background image

MCD Remote Operator 

 

4-20 mA Analog Output 

 

MG.17.E5.02 - VLT

®

 is a registered Danfoss trademark 

5.

 

4-20 mA Analog Output 

 

N.B.!:

 

When using the Remote Operator with MCD 500 models MCD5-0023B ~ MCD5-0068B, 
the motor current and analog output must be normalised using Pars. 6 and 9.  => 
Programmable Parameters for details. 

5.1.

 

Overview 

The Remote Operator has a 4-20 mA analog output for monitoring motor current.  The 4-20 mA output 
is available on terminals B10, B11. 

The analog output signal spans from 4 mA when the motor current is zero (when the soft starter is not 
running) to 20 mA when the motor current is 125% of the Motor FLC setting in the Remote Operator 
(Parameter 6). 

 

N.B.!: 
The 4-20 mA output is available only when the Remote Operator is connected to MCD 202, 
MCD 500 and MCD 3000 soft starters.  

 

5.2.

 

Calibration 

The Remote Operator Motor FLC parameter (Parameter 6) must be adjusted to match the Motor FLC 
setting in the soft starter. The lower end of the analog output signal can be calibrated using the Remote 
Operator Analog Output 4 mA Offset parameter (Parameter 7). This is set to give a 4 mA output signal 
when the motor current is zero. 

The 4-20 mA analog output has an accuracy of ±10%.  It is not designed for process signal control use 
and should only be used for motor current monitoring and metering. 

 

N.B.!: 
The analog output uses only one Motor FLC setting. This function is not suitable for 
applications using two motor parameter sets.  

 

5.3.

 

Programming 

When the 4-20 mA output is being used, the Remote Operator's Motor FLC and Analog Output 4 mA 
Offset parameters (Parameters 6 and 7) must be set appropriately (=> Calibration above). 
Programming can only be carried out while the soft starter is not running. 

5.4.

 

Programming Procedure 

1.

 

 To enter Programming Mode, hold down the Data/Prog pushbutton for four seconds. The 
default value of the first parameter will be displayed. 

2.

 

Use the Data/Prog pushbutton to advance to the next parameter. 

3.

 

Use the Stop and Reset pushbuttons to adjust parameter values. 

 

Programming Mode closes when the Data/Prog pushbutton is pressed after Parameter 8. 

 

N.B.!: 
There is a 20 second timeout when the Remote Operator is in Programming Mode. 
Programming Mode will automatically close if no input is registered for 20 seconds. Any 
changes already made will be saved.  

 

Содержание 175G3061

Страница 1: ...actice for RS485 communications when installing and using this equipment 1 2 General Description The Remote Operator can be used with MCD 200 MCD 3000 and MCD 500 soft starters and offers the followin...

Страница 2: ...Remote Operator through the cutout and locate the mounting bracket at the rear of the panel onto the four studs Use the four fasteners to tighten the mounting bracket up to the rear of the panel For u...

Страница 3: ...177HA264 11 Remove mains and control voltage from the soft starter before attaching or removing accessories Failure to do so may damage the equipment Once the Remote Operator Module has been installed...

Страница 4: ...lows 1 Protocol AP ASCII 2 Address 20 3 Baud Rate 9600 4 Parity No parity 5 Timeout No timeout 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 16 8 4 2 1 0 0 0 0 0 DIP SWITCH A DIP SWITCH B 177HA543 10 1 2 3 4 5 4 Appl...

Страница 5: ...starter 177HA375 10 MCD 3000 REMOTE OPERATOR RS485 SERIAL PORT 68 61 69 B1 B2 B3 B6 B7 B8 GND RS485 STARTER RS485 NETWORK 4 20 mA ANALOGUE OUTPUT MOTOR CURRENT B10 B11 4 20 mA SUPPLY VOLTAGE 18 30 VA...

Страница 6: ...Interface AP ASCII protocol as standard Connection Terminals B1 B2 B3 3 pole spring clamp connector terminals Analog Output Motor Current Monitoring Interface 4 20 mA max burden 200 Connection Termin...

Страница 7: ...h the serial communications network if connected on the network side of the Remote Operator SOFT STARTER START STOP DATA PROG RESET START RUN TRIP RS485 AMPS TEMP CODE Stop Pushbutton Start Pushbutton...

Страница 8: ...and 1 11 instead of motor temperature N B When using the Remote Operator with MCD 500 models MCD5 0023B MCD5 0068B the motor current and analog output must be normalised using Pars 6 and 9 Programmab...

Страница 9: ...rameter Parameter 7 This is set to give a 4 mA output signal when the motor current is zero The 4 20 mA analog output has an accuracy of 10 It is not designed for process signal control use and should...

Страница 10: ...mote Operator start stop quick stop function enabled Network start stop quick stop function disabled 2 Remote Operator start stop quick stop function disabled Network start stop quick stop function en...

Страница 11: ...5 LED flashing The Remote Operator has detected a loss of communication on the RS485 link to the soft starter Verify and solve the cause for loss of communication If communication is restored before t...

Отзывы: