background image

1

M6 hex nut

5

Side view of assembled ground bar and bracket

2

Ground bar assembly for mains side

6

Front view of assembled ground bar and bracket

3

Angle bracket

7

Ground bar assembly for motor side

4

M5x18 mm screw

8

End view of assembled ground bar and bracket

Illustration 1.2 Assembly of Ground Bars and Angle Brackets

1.

Attach the ground bars to the angle brackets:

1a

Place 1 ground bar over the 2 threaded
posts on the angle bracket.

1b

Fasten 2 M6 hex nuts (T30) to the bracket
posts, 1 on each post. See 

Illustration 1.2

.

1c

Tighten nuts to 3.9 Nm (35 in-lb).

1d

Repeat for remaining ground bar and angle
bracket. Position ground bar with the long
end oriented in the opposite direction on

Installation Instructions

Ground Bar Kit for E1h/E2h Drives
VLT

®

 FC Series FC 102, FC 103, FC 202, and FC 302

MI35K102

Danfoss A/S © 10/2017 All rights reserved.