1.4.2 Installing Power Terminal Mounting

Plate

To install the new power terminal mounting plate in the drive,
use the following steps. Refer to 

Illustration 1.4

 and

Illustration 1.5

.

1.

Position the power terminal mounting plate in the
drive.

2.

Fasten the plate with 7 M5x11 thread-cutting screws
(T25).

3.

Connect the wire harness to the MK100 connector on
the power card.

4.

Connect the fan cable to the mixing fan cable
connector.

5.

Insert the mixing fan into the fan housing, with the
label facing the open side of the housing.

6.

With the fan label facing up, insert the mixing fan
assembly into the slot in the plate and press. The fan
assembly is level with the plate when properly
seated.

7.

For the IP21/Type 1 and IP54/Type 12 enclosures
only, fasten 4 ground nuts with captive washer
(10 mm) in the power terminal mounting plate.

8.

For IP20/Chassis enclosures only, fasten 3 nuts
(8 mm) at the bottom of the plate.

1.4.3 Installing Motor Terminal Block

To install the motor terminal block, use the following steps.
Refer to 

Illustration 1.4

.

1.

Position the output terminal block by sliding it
upward under the 2 metal retaining clips on the
power terminal mounting plate.

2.

Fasten 2 M5x12 machine screws (T25) at the bottom
of the terminal block.

3.

Position the 3 Nomex tubes, 1 in the middle of each
current sensor.

4.

Insert 3 cylinder busbars, 1 inside each Nomex tube.

5.

Replace the U motor busbar:

5a

Slide the insulator sleeve over the U busbar.

5b

Fasten 1 screw (T30) in the current sensor
end of the busbar.

5c

Fasten 1 thread-forming screw (T25) in the
middle of the busbar.

6.

Replace the V motor busbar:

6a

Fasten 1 screw (T30) in the current sensor
end of the busbar.

6b

Fasten 1 thread-forming screw (T25) in the
middle of the busbar.

7.

Replace the W motor busbar:

7a

Fasten 1 screw (T30) in the current sensor
end of the busbar.

7b

Fasten 1 thread-forming screw (T25) in the
middle of the busbar.

8.

Position the EMC shield between the mains input
terminal block and motor terminal block and secure
with 1 screw (T25).

9.

Reconnect wiring to the motor terminals, and replace
the U/V/W terminal label.

1.4.4 Installing Brake Terminals (Optional)

To replace the optional brake terminals, if any, use the
following steps.

1.

Install the brake terminal block by fastening 2 nuts
(13 mm) in the block.

2.

Install the R (-) terminal:

2a

Fasten 1 thread-forming screw (T25) at the
terminal block.

2b

Fasten 1 additional nut (13 mm).

3.

Install the R (+) terminal:

3a

Fasten 1 thread-forming screw (T25) at the
terminal block.

3b

Fasten 1 additional screw (T40).

1.4.5 Installing Mains Input Terminal Block

1.

Position the mains input terminal block on the power
terminal mounting plate and slide it upward under 2
metal retaining clips.

2.

Fasten 2 screws (T25) at the bottom of the mains
input terminal block.

3.

Route the current sensor wiring through the cable
retaining clips.

4.

Place the R/S/T terminal label above the terminal
connections.

Installation Instructions

300 A/500 A Current Sensor Kit for D2h/D4h/D7h/D8h Drives
VLT

®

 FC Series FC 102, FC 103, FC 202, FC 302

8

Danfoss A/S © 07/2018 All rights reserved.

MI70V202

Содержание 176F3737

Страница 1: ... T7 525 690 160 315 200 350 Table 1 2 Applicable Power Ranges for 500 A Current Sensor Kit 1 1 1 Identifying the Power Rating To find the drive power rating use the following steps 1 Obtain the following information from the nameplate which is on the drive Refer to Illustration 1 1 Product group and drive series characters 1 6 Power rating characters 7 10 Voltage rating phases and mains characters...

Страница 2: ...ZARD VLT FC series drives contain dangerous voltages when connected to mains voltage Improper installation and installing or servicing with power connected can cause death serious injury or equipment failure To avoid death serious injury or equipment failure Only use qualified electricians for the installation Disconnect the drive from all power sources before installation or service Treat the dri...

Страница 3: ...e 1 6 Torque Values for Thread Cutting into Metal Shaft size Torx drives size Class A Nm in lb Class B Nm in lb M4 T20 2 8 24 2 8 24 M5 T25 5 1 45 4 0 35 Table 1 7 Torque Values for Thread Forming into Plastic Class A Clamping metal Class B Clamping PCA or plastic 1 3 2 Removing AC Input Busbars To remove the AC input busbars use the following steps The AC input busbars can look different when the...

Страница 4: ...ce 1 3 4 Removing Brake Terminals Optional Drives can be configured with optional brake terminals To remove the brake terminals if any use the following steps 1 Disconnect the customer brake wiring if present 2 Remove the R terminal 2a Unfasten 1 thread forming screw T25 at the terminal block 2b Unfasten 1 additional screw T40 3 Remove the R terminal 3a Unfasten 1 thread forming screw T25 at the t...

Страница 5: ...Release the current sensor cables from the current sensors 4 Unplug the wire harness from the power card and discard it 5 Lift the power terminal mounting plate and unplug the mixing fan cable that is located under the plate 6 Remove the power terminal mounting plate with the old current sensors attached and discard it Installation Instructions 300 A 500 A Current Sensor Kit for D2h D4h D7h D8h Dr...

Страница 6: ...guide wire routing clip M5x11 thread cutting screw power terminal mounting plate IP20 Chassis and IGBT busbars in 300 A current sensor kit only 7 Motor terminal block 18 Motor busbar V 8 Cable retaining clip 19 Motor busbar W 9 M10 nut with captive washer 20 M5x16 torx screw 10 Cable clamp adapter 21 M8x70 screw 11 Power terminal mounting plate IP21 IP54 22 Cylinder busbar Illustration 1 4 Explode...

Страница 7: ...d the front of the drive 2 Secure 6 M4x10 thread forming screws T20 2 in the base of each current sensor Torque to 2 0 Nm 17 7 in lb 3 Connect the wire harness to the current sensors 1 cable to each current sensor 4 Route the cables through the cable guides 1 M4x10 thread forming screw 2 Current sensor 3 Current sensor cable connector 4 Mounting hole 5 Power terminal mounting plate 6 Mounting hole...

Страница 8: ... busbar 5b Fasten 1 screw T30 in the current sensor end of the busbar 5c Fasten 1 thread forming screw T25 in the middle of the busbar 6 Replace the V motor busbar 6a Fasten 1 screw T30 in the current sensor end of the busbar 6b Fasten 1 thread forming screw T25 in the middle of the busbar 7 Replace the W motor busbar 7a Fasten 1 screw T30 in the current sensor end of the busbar 7b Fasten 1 thread...

Страница 9: ... the fuses 4 Connect the customer mains input power wiring 5 Replace the air baffle and secure with 4 screws T25 and 2 nuts 13 mm RFI filter only 1 Connect the RFI cable to MK100 on the RFI printed circuit card 2 Fasten the RFI filter to the side channels of the drive with 4 thread cutting screws T20 3 Secure the top of the RFI filter using 3 nuts 13 mm 1 per phase 4 Secure the bottom of the RFI f...

Страница 10: ...ducts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S Ulsnaes 1 DK 6300 Graasten vlt drives danfoss com MI70V202 MI70V202 130R0678 07 2018 ...

Отзывы: