Menu operation   RC8CE202  ©  Danfoss 03/2013 

AK-PC 781 Version 4.1x 

 

Rec. Status 

0: Off

 

 

1: Standby

 

 

2: Normal

 

 

3: Emergency operation

 

 

4: Manual

 

Prec Bar 

Read pressure of receiver 

 

Vrec OD% 

Read opening degree of receiver valve

Settings 

Main switch 

Main switch: 

ON:  Regulation

 

 

 

OFF:  Controller stopped

 

HP control ManAut 

Control of high pressure valve: 1=automatic, 2=manual override

 

Vhp manual OD% 

Manual setting of opening degree of high pressure valve

 

Pgc min. Bar 

Setting of gas coolers min. pressure

 

Pgc max. Bar 

Setting of gas coolers max. pressure

 

Extra capacity offs 

Set requested pressure increase if the "extra cooling capacity" is activated

 

dT Subcool K 

Set requested sub cooling in the sub critical range 

 

Rec. Control ManAut 

Control of receiver valve: 1=automatic, 2=manual override 

 

Rec. Manual OD% 

Manual setting of opening degree of the receiver valve

 

Prec setpoint Bar 

Set requested receiver pressure

Oil management

Measurements 

AK error 

When “ON”, the controller is in alarm condition.

 

Comp. ctrl. temp °C 

Actual temperature for control sensor (Po or S4)

 

Comp. ctrl. ref. °C 

Actual reference temp. for compressor capacity 

 

 

(incl. external reference signal, if any)

 

Compressor cap. % 

Cut-in compressor capacity in % (of total capacity)

 

Request Comp. Cap % 

Reference for compressor capacity (deviations may be due to time delays)

 

P0 °C 

Suction pressure in °C.  (Measured with the pressure transmitter)

 

Ss Suction gas °C 

Actual suction gas temperature

 

Cond. ctrl. temp °C 

Actual temperature for control sensor (Pc or S7)

 

Cond. ctrl. ref. °C 

Actual reference temp. for condenser capacity

 

 

(incl. external contributions, if any)

 

Cond. cap.  % 

Cut-in condenser capacity in % (of total capacity)

 

Request Cond. cap % 

Reference for condenser capacity

 

Pc Bar 

Condensing pressure (measured with the pressure transmitter)

 

Tc °C 

Condensing pressure in °C. (measured with the pressure transmitter)

 

Gc status 

Actual gas cooler operation:

 

 

0=Off.  1=Standby.  2=Max COP operation. 3=Heat recovery. 4=Extra capacity.

 

 

5=Manual control.

 

Pgc Bar  

Actual gas cooler pressure

 

Pgc reference Bar 

Actual reference for gas cooler pressure 

 

Sd discharge gas °C 

Actual discharge gas temperature

 

Sgc °C 

Actual temperature at outlet from the gas cooler

 

Rec. pressure 

Actual pressure in receiver

 

Rec. pres. buildup 

Status of oil separator

Settings 

Main switch 

Main switch: 

ON:  Regulation

 

 

 

OFF:  Controller stopped

 

Interval time 

Time between breaks. (Simple oil equalisation)

 

Equalisation time 

Duration of oil equalisation (Simple oil equalisation)

 

Rec. pres. cutin Bar 

Reciever pressure, which to cutin for the oil

 

Rec.pres.cutout  Bar 

Receiver pressure, which to cutout for the oil

 

High alarm limit Bar 

Alarm limit high

 

Low alarm limit Bar 

Alarm limit low

 

High alarm delay m 

Delay time for high pressure alarm

 

Low alarm delay m 

Delay time for low pressure alarm

 

Lvl. alarm delay s 

Delay time for Level alarm

Condenser capacity control

Measurements 

AK error 

When “ON”, the controller is in alarm condition.

 

Comp. ctrl. temp °C 

Actual temperature for control sensor (Po or S4)

 

Comp. ctrl. ref. °C 

Actual reference temp. for compressor capacity 

 

 

(incl. external reference signal, if any)

Содержание ADAP-KOOL AK-PC 781

Страница 1: ...Capacity controller with heat recovery AK PC 781 User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...an only be made from the Service Tool programme There are four kinds of settings ON OFF settings settings with a variable value time settings and reset alarms Enter the new value or move the sliding s...

Страница 3: ...e Read the next section Documentation Documentation Documentation of the settings of the individual controllers can be made with the print function in the AKM programme Select the controller for which...

Страница 4: ...FF in order to set configuration lock in open position 0 Open 1 Locked Refrigerant type Po Select refrigerant type 0 not selected 1 R12 2 R22 3 R134a 4 R502 5 R717 6 R13 7 R13b1 8 R23 9 R500 10 R503 1...

Страница 5: ...l status on Comp release output signal from MT controller MT request input Actual status on Comp request input signal on MT controller LT request output Actual status on Comp request output signal fro...

Страница 6: ...oad shed input 1 Load shed limit 2 Set max capacity limit for load shed input 2 MT release delay s Time delay on output signal Comp release on MT controller MT request delay s Time delay on input sign...

Страница 7: ...e m Minimum duration of OFF period 2 Min OFF time m As above for compressor no 2 to 8 1 Recycle time m Minimum period of time between two successive starts 2 Recycle time m As above for compressor no...

Страница 8: ...p C Actual temperature for control sensor Pc or S7 Cond ctrl ref C Actual reference temp for condenser capacity incl external contributions if any Cond cap Cut in condenser capacity in of total capaci...

Страница 9: ...pacity control is ready to start 6 Unloaded 7 9 Part loaded 10 Full loaded All capacity cutin 11 Running Capacity control is running Air flow status 0 No RFG selectNo refrigerant has been selected mon...

Страница 10: ...pressure measured with the pressure transmitter Tc C Condensing pressure in C measured with the pressure transmitter Gc status Actual gas cooler operation 0 Off 1 Standby 2 Max COP operation 3 Heat re...

Страница 11: ...overy is on HR temp cutin C Not at CO2 Temperature value when thermostat switch to heat recovery HR temp cutout C Not at CO2 Temperature value when thermostat switch off the heat recovery Alarm priori...

Страница 12: ...capacity Request Compr Cap Reference for compressor capacity deviations may be due to time delays P0 C Suction pressure in C Measured with the pressure transmitter Ss Suction gas C Actual suction gas...

Страница 13: ...ment of function defined in Pressostat 1 Pressostat 2 Bar As above but for Pressostat 2 Pressostat 3 Bar As above but for Pressostat 3 Settings Main switch Main switch ON Regulation OFF Controller sto...

Страница 14: ...where the relay is to cut in V1 Cutout The value where the relay is to cut out V1 Cutin delay m Time delay for cutin of relay V1 Cutout delay m Time delay for cutout of relay V1 High Al Limit The valu...

Отзывы: