User Guide
|
Intelligent Purging System (IPS 8) Ammonia
22 | BC344024774466en-000401
© Danfoss | DCS (ms) | 2021.04
Register Parameter Name
Description
User
Level
Min Value
Max Value
Default
Value
Unit/
Type
Read/
Write
Modbus
Function
Code
Modbus
Data Type
Persistent
Yes/No
8123
Event3
Purge cycle event -
counts the accumative
minutes that the
purge valve has been
open on a finished
cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No
8125
Event4
Purge cycle event -
counts the accumative
minutes that the
purge valve has been
open on a finished
cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No
8127
Event5
Purge cycle event -
counts the accumative
minutes that the
purge valve has been
open on a finished
cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No
8129
Event6
Purge cycle event -
counts the accumative
minutes that the
purge valve has been
open on a finished
cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No
8131
Event7
Purge cycle event -
counts the accumative
minutes that the
purge valve has been
open on a finished
cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No
8133
PP1
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8135
PP2
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8137
PP3
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8139
PP4
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8141
PP5
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8143
PP6
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8145
PP7
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8147
PP8
The time percentage
for this purge point
0
-32768
32767
0
%
Read
only
3
Long
No
8149
Val1
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8150
Val2
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8151
Val3
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8152
Val4
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8153
Val5
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8154
Val6
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8155
Val7
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8156
Val8
This indicates if the
purge point is active
0
-32768
32767
0
N/A
Read
only
3
Short
No
8158
TempStatus
The measured
temperature on the
discharge line of
compressor
0
-32768
32767
0
°C
Read
only
3
Short
No
8159
BPLStatus
The pressure on R452
0
-32768
32767
0
bar
Read
only
3
Short
No
8160
BPHStatus
The pressure on R717
0
-2147483648
2147483647
0
bar
Read
only
3
Short
No