator alarms
Medium
Low oil in separator x
Oil level too low in separator x
No oil separated sep. x
No oil in oil separator x
To high oil in separator x
Oil level too high in separator x
Remaining oil separator x
Separator x can not be emptying total for oil
Receiver alarm
Medium
Oil recv. high level
Oil level too high in receiver
Oil recv. low level
Oil level is too low in receiver
Rec. high pressure
Medium
Recv. High pressure alarm
Pressure too high in receiver
Rec. low pressure
Medium
Recv. Low pressure alarm
Pressure too low in receiver
Condensor
High Sd temp.
High
High disch. temp. Sd_
Safety limit for discharge temperature has been exceeded
High Pc pressure
High
High pressure Pc_
High safety limit for condensing pressure Pc has been exceeded
Pc/S7 Sensor error
High
Pc_ sensor error
Pressure transmitter signal from Pc is defective
S7A sensor error
Temperature signal for S7 media temperature sensor is defective
Detect blocked air flow
Medium
Air flow reduced cond. A
The intelligent air flow monitoring of the condenser reports that a
cleaning is due
Содержание ADAP-KOOL AK-PC 783
Страница 31: ...AK PC 783 Capacity controller RS8GN202 Danfoss 11 2013 31...
Страница 41: ...AK PC 783 Capacity controller RS8GN202 Danfoss 11 2013 41 Example continued...
Страница 44: ...44 Capacity controller RS8GN202 Danfoss 11 2013 AK PC 783...
Страница 125: ...AK PC 783 Capacity controller RS8GN202 Danfoss 11 2013 125...