2 Installation

2.1 Safety Information

N O T I C E

QUALIFIED PERSONNEL

Only qualified, Danfoss authorized personnel are allowed to install the parts described in these installation instructions.

Disassembly and reassembly of the frequency converter must be done in accordance with the service guide.
Use the standard fastener torque values from the service guide, unless the torque value is specified in these instructions.

W A R N I N G

DISCHARGE TIME (40 MINUTES)

The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not pow-
ered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait 40 minutes after power has
been removed before performing service or repair work can result in death or serious injury.

Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other
frequency converters.
Disconnect or lock the motor.
Disconnect any brake option.
Disconnect any DC connector option.
Wait 40 minutes for the DC-link capacitors to discharge fully.
Before performing any service or repair work, measure the voltage level to verify that the capacitors are fully discharged.

W A R N I N G

ELECTRICAL SHOCK HAZARD

The frequency converter contains dangerous voltages when connected to mains voltage. Improper installation, and installing or
servicing with power connected, can cause death, serious injury, or equipment failure.

Only use qualified electricians for the installation.
Disconnect the frequency converter from all power sources before installation or service.
Treat the frequency converter as live whenever the mains voltage is connected.
Follow the guidelines in these instructions and local electrical safety codes.

N O T I C E

ELECTROSTATIC DISCHARGE

Electrostatic discharge can damage components.

Ensure electrostatic discharge before touching internal frequency converter components, for example by touching a groun-
ded, conductive surface or by wearing a grounded armband.

AN361428862578en-000101 / 136R0249 | 3

Danfoss A/S © 2022.03

Installation

In-back/Out-back Cooling Kit for FA11-FA12

Installation Guide

Содержание 176F4057

Страница 1: ...tration 1 Direction of Airflow with Kit Installed 1 Top cover 2 Cabinet 3 Pedestal 4 Cooling back channel 5 Air flow direction 6 Bottom cover 1 2 Kit Numbers Use these instructions with the following...

Страница 2: ...ing Kits Item Quantity Top cover 1 Top gasket 1 Bottom cover 1 Bottom gasket 1 Back duct 2 6 hole gasket 4 8 hole gasket 4 Clip on nut 16 M5x14 screw 8 10 M5x18 screw 16 M6x12 screw 12 AN361428862578e...

Страница 3: ...or Disconnect any brake option Disconnect any DC connector option Wait 40 minutes for the DC link capacitors to discharge fully Before performing any service or repair work measure the voltage level t...

Страница 4: ...etal parts Before affixing a gasket check that the part matches the gasket and that no holes are covered 2 1 3 4 5 6 7 8 9 10 11 12 e30bg242 10 Illustration 2 Overview of In back Out back Cooling Kit...

Страница 5: ...6 mounting holes in the back of the frequency converter using the dimensions in the template Insert 6 M10 pem self clinching nuts not supplied in the mounting holes Cut out the upper and lower vent op...

Страница 6: ...6 12 8 347 13 7 1645 64 7 215 8 5 0 0 7 0 3 3 0 1 215 8 5 1335 52 6 1357 53 4 1368 53 9 1513 59 6 1524 60 0 1545 60 8 2X 230 9 1 2X 230 9 1 e30bg240 10 Illustration 3 Vent Dimensions for Mounting Plat...

Страница 7: ...te To create upper and lower vent openings in the cabinet backplate use the following steps Use the dimensions in Illustration 5 for 600 mm 24 in cabinets and Illustration 6 for 800 mm 32 in cabinets...

Страница 8: ...2X 232 9 1 225 8 9 2X 218 8 6 2X 82 3 2 75 3 0 2X 68 2 7 244 9 6 2X 218 8 6 225 8 9 2X 232 9 1 2X 68 2 7 75 3 0 2X 82 3 2 0 0 592 23 3 e30bg241 10 Illustration 5 Vent Dimensions for Backplate in 600 m...

Страница 9: ...dhesive Adhere the top gasket to the underside of the top cover Remove the M5x14 screws T25 surrounding the sides and back of the vent in the top of the frequency converter Retain the screws FA11 conv...

Страница 10: ...on tubing with interior diameter of 8 mm 0 3 in To seal the drain in dry environments fasten a screw in the drain hole To install the bottom cover at the lower end of the cooling back channel use the...

Страница 11: ...g plate in the Rittal cabinet aligning the top mounting plate hole with the 5th hole from the top of the cabinet rails Check that the pem nuts face the back of the cabinet Fasten the mounting plate to...

Страница 12: ...he cabinet behind the mounting plate Secure the backplate to the rails using the existing fasteners Slide 8 M5 clip on nuts over the screw holes surrounding the upper duct opening in the backplate Rep...

Страница 13: ...uct Torque screws to 3 9 Nm 35 in lb Fasten the outer flanges of the back ducts with 16 M5x18 screws T25 8 screws in each duct Torque screws to 2 3 Nm 20 in lb AN361428862578en 000101 136R0249 13 Danf...

Страница 14: ...n a quotation or order confirmation Danfoss cannot accept any responsibility for possible errors in catalogues brochures videos and other material Danfoss reserves the right to alter its products with...

Отзывы: