INSTALLATION SUMMARY
When installing multiple indoor units to a single outdoor unit, ensure that the length of the refrigerant pipe
and the drop height between the indoor and outdoor units meet the following requirements:
INSTALLATION INSTRUCTIONS
49ft (15m)
49ft (15m)
32.8ft (10m)
Outdoor Unit
Outdoor Unit
Outdoor Unit
Indoor Unit
Indoor units that can be used in combination Number of connected units 1 - 5 units
Compressor stop/start frequency
Stop time
3 minutes or more
Power source voltage
Voltage fl uctuation
within ± 10% of rated voltage
Voltage drop during start
within ± 15% of rated voltage
Interval unbalance
within ± 3% of rated voltage
Units are in meters/feet
1 drive 2 1 drive 3 1 drive 4 1 drive 5
Max. length for all rooms
40/131
60/197
80/262
80/262
Max. length for one indoor unit
25/82
30/98
35/115
35/115
Max. height difference between indoor and outdoor
15/49
15/49
15/49
15/49
Max. height difference between indoor units
10/33
10/33
10/33
10/33