User 

Guide RS8GY302 © Danfoss 2015-06 

AK-PC 

551

Start/stop

Main switch

Main switch

Start and stop regulating here.

The configuration settings will require that regulating is stopped. 

If you try to enter a configuration setting when regulating has started, the controller will  

ask if regulating should be stopped.

When all settings have been made and the main switch is set to “ON”, the controller will  

enable the display of the various measurements. Regulation will start. (If an external main 

switch has been defined, it must also be “ON” before regulating starts.) 

On / Off

Extern Main swich

External main switch

It is possible to connect an external switch which can be used to start and stop regulating.

Both the internal and external main switch must be ON before regulating starts. 

An external main switch can be defined in the menu “Plant type” - “Main switch via DI”.   

Plant type

Select Plant type

Plant settings:

The following must be regulated:

• Compressor group

• Condenser group

• One compressor group (A) + One condenser group

• Two compressor groups (A) and (B) + One condenser group

Fac: None

Refrigerant type

Refrigerant setting

Before refrigeration is started, the refrigerant must be defined. You may choose between  

the following refrigerants:

R12,  R22,  R134a,  R502,  R717,  R13,  R13b1,  R23,  R500,  R503,  R114,  R142b, user defined, 

R32, R227,  R401A,  R507, R402A,  R404A, R407C,  R407A,  R407B,  R410A,  R170,  R290,  R600,  

R600a,  R744,  R1270,  R417A,  R422A, R413A, R422D, R427A, R438A, R513A (XP10), R407F.

Warning: Wrong selection of refrigerant may cause damage to the compressor.

Other refrigerants: Here Setting "user defined" is selected and then three factors - fac1, fac2 

and fac3 and temperature glide (if necessary).

Fac: None

Unit of setpoints

Device for controlling compressor and condenser

Select pressure or saturation temperature.

(Can be set during initial set-up and must not be subsequently changed.)

Temp. / press

Fac: Saturated

Night signal via DI

Night time operation via DI signal

Define an external switch here, so that the regulation reference can be raised and lowered 

externally. 

1. Set the function to “Yes”

2. Go to I/O configuration and select an available digital input. Set this input to  

“Night condition”

3. Next, define whether the function is to be active when the signal is ON, or when it is OFF.

DI-demand

No / Yes

Fac: No

Main Switch via DI

Main switch via DI

Define an external main switch here, so that regulation can be started and stopped  

externally.

1. Set the function to “Yes”

2. Go to I/O configuration and select an available digital input. Set this input to “Main switch”

3. Next, define whether the function is to be active when the signal is ON, or when it is OFF. 

DI-demand

No / Yes

Fac: No

Mains frequency

Frequency

Set the net frequency

50 Hz / 60 Hz

Fac: 50 Hz

Alarm output

Alarm relay

Define an alarm relay here that will be activated in the event of an alarm.

1. Select the alarm priority that will activate the relay

• No relay

• Critical alarm

• Severe alarm

• All alarms

2. Go to I/O configuration and select an available digital output. Set this output to “Alarm”

3. Next, define whether the relay will be active (pulled) when the alarm is ON, or when it is 

OFF.

DO-demand

Fac: No relay

Alarm buzzer

Alarm sound

Here the sound generator can be defined to emit a sound in the event of an alarm.

Select which alarm priority will activate the sound generator:

• No buzzer

• Critical alarm

• Severe alarm

• All alarms

(In the event of an alarm, the sound generator can be stopped by moving across the  

active alarm screen;  see page 6) 

Fac: No buzzer

Suction A

Control status

Regulation status

Menu

SW: 1.5x

Содержание ADAP-KOOL AK-PC 551

Страница 1: ...Capacity Controller AK PC 551 User Guide ADAP KOOL Refrigeration Control System...

Страница 2: ...ignal from automatic safety control day night signal etc Relay outputs max 6 pcs Connection of compressors condenser fans Solid state outputs max 2 pcs Control of capacity valve on a Copeland digital...

Страница 3: ...ne cut in of the next compressor arrow up is permitted When the pressure is lower than the reference a half neutral zone cut out of a compressor arrow down is permitted When the pressure is within the...

Страница 4: ...ing functions Fixed reference Variable reference which follows the outdoor temperature When the outdoor temperature drops the reference will drop by a corresponding amount This variable reference requ...

Страница 5: ...am or Bitzer CRII the capacity will be increased so that the compressor can cool down itself The compressors will be stopped if the temperature nears the set max temperature value Sensor failure If la...

Страница 6: ...low 1 condenser group 1 suction groupe 2 suction groups 2 suction groups and 1 condenser group Each of the four rows above is continued with three additional displays The arrow in the top corner of th...

Страница 7: ...ly None Main Menu The first setting is the Plant type When the Plant type has been selected it will al low several settings to be made For example Continue to the next menus All settings are explained...

Страница 8: ...nit of setpoints Device for controlling compressor and condenser Select pressure or saturation temperature Can be set during initial set up and must not be subsequently changed Temp press Fac Saturate...

Страница 9: ...atus of the load shed function can be read here Injection ON A The status of the injection ON signal sent to the evaporator controllers can be read here MC Load Shedding The status of the load shed si...

Страница 10: ...c Po Compressor mode Set the type of compressor to be used for regulation Multi all All compressors have unloaders Multi Single First compressor has unloaders The remaining ones are one step units Spe...

Страница 11: ...d Network The controller sends a signal to the system unit which then forwards it to the evaporator controls Relay The function reserves a relay that pulls in if all compressors are stopped All evapor...

Страница 12: ...ssors Suction B Suction group B Please see descriptions under suction group A Bitzer CRII can not be used in suction group B Condenser Control status Regulation status Control status Here you can read...

Страница 13: ...Step on off control of fans will be via relays Variable step The signals are parallel so external wiring can switch over to step e g if the frequency converter fails AO demand Step Speed Fac Step No...

Страница 14: ...im A Alarm limit for excess superheating Min 20 K Max 80 K Fac 80 K Superheat delay A Delay time before alarm is generated for insufficient or excess superheating Min 0 min Max 60 min Fac 5 min SdA Ma...

Страница 15: ...t to thermostat AI demand Yes No Fac No Thermostat cut in Here set the temperature value at which the thermostat will cut in Min 50 C Max 150 C Fac 5 C Thermostat cut out Here set the temperature valu...

Страница 16: ...rge gas temperature monitoring an NTC 86K 25 C can also be selected Calibration value 10 C Pressure sensors Signal type 0 20mA 4 20mA AKS32 1 5V or AKS32R 10 90 ratiometric of 5 V supply voltage Minim...

Страница 17: ...bration I O Summary DO Max 8 Used __ DI Max 8 Used __ AO Max 2 Used __ AI Max 8 Used __ Inputs and outputs used Here you can see how many of the different inputs and outputs are available You can also...

Страница 18: ...A FS 1 3 x 5 4CA FS 4 x 4 4CA 4F 4 4 3 3CSA FS 1 2 x 2 3CA FS 3 x 1 3CA 3 F 3 3 0 None After making a selection the setting will return to None After making a selection you must 1 Set the type of refr...

Страница 19: ...1 Fan2 Fan3 Alarm PoA PoB Pc Sc3 C1A C2A C1B CB2 Main Sw Fan safe 10 4CDA FS C1 C2 C3 C4 C1 PWM Fan VSD Alarm Fan Speed PoA Pc Sc3 SdA Digi C1 C2 C3 C4 Main Sw Fan safe 9 3CDA FS C1 C2 C3 C1 PWM Fan V...

Страница 20: ...tion groups A and B respectively Fan safety input External main switch start stop HP safety switch LP safety switch for suction groups A and B respectively Night status Heat recovery Load sheeding Ge...

Страница 21: ...Low superheat Superheat in suction line A too low measured by PoA and SsA SdA High discharge temp Safety prevention limit for SdA discharge temperature has been exceeded 10K below safety limit High di...

Страница 22: ...newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until the Bios menu appears 2 Select the MCX se...

Страница 23: ...pply Avoid earth fault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals N and AO3 respectively N and AO4 PAY ATTENTION TO THE POLARITY o...

Страница 24: ...r capacity is distributed by up to 50 for one relay and the remaining 50 100 for the unloader The unloader is con nected to DO5 or DO6 Injection off The electronic expansion valves in the cooling appl...

Страница 25: ...5 4 A inductive 2 pcs SPST 16A AC 1 10 A ohmic AC 15 3 5 inductive 2 pcs Solid State PWM for scroll unload Imax 0 5A Imin 50 mA Leak 1 5 mA 2 Voltage output 0 10 V d c Ri 1kohm Separate 24 V supply re...

Страница 26: ...hts reserved Installation considerations Accidental damage poor installation or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possi...

Отзывы: