HEATING SWITCH

 

(d) 

With selector switch in 

ON

 position, terminal 2  

 

should be LIVE.

 

(e) 

With selector switch in 

OFF

 position, terminal 3  

 

should be LIVE.

 

(f) 

With selector switch in 

TIMED

 position, terminal  

 

2 should be LIVE between tappets A-B and C-D  

 

and terminal 3 should be LIVE between tappets  

 

B-C and D-A.

9.  Remove cut-out from bottom of outer case as 

required. Re

fi

 t outer case and selector switch 

fi

 xing 

rings. Check that outer case sits squarely on body and 
is not distorted by an uneven wall surface.

10.  Rotate dial clockwise through at least one complete 

revolution and check that all four tappets are clear of 
outer case aperture.

11.  Ease of installation can be achieved by the use of the 

Danfoss Randall Wiring Centre which is obtainable 
from most Builders Merchants and Distributors.

 
 

 

NOTE: If a Wiring Centre is used follow the  

 

installation instructions included with that  

 

unit and not the wiring diagrams overleaf.

 

!

Installation

Содержание 4033

Страница 1: ...4033 Installation User Instructions electro mechanical programmer for controlling heating hot water Return to www uk plumbing com...

Страница 2: ...2 INDEX Index Installation Product specification 3 Installation 4 5 Wiring 6 7 User Your programmer 8 Programming the unit 8 9 Setting the clock 9 Using the programmer 10 11 Contact details 12...

Страница 3: ...supply 230 15 Vac 50 60Hz Switch action 2 x SPDT type 1B Switch rating Max 264 Vac 50 60Hz 3 1 A Timing accuracy 1 min month Enclosure rating IP30 Max ambient temperature 55 C Dimensions mm W H D 102...

Страница 4: ...in programmer module and re tighten the 2 retaining screws do not overtighten 7 Switch on mains turn both selector switches to ON and light up boiler according to manufacturer s instructions 8 With b...

Страница 5: ...uter case and selector switch fixing rings Check that outer case sits squarely on body and is not distorted by an uneven wall surface 10 Rotate dial clockwise through at least one complete revolution...

Страница 6: ...s Randall HP22 or HP28 Flying lead Flying lead 2 4 1 N 1 2 3 4 5 6 7 Danfoss Randall ATC Cylinder Stat 2 3 1 3 core 2 core 3 core Danfoss Randall RMT230 Room Stat 4033 Terminals Mains Supply N L 2 cor...

Страница 7: ...Terminals Mains Supply N L N N L L Boiler Pump Junction Box Blue Grey Orange Brown White L N 2 4 1 Danfoss RMT Room Stat 1 3 2 Danfoss Randall ATC Cylinder Thermostat Danfoss Randall HS3 mid position...

Страница 8: ...Heating and Hot Water independently of each other either at the set times constantly ON constantly OFF Your Programmer Programming the unit Programming the unit There are four TAPPETS on your timing d...

Страница 9: ...E NB Clock is in 24 hour mode If you want your heating and hot water ON between 7am and 10am and ON again between 5pm and 11pm set tappets as follows A at 1st ON time 7 B at 1st OFF time 10 C at 2nd O...

Страница 10: ...endently of one another letting you select different programmes for each service HEATING switch TIMED the Heating will be switched ON and OFF according to the times at which the tappets have been set...

Страница 11: ...at which the tappets have been set OFF the Hot Water will ignore the tappet positions and remain OFF ON the Hot Water will be ON constantly This enables you to switch the Hot Water ON during a period...

Страница 12: ...neer Name Tel Visit our website www danfoss randall co uk Email our technical department drl_technical danfoss com Call our technical department 0845 121 7505 8 45 5 15 Mon Thurs 8 45 4 45 Fri For a l...

Отзывы: