212-0024-6SS
7
July 30th, 2019
Table 1: Recommended Input Power Feed Wire Size
Max. Total Load
Current Amps
Wire Size (AWG) vs Wire Length (3% drop)
<5 ft.
5-10 ft.
10-15 ft.
15-20 ft.
25-30 ft.
25
#10
#6
#6
#4
#2
50
#6
#4
#2
#2
#0
75
#6
#2
#1
#0
#3/0
100
$4
#2
#0
#2/0
#4/0
Table 2: Recommended Circuit Load Wire Size
Max. Total Load
Current Amps
Wire Size (AWG) vs Wire Length (3% drop)
1-5 ft.
5-10 ft.
10-15 ft.
15-20 ft.
25-30 ft.
5
18
18
18
16
14
10
18
16
14
14
12
15
18
14
12
12
10
20
16
14
12
10
8