User Guide
|
Intelligent Purging System (IPS 8) Ammonia
© Danfoss | DCS (ms) | 2021.04
BC344024774466en-000401 | 21
Register Parameter Name
Description
User
Level
Min Value
Max Value
Default
Value
Unit/
Type
Read/
Write
Modbus
Function
Code
Modbus
Data Type
Persistent
Yes/No
UNIT CONFIG >
VALVE SETTINGS
3022
Max_PP
Used amount of purge
points - part of initial
setup
2
0
8
8
N/A
RW
3/6
Short
Yes
UNIT CONFIG >
LIMITS SETTINGS
3034
Setpoint
Pressure threshhold
for compressor
2
0,0
12,0
6.5
bar
R/W
3/6
Short
Yes
3035
Tsh
Setpoint for superheat
2
5,0
40,0
15
°C
R/W
3/6
Short
Yes
STATUS VAR > MCX
DESIGN HOTSPOTS
1859
Reset Alarms
Reset alarm
0
0
2
0
N/A
R/W
3/6
Short
Yes
8101
SystemOnOff
Feedback from the
main switch
0
-32768
32767
0
Enum 1
Read
only
3
Short
No
8102
ValveStatus
Feedback from the
purge valve - open/
closed
0
-32768
32767
0
Enum 1
Read
only
3
Short
No
8103
CompressorStatus
Feedback from the
compressor - on/off
0
-32768
32767
0
Enum 1
R/W
3/6
Short
Yes
8104
ALARActive
Any alarm active
indicator
0
-32768
32767
0
Enum 2
Read
only
3
Short
No
8105
PressTotemp
Suction temperature
(calculated from
pressure on suction)
0
-327,7
327,7
0
°C
Read
only
3
Short
No
8106
ValveCount
The amount of purge
valve activations
0
-2147483648
2147483647
0
N/A
Read
only
3
Long
No
8108
ComprTime
Remaining time for
compressor pull-down
for the actual purge
pointr cycle
0
-2147483648
2147483647
0
Minutes
Read
only
3
Long
No
8110
COmprStartAfter
The delay between
the purging cycles
0
-2147483648
2147483647
0
Minutes
Read
only
3
Long
No
9901
Advanced Setting -
ResetMem
Recommend default
setting only - All
logged values are
reset
0: NO
1: YES
0
0
1
0
Enum 2
R/W
3/6
Short
Yes
8112
ValveHour
The amount of hours
that the main purge
valve has been active
0
-214748364,8 214748364,7
0
Hours
Read
only
3
Long
No
8114
StatusKL
Status of KL01 relay
(compressor and
crankcase heater)
0
-32768
32767
0
Enum 2
Read
only
3
Short
No
8115
WaringCompr
Indicates problem
with compressor
status
0
-32768
32767
0
Enum 2
Read
only
3
Short
No
8116
ValveSetpoint
Temperature
threshhold for the
opening of the main
purge valve
0
-2147483648
2147483647
0
°C
Read
only
3
Short
No
8117
ValveClose
Temperature
threshhold for the
closing of the main
purge valve
0
-2147483648
2147483647
0
°C
Read
only
3
Long
No
8119
Event1
Purge cycle event -
counts the minutes
that the purge valve
has been open on a
finished cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No
8121
Event2
Purge cycle event -
counts the accumative
minutes that the
purge valve has been
open on a finished
cycle
0
-3276,8
3276,7
0
Minutes
Read
only
3
Long
No